FINAL YEAR PROJECT 2

Estimation Of Line Performance Of


Transmission Distribution Line Based
On Local Lightning Data Using
TFlash

AHMAD KAMAL BIN MOID SANI
EP077212
1
Introduction

analysis 1
the effect of the lightning performance of
the local lightning data
analysis 2
the effect of lighting performance of the
assumption data


2
Analysis 1: the effect of the lightning performance of
the local lightning data

Aim
to use the real data to obtain the real result of the
lightning performance in Malaysia
Data Source
TNB Research
collaboration with TNB and Uniten
3
Analysis 1: the effect of the lightning performance of
the local lightning data
Line Setup
Location :Pantai Remis to Trong ,Perak
sum of the line at 26.71 km
106 tower were set up at the line
Distance between tower-100-300 m
Tower energized at 33 kV
GFD (Ground Flash Density -6.4 flashes /year
The distant between object are 12 m and the
height of the object are 10 meter.
4
Analysis 1: the effect of the lightning
performance of the local lightning data
Tower
No/Event/
year
1 3 5 7 9 12 15 18 21 24 27 30
Elevation
(m)
15 12 12 9 13 13 16 16 16 16 16 16
Phase
Strike
0.001 0.002 0.003 0.003 0.003 0.003 0.003 0.003 0.003 0.004 0.003 0.003
Back
Flashover
0.014 0.102 0.203 0.198 0.167 0.203 0.203 0.167 0.199 0.268 0.166 0.167
Induced
Flashover
0.005 0.005 0.013 0.013 0.013 0.013 0.011 0.011 0.011 0.020 0.013 0.011
5
Analysis 1: the effect of the lightning
performance of the local lightning data
Event/Year
Tower No
FIGURE 1
6
Analysis 2:the effect of lighting performance of
the assumption data
Divide into 3 subcases:
Effect of the tower footing resistance to the
transmission line
Distance from a nearby object to the tower
Elevation differences from a tower to
another tower along the line


7
Subcase 1: Effect of the tower footing resistance
to the transmission line
Line Setup
Aim : show the effect of the earth resistance
sum of the line at 5.8 km
30 tower were set up at the line
Distance between tower around 200 m
Tower energized at 33 kV
GFD (Ground Flash Density -6.4 flashes /year
The distant between object are 12 m and the
height of the object are 10 meter.

8
Subcase 1: Effect of the tower footing resistance
to the transmission line
FIGURE 2
9
Subcase 1: Effect of the tower footing resistance
to the transmission line
Event/year
/Resistance
()
25 35 45 55 65 75
Phase
Strike
0.012 0.012 0.012 0.012 0.011 0.011
Back
Flashover
0.518 0.649 0.774 0.876 0.883 0.949
Induced
Flashover
0.054 0.054 0.054 0.054 0.047 0.047
FIGURE 3
10
Subcase 1: Effect of the tower footing resistance
to the transmission line
FIGURE 4
Event/Year
Resistance
11
Subcase 2 :Distance from a nearby object to the
tower
Line Setup
Aim :effect of the distant from the tower to a nearby
object
sum of the line at 5.8 km
30 tower were set up at the line
Distance between tower around 200 m
Tower energized at 33 kV
GFD (Ground Flash Density) -6.4 flashes /year
The distant between object are 12 m and the height of
the object are 10 meter.

12
FIGURE 5
Subcase 2 :Distance from a nearby object to the
tower
13
FIGURE 6
Distance(m)
/Event
10 15 20 25
Phase Strike 0.02 0.02 0.019 0.019
Back
Flashover
0.908 0.93 0.86 0.86
Induced
Flashover
0.09 0.09 0.083 0.083
Subcase 2 :Distance from a nearby object to the
tower
14
Subcase 2 :Distance from a nearby object to the
tower
FIGURE 7
Distance
Event/Year
15
Subcase 3:Elevation differences from a tower to
another tower along the line
Line Setup
Aim :effect of the distant from the tower to a nearby
object
sum of the line at 5.8 km
30 tower were set up at the line
Distance between tower around 200 m
Tower energized at 33 kV
GFD (Ground Flash Density -6.4 flashes /year
Geography Setup Divide to 5 types

16
Subcase 3:Elevation differences from a tower to
another tower along the line
Geography Setup

Geography/In
dicator
Type 1:Flat
Ground
Type 2 :Ridge Type 3 :Ridge
2
Type 4 : Valley Type 5 :Flat
Open
Distant 0 m 1200 m 1200 m
2400 m
2400 m
3600 m
3600 m -4800
m
4800 m
6000 m
Elevation 0 m 150 m 150 m 300
m
300 m 90 m 90 m 90 m 0 m
Ground Slope 0 Degree 15 Degree 15 Degree 7 Degree 0 Degree
ROW (Right Of
Way )
Distant
Object:12m
Height Object
:10m

No Object
Position
No Object
Position
No Object
Position
No Object
Position
FIGURE 8
17
Subcase 3:Elevation differences from a tower to
another tower along the line
FIGURE 9
18
Subcase 3:Elevation differences from a tower to
another tower along the line
Elevation(
m)/Event
0-150 150-300 300-90 90-90 90-0
Phase
Strike
0.012 0.19 0.198 0.026 0.046
Back
Flashover
0.536 0.708 0.714 0.553 0.537
Induced
Flashover
0.054 0.00 0.00 0.066 0.027
FIGURE 10
19
Subcase 3:Elevation differences from a tower to
another tower along the line
Event/year
Elevation(m)
FIGURE 11
20
CONCLUSION/DISCUSSION
Increasing the value of soil resistivity will increase the total
flashover
To increase accuracy and efficiency
Use multiple value of earth resistance
Use the exact value of GFD rather use a default value for
the whole line
Distant of nearby object give a big impact to the change in a
total flashover
Increasing the elevation of the earth also will increase the
chance of the total flashover that occur to the tower

21