Vous êtes sur la page 1sur 87

This document is the exclusive property of Alstom Grid and shall not be

transmitted by any means, copied, reproduced or modified without the prior


written consent of Alstom Grid Technical Institute. All rights reserved.
GRID
Technical Institute
Analysis of Unbalanced Faults
> Analysis of Unbalanced Fults 2
Fault Types
Line - Ground (65 - 70%)

Line - Line - Ground (10 - 20%)

Line - Line (10 - 15%)

Line - Line - Line (5%)

Statistics published in 1967 CEGB Report, but are similar today
all over the world.
> Analysis of Unbalanced Fults 3
Fault Incidence
85% of faults are overhead line faults.

50% of these due to lightning strikes.
> Analysis of Unbalanced Fults 4
Unbalanced Faults (1)
In three phase fault calculations, a single phase
representation is adopted
3 phase faults are rare
Majority of faults are unbalanced faults
UNBALANCED FAULTS may be classified into
SHUNT FAULTS and SERIES FAULTS
SHUNT FAULTS
Line to Ground
Line to Line
Line to Line to Ground
SERIES FAULTS
Single Phase Open Circuit
Double Phase Open Circuit
> Analysis of Unbalanced Fults 5
Unbalanced Faults (2)
LINE TO GROUND
LINE TO LINE
LINE TO LINE TO GROUND

Causes :

1) Insulation Breakdown
2) Lightning Discharges and other Overvoltages
3) Mechanical Damage
> Analysis of Unbalanced Fults 6
Unbalanced Faults (3)
OPEN CIRCUIT OR SERIES FAULTS

Causes :

1) Broken Conductor
2) Operation of Fuses
3) Maloperation of Single Phase Circuit Breakers


DURING UNBALANCED FAULTS, SYMMETRY OF SYSTEM
IS LOST

SINGLE PHASE REPRESENTATION IS NO LONGER VALID
> Analysis of Unbalanced Fults 7
Unbalanced Faults (4)
Analysed using :-

Symmetrical Components
Equivalent Sequence Networks of Power System
Connection of Sequence Networks appropriate to Type
of Fault
> Analysis of Unbalanced Fults 8
Symmetrical Components
Fortescue discovered a property of unbalanced phasors

n phasors may be resolved into :-
(n-1) sets of balanced n-phase systems of phasors, each set
having a different phase sequence
plus
1 set of zero phase sequence or unidirectional phasors

V
A
= V
A1
+ V
A2
+ V
A3
+ V
A4
- - - - - V
A(n-1)
+ V
An

V
B
= V
B1
+ V
B2
+ V
B3
+ V
B4
- - - - - V
B(n-1)
+ V
Bn

V
C
= V
C1
+ V
C2
+ V
C3
+ V
C4
- - - - - V
C(n-1)
+ V
Cn

V
D
= V
D1
+ V
D2
+ V
D3
+ V
D4
- - - - - V
D(n-1)
+ V
Dn

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
V
n
= V
n1
+ V
n2
+ V
n3
+ V
n4
- - - - - V
n(n-1)
+ V
nn


(n-1) x Balanced 1 x Zero
Sequence
> Analysis of Unbalanced Fults 9
Unbalanced 5-Phase System of Voltages (1)
This can be resolved into :-














First Set of Balanced Second Set of
Phasors Balanced Phasors
V
A1

2

V
E1

V
D1

V
C1

V
B1

V
A2

V
C2

V
E2

V
B2

V
D2

> Analysis of Unbalanced Fults 10
Unbalanced 5-Phase System of Voltages (2)
Third Set of Balanced Fourth Set of
Phasors Balanced Phasors
4
3
V
A4

V
B4

V
C4
V
D4

V
E4

V
A3

V
D
3

V
B3

V
E3

V
C3

> Analysis of Unbalanced Fults 11
Unbalanced 5-Phase System of Voltages (3)
Fifth Set of Zero
Sequence Phasors
V
A5

V
B5

V
D5

V
E5

V
C5

> Analysis of Unbalanced Fults 12
Unbalanced 3-Phase System of Voltages (1)
This can be resolved into :-









First Set of Balanced Second Set of
Phasors Balanced Phasors
V
A1
V
C1
120
V
B1
V
A2
V
B2
V
C2
240
> Analysis of Unbalanced Fults 13
Unbalanced 3-Phase System of Voltages (2)
Third Set of Zero
Sequence Phasors
V
A3

V
B3

V
C3

> Analysis of Unbalanced Fults 14
Unbalanced 3-Phase System (1)
V
A
= V
A1
+ V
A2
+ V
A0

V
B
= V
B1
+ V
B2
+ V
B0
V
C
= V
C1
+ V
C2
+ V
C0












Positive Sequence Negative Sequence
V
A1
V
C1
120
V
B1
V
A2
V
B2
V
C2
240
> Analysis of Unbalanced Fults 15
Unbalanced 3-Phase System (2)
Zero Sequence
V
A0

V
B0

V
C0

> Analysis of Unbalanced Fults 16
Symmetrical Components
Phase Positive + Negative + Zero
V
A
V
A1
+

V
A2
+ V
A0
V
B
V
B1
+

V
B2
+ V
B0
V
C
V
C1
+

V
C2
+ V
C0

V
A

V
B

V
C

+
+
V
B1

V
C1

V
A1

V
B2

V
C2

V
C0
V
B0
V
A0

V
A2

V
B1
=

a
2
V
A1
V
B2
=

a V
A2
V
B0
=

V
A0
V
C1
=

a V
A1
V
C2
=

a
2
V
A2
V
C0
=

V
A0
=
=
=
> Analysis of Unbalanced Fults 17
Converting from Sequence Components
to Phase Values
V
A
= V
A1
+ V
A2
+ V
A0
V
B
= V
B1
+ V
B2
+ V
B0
= a
2
V
A1
+ a V
A2
+ V
A0
V
C
= V
C1
+ V
C2
+ V
C0
= a V
A1
+ a
2
V
A2
+ V
A0

V
A0

V
C1

V
C

V
A2

V
A1

V
A

V
C0

V
C2

V
B2

V
B0

V
B1

V
B

> Analysis of Unbalanced Fults 18
Converting from Phase Values
to Sequence Components
V
A1
= 1/3 {V
A
+ a V
B
+ a
2
V
C
}
V
A2
= 1/3 {V
A
+ a
2
V
B
+ a V
C
}
V
A0
= 1/3 {V
A
+ V
B
+ V
C
}


V
C

3V
A0

V
B

V
A0

V
A

> Analysis of Unbalanced Fults 19
Add V
A
, V
B
, V
C
vectorially
V
A
= V
A1
+ V
A2
+ V
A0

V
B
= a
2
V
A1
+ a V
A2
+ V
A0
V
C
= a V
A1
+ a
2
V
A2
+ V
A0

V
A
+ V
B
+ V
C
= 0 + 0 + 3V
A0

V
A0
= 1/3 (V
A
+ V
B
+ V
C
)

Add V
A
, aV
B
and a
2
V
C
vectorially
V
A
= V
A1
+ V
A2
+ V
A0

a V
B
= V
A1
+ a
2
V
A2
+ a V
A0
a
2
V
C
= V
A1
+ a V
A2
+ a
2
V
A0

V
A
+ aV
B
+ a
2
V
C
= 3V
A1
+ 0 + 0

V
A1
= 1/3 (V
A
+ a V
B
+ a
2
V
C
)

> Analysis of Unbalanced Fults 20
Add V
A
, a
2
V
B
and aV
C
vectorially

V
A
= V
A1
+ V
A2
+ V
A0

a
2
V
B
= a V
A1
+ V
A2
+ a
2
V
A0
a V
C
= a
2
V
A1
+ V
A2
+ a V
A0

V
A
+ a
2
V
B
+ V
C
= 0 + 3V
A2
+ 0



V
A2
= 1/3 (V
A
+ a
2
V
B
+ aV
C
)
> Analysis of Unbalanced Fults 21
V
A
= V
A1
+ V
A2
+ V
A0
V
B
= a
2
V
A1
+ a V
A2
+ V
A0
V
C
= a V
A1
+ a
2
V
A2
+ V
A0

I
A
= I
A1
+ I
A2
+ I
A0
I
B
= a
2
I
A1
+ a I
A2


+ I
A0
I
C
= a I
A1
+ a
2
I
A2
+ I
A0


V
A1
= 1/3 {V
A
+ a V
B
+ a
2
V
C
}
V
A2
= 1/3 {V
A
+ a
2
V
B
+ a V
C
}
V
A0
= 1/3 {V
A
+ V
B
+ V
C
}

I
A1
= 1/3 { I
A
+ a I
B
+ a
2
I
C
}
I
A2
= 1/3 { I
A
+ a
2
I
B
+

a I
C
}
I
A0
+ 1/3 { I
A
+ I
B
+ I
C
}
> Analysis of Unbalanced Fults 22
Residual Current
Used to detect earth faults











* I
RESIDUAL
is zero for :- * I
RESIDUAL
is present for :-

Balanced Load /E Faults
3 Faults //E Faults
/ Faults
I
A

I
RESIDUAL
= I
A
+

I
B
+
I
C
= 3I
0

I
B

I
C

E/F
> Analysis of Unbalanced Fults 23
Residual Voltage
Used to detect earth faults


Residual voltage is measured from
Open Delta or Broken Delta VT
secondary windings.
V
RESIDUAL
is zero for:-
Healthy unfaulted systems
3C Faults
C/C Faults
V
RESIDUAL
is present for:-
C/E Faults
C/C/E Faults
Open Circuits (on supply
side of VT with earthed source)
V
RESIDUAL

= V
A
+

V
B
+V
C
= 3V
0

> Analysis of Unbalanced Fults 24
Example
Evaluate the positive, negative and zero sequence components
for the unbalanced phase vectors :

V
A
= 1Z0
V
B
= 1.5 Z-90
V
C
= 0.5 Z120

V
C

V
A

V
B

> Analysis of Unbalanced Fults 25
Solution
V
A1
= 1/3 (V
A
+ aV
B
+ a
2
V
C
)
= 1/3 | 1 + (1 Z120) (1.5 Z-90)
+ (1 Z240) (0.5 Z120) |
= 0.965 Z15

V
A2
= 1/3 (V
A
+ a
2
V
B
+ aV
C
)
= 1/3 | 1 + (1 Z240) (1.5 Z-90)
+ (1 Z120) (0.5 Z120) |
= 0.211 Z150

V
A0
= 1/3 (V
A
+ V
B
+ V
C
)
= 1/3 (1 + 1.5 Z-90 + 0.5 Z120)
= 0.434 Z-55

> Analysis of Unbalanced Fults 26
Positive Sequence Voltages
V
C1
= aV
A1

15
V
A1
=
0.965Z15
V
B1
=
a
2
V
A1

> Analysis of Unbalanced Fults 27
Zero Sequence
Voltages
Negative Sequence
Voltages
V
A0
= 0.434Z-
55
V
B0
= -
V
C0
= -

-55
V
C2
= a
2
V
A2

150
V
B2
= a V
A2

V
A2
=
0.211Z150
> Analysis of Unbalanced Fults 28
Symmetrical Components
V
C1

V
A1

V
B1

V
C2

V
A2

V
B2

V
C0

V
A0

V
B0

V
A2

V
C2

V
B2

V
C

V
A

V
0

V
B

> Analysis of Unbalanced Fults 29
Example (1)
Evaluate the phase quantities I
A
, I
B
and I
C
from the
sequence components
I
A1
= 0.6 Z0
I
A2
= -0.4 Z0
I
A0
= -0.2 Z0

Solution
I
A
= I
A1
+ I
A2
+ I
A0
= 0
I
B
= a
2
I
A1
+ aI
A1
+ I
A0

= 0.6Z240 - 0.4Z120 - 0.2Z0 = 0.91Z-109
I
C
= aI
A1
+ a
2
I
A2
+ I
A0

= 0.6Z120 - 0.4Z240 - 0.2Z0 = 0.91Z+109
> Analysis of Unbalanced Fults 30
Example (2)
I
C

I
B

109
109
> Analysis of Unbalanced Fults 31
POSITIVE
I
A1
NEGATIVE
I
B1
I
C1
I
A2
I
B2
I
C2
I
C1
I
B1
I
A1
I
A2
I
B2
I
C2
> Analysis of Unbalanced Fults 32
PHASE
ZERO
I
A0

I
B0

I
C0

I
B

I
C

I
C

I
B

I
A0

I
B0

I
C0

> Analysis of Unbalanced Fults 33
Sequence Components (1)
Any 3 phase system of vectors may be represented as the sum of
3 sets of symmetrical vectors :-
3 PHASE
VECTORS
EQUIVALENT SYMMETRICAL COMPONENTS
POSITIVE PHASE
SEQUENCE (PPS)
ZERO PHASE
SEQUENCE
I
2

BALANCED LOAD
OR 3-PHASE FAULT
/I
A
/ = /I
B
/ = /I
C
/ = I
F

I
0
= 0
I
2
= 0
I
1
= I
F

NEGATIVE PHASE
SEQUENCE (NPS)
I
1

I
A

I
C

I
B

I
0

I
A1

I
C1
I
B1

> Analysis of Unbalanced Fults 34
Sequence Components (2)
PHASE-PHASE
FAULT /I
A
/=/I
B
/ = I
F

I
A

I
B

I
0
= 0
I
A1

I
C1

I
B1

I
A2

I
C2

I
B2

I
1
= I
F

\3
I
2
= I
F

\3
> Analysis of Unbalanced Fults 35
Sequence Components (3)
PHASE-EARTH
FAULTS
/I
A
/ OR /I
C
/ = I
F

I
A

I
C

I
B2

I
C2
I
A2

I
A0
I
C0
I
B0

I
A1

I
C1

I
B1

I
A2

I
B2

I
C2

I
A1

I
C1

I
B1

I
1
= I
F

3
I
2
= I
F

3
I
0
= I
F

3
I
A0

I
C0

I
B0

> Analysis of Unbalanced Fults 36
Sequence Networks
It can be shown that providing the system impedances are
balanced from the points of generation right up to the fault, each
sequence current causes voltage drop of its own sequence only.

Regard each sequence current flowing within its own network
thro impedances of its own sequence only, with no
interconnection between the sequence networks right up to the
point of fault.
> Analysis of Unbalanced Fults 37
Unbalanced Voltages and Currents acting on
Balanced Impedances
Z
S

I
A

V
A

Z
M

Z
M

Z
S

I
B

V
B

Z
M

Z
S

I
C

V
C

V
A
= I
A
Z
S
+

I
B
Z
M
+

I
C
Z
M
V
B
= I
A
Z
M
+

I
B
Z
S
+

I
C
Z
M
V
C
= I
A
Z
M
+

I
B
Z
M
+

I
C
Z
S
In matrix form

V
A
Z
S
Z
M
Z
M
I
A
V
B
= Z
M
Z
S
Z
M
I
B
V
C
Z
M
Z
M
Z
S
I
C
> Analysis of Unbalanced Fults 38
Resolve V & I phasors into symmetrical components

1 1 1 V
0
Z
S
Z
M
Z
M
1 1 1 I
0
1 a
2
a V
1
= Z
M
Z
S
Z
M
1 a
2
a

I
1
1 a a
2
V
2
Z
M
Z
M
Z
S
1 a a
2
I
2

Multiply by [A]
-1


V
0
1 1 1 Z
S
Z
M
Z
M
1 1 1 I
0
V
1
=

1 a
2
a Z
M
Z
S
Z
M
1 a
2
a I
1
V
2
1 a a
2
Z
M
Z
M
Z
S
1 a a
2
I
2

V
0
1 1 1 Z
S
Z
M
Z
M
1 1 1 I
0
V
1
= 1/3

1 a a
2
Z
M
Z
S
Z
M
1 a
2
a I
1
V
2
1 a
2
a Z
M
Z
M
Z
S
1 a a
2
I
2


V
0
Z
S
+ 2Z
M
Z
S
+ 2Z
M
Z
S
+

2Z
M

V
1
= 1/3

Z
S
- Z
M
Z
M
+ a Z
S
+ a
2
Z
M
Z
M
+ aZ
M
+ a
2
Z
S
V
2
Z
S
- Z
M
Z
M
+ a
2
Z
S
+ a Z
M
Z
M
+ a
2
Z
M
+ a Z
S

1 1 1 I
0
1 a
2
a I
1
1 a a
2
I
2

-1
> Analysis of Unbalanced Fults 39
V
0
Z
S
+ 2Z
M
0 0 I
0

V
1
=

0

Z
S
- Z
M
0 I
1
V
2
0 0

Z
S
- Z
M
I
2

V
0
Z
0
0 0 I
0

V
1
=

0

Z
1
0 I
1
V
2
0 0

Z
2
I
2


The symmetrical component impedance matrix is a
diagonal matrix if system is symmetrical.
The sequence networks are independent of each other.
The three isolated sequence networks are
interconnected when an unbalance such as a fault or
unbalanced loading is introduced.
> Analysis of Unbalanced Fults 40
Phase Sequence Equivalent Circuits (1)
Positive Sequence Impedance
E
Q P
a
2
E
aE
Z
1
= E/I
Q
1
P
1
I
a
2
I
aI
> Analysis of Unbalanced Fults 41
Phase Sequence Equivalent Circuits (2)
Negative Sequence Impedance
For static non-rotating plant :- Z
2
= Z
1

E
Q P
a
2
E
aE
Z
2
= E/I
Q
2
P
2

I
a
2
I
aI
> Analysis of Unbalanced Fults 42
Phase Sequence Equivalent Circuits (3)
Zero Sequence Impedance
I
I
I 3I
E
Q P
Z
0
= E/I
P
0
Q
0
> Analysis of Unbalanced Fults 43
Sequence Networks
+ve, -ve and zero sequence networks are drawn for a
reference phase. This is usually taken as the A phase.

Faults are selected to be balanced relative to the reference
A phase.
e.g. For /E faults consider an A-E fault
For / faults consider a B-C fault

Sequence network interconnection is the simplest for the
reference phase.
> Analysis of Unbalanced Fults 44
Positive Sequence Diagram
1. Start with neutral point N
1

- All generator and load neutrals are connected to N
1
2. Include all source EMFs
- Phase-neutral voltage
3. Impedance network
- Positive sequence impedance per phase
4. Diagram finishes at fault point F
1

Z
1

N
1

E
1

F
1

> Analysis of Unbalanced Fults 45
Example
V
1
= Positive sequence /N voltage at fault point
I
1
= Positive sequence phase current flowing into F
1

V
1
= E
1
- I
1
(Z
G1
+ Z
T1
+ Z
L1
)
E
1

F
1

I
1

Z
L1
Z
G1
Z
T1

N
1

(N
1
)
V
1

Line
F
N
E
R
Generator Transformer
> Analysis of Unbalanced Fults 46
Negative Sequence Diagram
1. Start with neutral point N
2

- All generator and load neutrals are connected to N
2
2. No EMFs included
- No negative sequence voltage is generated!
3. Impedance network
- Negative sequence impedance per phase
4. Diagram finishes at fault point F
2

Z
2

N
2
F
2

> Analysis of Unbalanced Fults 47
Example
V
2
= Negative sequence /N voltage at fault point
I
2
= Negative sequence phase current flowing into F
2
V
2
= -I
2
(Z
G2
+ Z
T2
+ Z
L2
)
F
2

I
2

Z
L2
Z
G2
Z
T2

N
2

(N
2
)
V
2

Line
F
N
E
R
Generator Transformer
System Single Line
Diagram
Negative Sequence Diagram
> Analysis of Unbalanced Fults 48
Zero Sequence Diagram (1)
For In Phase (Zero Phase Sequence) currents to flow in each
phase of the system, there must be a fourth connection (this is
typically the neutral or earth connection).
I
A0
+

I
B0
+

I
C0
=

3I
A0

I
A0

N
I
B0

I
C0

> Analysis of Unbalanced Fults 49
Zero Sequence Diagram (2)
Resistance Earthed System :-
3I
A0

N
E
R
Zero sequence voltage between N & E given by
V
0
= -3I
A0
. R
Zero sequence impedance of neutral to earth path
Z
0
= V
0
= 3R
-I
A0
> Analysis of Unbalanced Fults 50
Transformer Zero Sequence Impedance
Q
P
Z
T0

a a
Q
P
b b
N
0

> Analysis of Unbalanced Fults 51
General Zero Sequence Equivalent Circuit
for Two Winding Transformer
Secondary
Terminal 'a'
'a'
Primary
Terminal
'b' 'b'
N
0
Z
T0
On appropriate side of transformer :

Earthed Star Winding - Close link a
Open link b

Delta Winding - Open link a
Close link b

Unearthed Star Winding - Both links open
> Analysis of Unbalanced Fults 52
Zero Sequence Equivalent
Dy Tx (1)
3I
0

No zero sequence
in line connection
on A side
I
0

I
0

I
0

> Analysis of Unbalanced Fults 53
Zero Sequence Equivalent
Dy Transformer (2)
side
terminal
A side
terminal
Z
T0

N
0
(E
0
)
I
0

Thus, equivalent single phase zero sequence diagram :-
> Analysis of Unbalanced Fults 54
Zero Sequence Equivalent Circuits (1)
S
0

Z
T0

N
0

P
0

P S
a
a
b b
> Analysis of Unbalanced Fults 55
Zero Sequence Equivalent Circuits (2)
S
0

Z
T0

N
0

P
0

P S
a
a
b b
> Analysis of Unbalanced Fults 56
Zero Sequence Equivalent Circuits (3)
S
0

Z
T0

N
0

P
0

P S
a
a
b b
> Analysis of Unbalanced Fults 57
Zero Sequence Equivalent Circuits (4)
S
0

Z
T0

N
0

P
0

P S
a
a
b b
> Analysis of Unbalanced Fults 58
Zero Sequence Diagram
V
0
= Zero sequence PH-E voltage at fault point
I
0
= Zero sequence current flowing into F
0

V
0
= -I
0
(Z
T0
+ Z
L0
+ 3R
T
)
F
0

I
0

Z
L0
Z
G0
Z
T0

N
0

N
0

V
0

Line
F
N
E
R
Generator Transformer
System Single Line
Diagram
Zero Sequence Network
3R
E
0

3R
T

R
T

> Analysis of Unbalanced Fults 59
Zig-Zag Earthing Transformers (1)
Positive (and negative) sequence impedance is very high.
Equivalent Circuit :

P
N
E
R
P
1

N
1

> Analysis of Unbalanced Fults 60
Zig-Zag Earthing Transformers (2)
Zero sequence impedance is very low.
Equivalent Circuit

P
0

Z
T0

3R
N
0
(E
0
)
> Analysis of Unbalanced Fults 61
Summary of Sequence Diagrams (1)
System Single Line Diagram
R
E
N
GENERATOR
TRANSFORMER
LINE
F
> Analysis of Unbalanced Fults 62
Summary of Sequence Diagrams (2)
Positive Sequence
(N
1
)
V
1

F
1

Z
L1
Z
T1
Z
G1

E
1

N
1

I
1

> Analysis of Unbalanced Fults 63
Summary of Sequence Diagrams (3)
Negative Sequence
(N
2
)
V
2

F
2

Z
L2
Z
T2
Z
G2

N
2

I
2

> Analysis of Unbalanced Fults 64
Summary of Sequence Diagrams (4)
Zero Sequence
E
0
(N
0
)
V
0

F
0

Z
L0
Z
T0
Z
G0

3R
N
0

I
0

> Analysis of Unbalanced Fults 65
Interconnection of Sequence Networks
Consider sequence networks as blocks with fault terminals F & N for
external connections.

F
1

POSITIVE
SEQUENCE
NETWORK
N
1

F
2

NEGATIVE
SEQUENCE
NETWORK
N
2

F
0

ZERO
SEQUENCE
NETWORK
N
0

I
2

V
2

I
0

V
0

I
1

V
1

> Analysis of Unbalanced Fults 66
Interconnection of Sequence Networks
For any given fault there are 6 quantities to be considered at the fault point
i.e. V
A
V
B
V
C
I
A
I
B
I
C
Relationships between these for any type of fault can be converted into an
equivalent relationship between sequence components
V
1
, V
2
, V
0
and I
1
,

I
2
,

I
0
This is possible if :-
1) Any 3 phase quantities are known (provided they are not all
voltages or all currents)
or 2) 2 are known and 2 others are known to have a specific
relationship.
From the relationship between sequence Vs and Is, the manner in
which the isolation sequence networks are connected can be determined.
The connection of the sequence networks provides a single phase
representation (in sequence terms) of the fault.
> Analysis of Unbalanced Fults 67
To derive the system constraints at the fault terminals :-

I
A

V
A

I
B
I
C

V
B

V
C

F
Terminals are connected to represent the fault.

A
B
C
> Analysis of Unbalanced Fults 68
I
A
V
A
I
B
I
C
V
B
V
C
Phase to Earth Fault on Phase A
At fault point :-

V
A
= 0

V
B
= ?

V
C
= ?

I
A
= ?
I
B
= 0
I
C
= 0

A
B
C
> Analysis of Unbalanced Fults 69
Phase to Earth Fault on Phase A
At fault point
V
A
= 0

;

I
B
= 0 ; I
C
= 0
but V
A
= V
1
+ V
2
+ V
0

V
1
+ V
2
+ V
0
= 0

------------------------- (1)
I
0
= 1/3 (I
A
+

I
B
+ I
C
) = 1/3 I
A
I
1
= 1/3 (I
A
+

aI
B
+

a
2
I
C
) = 1/3 I
A
I
2
= 1/3 (I
A
+

a
2
I
B
+

aI
C
) = 1/3 I
A
I
1
= I
2
=

I
0
= 1/3 I
A
------------------------- (2)
To comply with (1) & (2) the sequence networks must be connected in series :-

I
1

F
1

N
1

V
1

+ve
Seq
N/W
I
2

F
2

N
2

V
2

-ve
Seq
N/W
I
0

F
0

N
0

V
0

Zero
Seq
N/W
> Analysis of Unbalanced Fults 70
Example : Phase to Earth Fault
SOURCE
LINE F
132 kV
2000 MVA
Z
S1
= 8.7O
Z
S0
= 8.7O
A - G
FAULT
Z
L1
= 10O
Z
L0
= 35O
Total impedance = 81.1O

I
1
= I
2
= I
0
= 132000 = 940 Amps
\3 x 81.1

I
F
= I
A
= I
1
+ I
2
+ I
0

= 3I
0

= 2820 Amps
I
F

8.7 10
I
1

F
1

N
1

8.7 10
I
2

F
2

N
2

8.7 35
I
0

F
0

N
0

> Analysis of Unbalanced Fults 71
I
A
V
A
I
B
I
C
V
B
V
C
Earth Fault with Fault Resistance
At fault point :-

V
A
= I
A
Z
F


V
B
= ?


V
C
= ?

I
A
= ?

I
B
= 0

I
C
= 0

Z
F

> Analysis of Unbalanced Fults 72
Earth Fault with Fault Resistance
At fault point
V
A
= I
A
Z
F
; I
B
= 0 ; I
C
= 0

I
0
= 1/3 (I
A
+ I
B
+ I
C
)
=
1/3 I
A
I
1
= 1/3 (I
A
+

aI
B
+

a
2
I
C
) = 1/3 I
A
I
2
= 1/3 (I
A
+

a
2
I
B
+

aI
C
) = 1/3 I
A


I
1
= I
2
=

I
0
------------------------- (1)
Since V
A
= I
A
Z
F
:-
V
1
+ V
2
+ V
0
= (I
1
+ I
2
+ I
0
)

Z
F
= 3I
0
Z
F
V
1
+ V
2
+ V
0
= 3I
0
Z
F


------------ (2)

F
1

POSITIVE
SEQUENCE
NETWORK
N
1

F
2

NEGATIVE
SEQUENCE
NETWORK
N
2

F
0

ZERO
SEQUENCE
NETWORK
N
0

I
2

V
2

I
0

V
0

I
1

V
1

3Z
F

> Analysis of Unbalanced Fults 73
I
A
V
A
I
B
I
C
V
B
V
C
Phase to Phase Fault :- B-C Phase
At fault point :-

V
A
= ?



V
B
= V
C



I
A
= 0

I
B
+ I
C
= 0


> Analysis of Unbalanced Fults 74
Phase to Phase Fault :- B-C Phase
At fault point
V
B
= V
C
;

I
A
= 0

;

I
B
+ I
C
= 0
I
0
= 1/3 (I
A
+

I
B
+ I
C
) = 0
I
0
= 0

---- (1)
I
1
= 1/3 (I
A
+

aI
B
+ a
2
I
C
) = 1/3 (a

- a
2

)I
B
I
2
= 1/3 (I
A
+

a
2
I
B
+

aI
C
) = -1/3 (a

- a
2

)I
B
I
1
+

I
2
= 0

------- (2)

V
1
= 1/3 (V
A
+ aV
B
+ a
2
V
C
) = 1/3 (V
A
- V
B
)


V
2
= 1/3 (V
A
+ a
2
V
B
+ aV
C
) = 1/3 (V
A
- V
B
)

V
1
= V
2
------------------------ (3)

From equations (1), (2) and (3) the positive and negative sequence networks are
connected in parallel and the zero sequence network is unconnected.
I
1

F
1

N
1

V
1

+ve
Seq
N/W
I
2

F
2

N
2

V
2

-ve
Seq
N/W
I
0

F
0

N
0

V
0

Zero
Seq
N/W
> Analysis of Unbalanced Fults 75
Phase to Phase Fault Current Level

For a / Fault ,assuming Z
1
= Z
2
:-


I
1
= -I
2
= E
2Z
1
I
A
= I
1
+ I
2
+ I
0
= 0
I
B
= a
2
I
1
+ aI
2
+ I
0
= (a
2

- a)I
1
= -j\3 . E
2 Z
1
I
C
= aI
1
+ a
2
I
2
+ I
0
= (a

- a
2
)I
1
= j\3 . E
2 Z
1
I
F(/)
= 0.866 I
F(3)
E
I
1
I
2
Z
1

Z
2

A
B
C
I
B
I
C
E
C
E
B
E
A
> Analysis of Unbalanced Fults 76
Example : Phase to Phase Fault
SOURCE
LINE F
132 kV
2000 MVA
Z
S1
= Z
S2
= 8.7O
B - C
FAULT
Z
L1
= Z
L2
= 10O
8.7 10
8.7
10
I
1

I
2

F
1

N
1

F
2

N
2

132000
\3
Total impedance = 37.4O I
B
= a
2
I
1
+ aI
2
I
1
= 132000 = 2037 Amps = a
2
I
1
- aI
1

\3 x 37.4 = (a
2

- a) I
1
I
2
= -2037 Amps = (-j) . \3 x 2037
= 3529 Amps
> Analysis of Unbalanced Fults 77
I
A

V
A

I
B
I
C

V
B
V
C

Phase to Phase Fault with Resistance
At fault point :-

V
A
= ?


V
B
- V
C
=
I
B
Z
F


I
A
= 0

I
B
+ I
C
= 0

Z
F

> Analysis of Unbalanced Fults 78
Phase to Phase Fault with Resistance
At fault point
I
A
= 0

;

I
B
+ I
C
= 0 ; V
B
- V
C
= I
B
Z
F

I
0
= 1/3 (I
A
+

I
B
+ I
C
) = 0
I
1
= 1/3 (I
A
+

aI
B
+

a
2
I
C
) = 1/3 (a

- a
2

) I
B
I
2
= 1/3 (I
A
+

a
2
I
B
+

aI
C
) = - 1/3 (a

- a
2

) I
B


I
0
= 0

----------- (1)
I
1
+ I
2
= 0
I
B
= a
2
I
1
+

aI
2
+ I
0
= (a
2
- a) I
1

V
B
- V
C
= (a
2
V
1
+ aV
2
+ V
0
) - (aV
1
+ a
2
V
2
+ V
0
)


= (a
2

-

a) V
1
- (a
2

-

a) V
2

but V
B
- V
C
= I
B
Z
F
= (a
2

-

a) I
1
Z
F
(a
2

-

a) I
1
Z
F
= (a
2

-

a) V
1
- (a
2

-

a) V
2

V
1
- V
2
= I
1
Z
F
------------ (2)

I
1

F
1

N
1

V
1

+ve
Seq
N/W
I
2

F
2

N
2

V
2

-ve
Seq
N/W
I
0

F
0

N
0

V
0

Zero
Seq
N/W
Z
F

> Analysis of Unbalanced Fults 79
I
A
V
A
I
B
I
C
V
B
V
C
Phase to Phase to Earth Fault :- B-C-E
At fault point :-

V
A
= ?

V
B
= 0

V
C
= 0

I
A
= 0
I
B


= ?
I
C


= ?

> Analysis of Unbalanced Fults 80
Phase to Phase to Earth Fault :- B-C-E
At fault point
V
B
= 0

; V
C
= 0 ; I
A
= 0

V
1
= 1/3 (V
A
+ aV
B
+ a
2
V
C
) = 1/3 V
A
V
2
= 1/3 (V
A
+ a
2
V
B
+ aV
C
) = 1/3 V
A
V
0
= 1/3 (V
A
+ V
B
+ V
C
) = 1/3 V
A

V
1
= V
2
= V
0
= 1/3 V
A
-------------------- (1)

I
A
= I
1
+ I
2
+

I
0
= 0 ------------------------------- (2)

From equations (1) & (2) the sequence networks are connected in parallel.
I
1

F
1

N
1

V
1

+ve
Seq
N/W
I
2

F
2

N
2

V
2

-ve
Seq
N/W
I
0

F
0

N
0

V
0

Zero
Seq
N/W
> Analysis of Unbalanced Fults 81
I
A
V
A
I
B
I
C
V
B
V
C
Phase to Phase to Earth Fault
B-C-E with Fault Resistance
At fault point :-

V
A
= ?

V
B
= (I
B
+

I
C
) Z
F


V
C
= (I
B
+

I
C
) Z
F


I
A
= 0
I
B


= ?
I
C


= ?
I
B
+ I
C
Z
F

> Analysis of Unbalanced Fults 82
Phase to Phase to Earth Fault
B-C-E with Resistance
At fault point
I
A
= 0 ; V
B
= V
C
= (I
B
+ I
C
)Z
F

I
A
= I
1
+

I
2
+ I
0
= 0

--------------------- (1)
I
0
= 1/3 (I
A
+ I
B
+

I
C
) = 1/3 (I
B
+ I
C
)
I
B
+ I
C
= 3I
0
V
1
= 1/3 (V
A
+ aV
B
+ a
2
V
C
) = 1/3 [V
A
+ (a
2
+ a)V
B
] = 1/3 (V
A
- V
B
)
V
2
= 1/3 (V
A
+ a
2
V
B
+ aV
C
) = 1/3 [V
A
+ (a
2
+ a)V
B
] = 1/3 (V
A
- V
B
)
V
1
= V
2
--------------------- (2)
V
0
= 1/3 (V
A
+ V
B
+ V
C
) = 1/3 (V
A
+ 2V
B
)
V
0
- V
1
= 1/3 (V
A
+ 2V
B
) - 1/3 (V
A
- V
B
)


= V
B
= (I
B
+

I
C
)Z
F
= 3I
0
Z
F
V
1
= V
0
- I
0
(3Z
F
) --------------------- (3)




I
1

F
1

N
1

V
1

+ve
Seq
N/W
I
2

F
2

N
2

V
2

-ve
Seq
N/W
I
0

F
0

N
0

V
0

Zero
Seq
N/W
3Z
F

> Analysis of Unbalanced Fults 83
4-wire Representation of
/E Fault (1)
Consider an earthed source.

Total sequence impedances to fault

= Z
1
, Z
2
, Z
0
i.e. Source + line



E
A

E
B

E
C

C
B
A
Z
1
, Z
2
, Z
0
> Analysis of Unbalanced Fults 84
4-wire Representation of /E Fault (2)
Sequence Networks

I
1

Z
1

I
2

I
0

Z
2

Z
0

E
3
Z Z
Z
E

3
Z Z
Z
3
Z 2Z

3
Z Z Z
E
3
) Z Z (Z E
1 0
1
A
1 0
1 A
0 1
A
0 2 1
A
1 0 2 1 A
0 2 1 1

+
= I
|
.
|

\
|

+ I =
|
.
|

\
|
+
I =
|
.
|

\
|
+ +
I =
I = I + I + I = I
+ + I =
4 Wire Equivalent Circuit
E
A

E
B

E
C

Z
1

Z
1

Z
1

Z
N
= Z
0
- Z
1
3


1 0
N

N 1
A F
3
Z - Z
Z
where
Z Z
E
I I
=
+
= =
> Analysis of Unbalanced Fults 85
3 Versus 1 Fault Level (1)
X
g

X
T

E
X
g
X
T

E
Z
1
I
F

3
1 T g
F
Z
E

X X
E

+
=
> Analysis of Unbalanced Fults 86
3 Versus 1 Fault Level (2)
Z
0
I
F

1
X
g1

X
T1

E
Z
2
= Z
1

Z
1
X
g2

X
T2

X
g0

X
T0

I =
+
3E

F
2Z Z
1 0
> Analysis of Unbalanced Fults 87
3 Versus 1 Fault Level (3)
LEVEL FAULT 3 LEVEL FAULT 1
Z Z IF
Z 2Z
3E
LEVEL FAULT 1
Z 2Z
3E

3Z
3E

Z
E
LEVEL FAULT 3
1 0
0 1
1 1 1 1
C > C
<
+
= C
+
= = = C

Vous aimerez peut-être aussi