Overhead Distribution Systems

ABB PTMV - 1, 2013-12-19

ABB

Improving Distribution Reliability with Reclosers


The Example Distribution Circuit

Typical of suburban/rural circuits 10 miles of 3-Phase 13.8 kV Main Feeder

8 single-phase laterals, evenly distributed on the main feeder. Each lateral 3 miles long, and connected to the main feeder through a fuse
A total of 1800 customers (8 x 225 customers/lateral)
Distribution Substation
10 miles 3 miles 115 kV 13.8 kV

ABB PTMV - 2

ABB

Basic Radial System


Case 1
Substation
R

10 miles

Recloser

SAIFI: 1.6 int/cust/yr SAIDI: 3.3 hrs/yr MAIFI: 8.7 mom/yr SAIFI: 1.2 int/cust/yr SAIDI: 2.6 hrs/yr MAIFI: 6.5 mom/yr

Case 2
Substation
R

5 miles
R

5 miles

Recloser

Case 2 - with Single-Pole Reclosing


Single phase

Substation
R
ABB PTMV - 3

5 miles
R

5 miles

SAIFI: 1.1 int/cust/yr SAIDI: 2.3 hrs/yr MAIFI: 5.4 mom/yr

Recloser

ABB

Loop Configuration with Manual Switch

Case 3
Substation 1 5 miles
R

5 miles

Substation 2
R

Manual Tie Switch

SAIFI: 1.2 int/cust/yr SAIDI: 2.3 hrs/yr MAIFI: 6.5 mom/yr

ABB PTMV - 4

Assumptions Circuit breakers have reclosing capability Manual Tie Switch requires 1 hour to switch Reclosers require 1 minute to switch

ABB

Loop Configuration with Manual Switch

Case 3 - With Single-Pole Reclosing


Substation 1 5 miles
R

5 miles

Substation 2
R

Manual Tie Switch

SAIFI: 1.1 int/cust/yr SAIDI: 2.0 hrs/yr MAIFI: 5.4 mom/yr

ABB PTMV - 5

Assumptions Circuit breakers have reclosing capability Manual Tie Switch requires 1 hour to switch Reclosers require 1 minute to switch and have single-pole capability

ABB

Automatic Loop Restoration - 3 Reclosers


Case 4
Substation 1 5 miles
R

5 miles

N.C. Recloser Substation 2


R

N.O. Recloser

SAIFI: 1.0 int/cust/yr SAIDI: 2.1 hrs/yr MAIFI: 6.8 mom/yr

N.C. Recloser
N.C. - Normally-Closed N.O. - Normally-Open

ABB PTMV - 6

Assumptions Circuit breakers have reclosing capability Reclosers require 1 minute to switch

ABB

Automatic Loop Restoration - 3 Reclosers


Case 4 - With Single-Pole Reclosing

Substation 1

5 miles
R

5 miles

N.C. Recloser Substation 2


R

N.O. Recloser

SAIFI: 0.8 int/cust/yr SAIDI: 1.8 hrs/yr MAIFI: 3.1 mom/yr

N.C. Recloser
N.C. - Normally-Closed N.O. - Normally-Open

ABB PTMV - 7

Assumptions Circuit breakers have reclosing capability Reclosers require 1 minute to switch

ABB

Automatic Loop Restoration - 5 Reclosers


Case 5
Substation 1 3.3 miles
R

3.3 miles
R

3.3 miles

N.C. Recloser Substation 2


R

N.C. Recloser

N.O. Recloser

N.C. Recloser
N.C. - Normally-Closed N.O. - Normally-Open

N.C. Recloser

ABB PTMV - 8

Assumptions Circuit breakers have reclosing capability Reclosers require 1 minute to switch

SAIFI: 0.8 int/cust/yr SAIDI: 1.7 hrs/yr MAIFI: 6.5 mom/yr

ABB

Automatic Loop Restoration - 5 Reclosers


Case 5 - With Single-Pole Reclosing

Substation 1

3.3 miles
R

3.3 miles
R

3.3 miles

N.C. Recloser Substation 2


R

N.C. Recloser

N.O. Recloser

N.C. Recloser
N.C. - Normally-Closed N.O. - Normally-Open

N.C. Recloser

ABB PTMV - 9

Assumptions Circuit breakers have reclosing capability Reclosers require 1 minute to switch

SAIFI: 0.6 int/cust/yr SAIDI: 1.4 hrs/yr MAIFI: 2.7 mom/yr

ABB

Benefits of Single-Pole Reclosing


SAIFI 3-Pole Reclosing Single-Pole Reclosing 1.0 0.8 SAIDI 2.1 1.8 MAIFI 6.8 3.1

3-Recloser Automatic Loop Restoration

5-Recloser Automatic Loop Restoration

ABB PTMV - 10

3-Pole Reclosing Single-Pole Reclosing

0.8 0.6

1.7 1.4

6.5 2.7

ABB

Summary of Reclosing Benefits with Single Phase


Hrs/Yr %* Hrs/Yr %*
R

Case 1 - Substation reclosing 3.3 3 phase only


R

---

3.3

---

Single phase
R

Case 2 - Line Recloser

2.6

21% 2.3

30%

Case 3 - Loop with Manual Switch

2.3

30% 2.0

39%

R R R

Case 4 - 3-Recloser Automatic 2.1 Loop Restoration

36%

1.8

45%

R R

Case 5 - 5-Recloser Automatic 1.7 Loop Restoration

48%

1.4

58%

R
ABB PTMV - 11

*% Improvement as compared to Case 1

ABB

Predictive Reliability Analysis


ABB Consultings Performance AdvantageTM Software

Useful for:

Looking at system configuration and design Placement of protective devices

Impacts of changes in failure rates and restoration times


Analyzing system reliability from a graphical perspective and determining the most cost-effective solutions

ABB PTMV - 12