Vous êtes sur la page 1sur 33

HKU SPACE PO LEUNG KUK COMMUNITY COLLEGE BUILDING

Building Services Installations

Building Services Installations


Air-Conditioning & Mechanical Ventilation (ACMV) Installation Electrical Installation Fire Services Installation Plumbing & Drainage Installations Lift Installation Gondola Installation Green Initiatives - Energy Efficiency - Water Conservation - Material Use

Building Services Installations

Reliability

Flexibility

New Technology

Design Intent
Energy Efficiency Health & Safety

Sustainability

Maintainability

ACMV Installation
Design Considerations
Conditions
Outdoor (Summer) 33.5 oC DB

Temperature

Relative Humidity
68% RH

Outdoor (Winter)

7 oC DB

40% RH

Indoor (Summer)

25.5+ 1 oC DB 22 oC DB (Server Room only)

55% + 5% RH

ACMV Installation
Air-Cooled Chillers System
Site outside Pilot Scheme Area Spatial Limitation Lower capital cost Two 400TR and One 150TR Chillers Chilled Water Pumps (3 Duty & 2 Standby) Chilled Water Piping Distribution System Motorized Isolating Valves Balancing Valves Motor Control Centre (MCC)

ACMV Installation
Air Distribution Systems
Air Intake away from Pollutant Sources Adequate Fresh Air Intake & Air Filters for AHU & PAU Noise Control Fan Coil System with Primary Air Unit (PAU) - Individual On/Off and Temperature Control - Classroom, Staff Zone, Library, Learning Commons Constant Air Volume (CAV) System - Lecture Theatres & College Hall Split Type AC with standby unit - Server Room (24hrs AC)

ACMV Installation
Mechanical Ventilation Systems
Plant Rooms Toilets maintained under negative pressure Computer Lab. & Library maintained under positive pressure

ACMV Installation
Central Control & Monitoring System
System network with flexible topology DDC controllers Software Control & Monitoring for : - Complete ACMV systems - On/Off and Time Frame Control of Lighting on floor basis - Energy Use of ACMV, lifts, general lighting & power - Total Building Energy Consumption - Emergency Generator System - Plumbing Equipment & Water Storage - Alarms from Lifts

ACMV Installation
Central Control & Monitoring System (Fan Coil Unit)

ACMV Installation
Central Control & Monitoring System (Lighting)

ACMV Installation
Central Control & Monitoring System (Genset)

ACMV Installation
Central Control & Monitoring System (Lift)

ACMV Installation
Central Control & Monitoring System (FS)

ACMV Installation
Central Control & Monitoring System (Plumbing System)

Electrical Installation
Power Distribution System
Power Supply Two 1500kVA Transformers by Hongkong Electric Co., Ltd. in G/F Transformer Room Low Voltage Switchboard in G/F Main Switchroom Low Smoke Zero Halogen (LSOH) Distribution Cables Power Factor Compensation Equipment Check Meter Multi-function Power Meters

Electrical Installation
Emergency Power System
One 600kVA Emergency Generator at R/F Serving FSI & Non-FSI Essential Loads in case of power failure Fuel Tank in separate room Comply with FSDs Requirement Comply with EPDs Requirement

Electrical Installation
Lighting & Small Power Installations
Lighting - CIBSE Codes - COP for Energy Efficient - Energy Saving Luminaire - Electronic Ballast & T5 Tube - Flexible Controls for Operational Needs - Emergency Lighting to BS5266 Small Power - General Socket Outlets - Connection Units, Fused Connection Units - Floor Boxes for Computers

Electrical Installation
Lightning Protection and Earthing Systems
Lightning Protection System - Early Streamer System (AS 1768) - Air Terminal - Co-axial Cable Down Conductor - Stroke Counter - Lightning Earthing Termination

Earthing System to BS 7430 - Main Earthing - Supplementary Bonding - Equipotential Bonding

Electrical Installation
Security Systems
CCTV System - Lobby, Corridor, Library, Learning Commons & Lifts - 24 hours Surveillance Camera Images - Monitors and Digital Recorders at Caretaker Room Door Monitoring System - Exit Doors at Perimeter - Doors of Laboratories for Computer and Special Programs - Computerized Control Station at Caretaker Room Watchman Patrol Tour System - Wireless Points at Strategic Locations - Data Acquisition Unit to record tour

Electrical Installation
Security Systems
Smartcard Access System - Library, Self-served Computer Lab - Staff Office Areas (Staff only) Emergency Call Bell System - Design Manual of Barrier Free Access - Disable Toilets - Male and Female Toilets - Common Control Panel at Caretaker Room

Electrical Installation
Other ELV Systems
Public Address System - Central announcement in emergency - Except staircases, toilets and lifts - Central Equipment at Central Service Support Area Induction Loop System - Design Manual of Barrier Free Access - Guard Station, Lecture Theatres and College Hall

Electrical Installation
Structural Cabling System
High Speed (10 Gbps) Ethernet Backbone System Redundancy Fixed or Wireless LAN Access Points, IP Phone Points Vertical Backbone - Dual Optical Fibres Horizontal Dual Optical Fibres to Server in Computer Lab

Electrical Installation
Internet Protocol (IP) Phone System
Simple Management Platform for Voice and Data Centralized Maintenance, Upgrade and Operation Manage Incoming Calls Easily (Detailed Call Log, Screen Pop) Simple Outgoing Calls by Universal Directory Access (Phone Book) Easy to Add or Relocate IP Phones

Electrical Installation
Audio and Video Installations
Projection System Audio System Wireless Microphone & Speakers AV Broadcasting between Lecture Theatres and College Hall Simultaneous Interpretation System for Lecture Theatres AV Systems for Special Programme Laboratories Integrated Control for Lighting & AV System

Fire Services Installation


Fire Hydrant (FH) / Hose Reel (HR) System Automatic Sprinkler System Automatic / Manual Fire Alarm System Visual Fire Alarm System Fixed Sprayer Fire Fighting System (Fuel Tank Room) FM200 System (Server Room) Portable Fire Extinguishers Direct Telephone Link Ventilation Air Conditioning Control (VAC) System

Plumbing Installation
Fresh Water System - Potable Water - Cleansing Water - Air-conditioning Make-up Water Flush Water System Fire Services Water System

Drainage Installation
Soil and Waste Drainage System - Two-pipe Ventilated Gravity System - U/G Petrol Interceptor for Carpark - Discharge to Public Foul Water System Storm Water Drainage System - Rain Water Outlet at Roof, Balcony & Canopy - Discharge to Public Storm Water System

Lifts Installation
Passenger Lifts (3 nos.) Service/Disable/Firemans Lift (1 no.) CIBSE Guide D 5-Min Handling Capacity > 10% of Population Waiting Time Interval < 50s Visual & Voice Indication Programmable Announcement (English, Cantonese, Mandarin) Pre-arrival Chiming & Arrival Lantern Computerized Group Supervisory Control Operation Modes for Different Traffic Demands

Gondola Installation
Roof Carriage Track Type System Suspension Rope Restraint System Intercommunication System

Green Initiatives
Energy Efficiency
Electronic Ballast T5 Fluorescent Tube LED Exit Sign Occupancy Sensor Photo Sensor CO2 Monitoring System Energy Metering

PAU

CO2 Sensor

CO2 Sensor

Classroom

Classroom

Green Initiatives
Water Conservation
Infrared on-off control water tap Dual flush cistern for WC

Material Use
Prefabricated system to minimize construction waste Zero ozone depletion type refrigerant CFC free thermal insulating material

HKU SPACE PO LEUNG KUK COMMUNITY COLLEGE BUILDING

THANK YOU

HKU SPACE PO LEUNG KUK COMMUNITY COLLEGE BUILDING

Q&A

Vous aimerez peut-être aussi