CT CB
CB - Circuit Breaker
PT CT - Current
Transformer
Relay PT - Potential
Transformer
Number of relays often large:
Each phase, each fault type
T
ime
Trip Constant delay
characteristic
T
1 Relative
overcurre
nt
Electric Power Systems P9 - Olof Samuelsson 6
Time-delay overcurrent relay
Detect overcurrent – Wait delay time T(I) – Trip CB
T
ime
Trip Inverse 1/t characteristic
Similar for fuses
1 Relative
overcurre
nt
Electric Power Systems P9 - Olof Samuelsson 7
Radial system
•ISC increases when approaching source
•R1 has higher current setting than R2
CB1 T
R1
ime
R2 Load
CB2 1
R1
R2
Relative
Load
2
overcurre
nt
Electric Power Systems P9 - Olof Samuelsson 8
Fault in radial system
• Both R1 and R2 detect overcurrent
• Delay of R2 Time
• R2 operates CB2 first
CB1 – Isolates fault + Load 2
R1
– R1 reset
R2 L1
CB2 • If R2 or CB2 fails R1
– R2
R1 not reset
Curren
– Extra delay of R1
t
– R1 operates CB1
– Isolates fault + Load 1 and 2
Load
2
Electric Power Systems P9 - Olof Samuelsson 9
Coordination
Relays 1 and 2 coordinated in example:
Trip
R
Radius=|
Zline |
Electric Power Systems P9 - Olof Samuelsson 12
Impedance relay types
Directional Admittance or MHO
X Zlin X
e
Trip
Trip
R R
Distan
T ce
ime
Distan
ce
Electric Power Systems P9 - Olof Samuelsson 16
Recloser
– Fast and slow inverse characteristic
R – Fast is faster than fuses
• Saves downstream fuses
Load
• Open-reclose clears temporary faults
3 • Several attempts to reclose
– Slow is slower than fuse
Load • Burns downstream fuse if reclose fails
2
– Final reclose
• Permanent open if fault persists
Load
1 Electric Power Systems P9 - Olof Samuelsson 17
Automatic sectionalizer
– Replaces fuses
– Opens when recloser is open
R
• Need not interrupt fault current
S
• Operation not electrically powered
Load
3 – Recloses when energized
S • Upstream first
Load
• Recloser opens when fault energized
2 – Failing sectionalizer stays open
S
• Maximum area restored
Load • Radio message to repairman
1 Electric Power Systems P9 - Olof Samuelsson 18
Repairing permanent fault
– Protection has tripped CB
– Localize fault
• Relay data, visually, phone calls
– Open isolator and ground equipment
– Fault removed, line repaired
– Remove grounding and close isolator
– Line energized with CB