Installation of Terminals
.The network management system is installed correctly
and works normally.
. Labels should be stuck on the terminal and alarm box
according to specifications easy to maintenance.

support.huawei.com

Page 1
Installation of Terminals
.The auxiliary cables for terminals, operators and alarm boxes
should be distributed and tied in an orderly way.
.The redundant cable ties should be cut from their bottom so that
any sharp edges do not exist.

support.huawei.com

Page 2
Power Cable and Grounding Cable
.The power cable and
ground cable should
be connected in a
correct and reliable
way.
.All kinds of server
with a complete or
part of metal shell of
rack and chassis
should be connected
to the protection
ground in a correct
and reliable way.

support.huawei.com

Page 3
Power Cable and Grounding Cable
.The ground cable of cabinet door should be connected in a
correct and reliable way.

support.huawei.com

Page 4
.The equipotential cables
of combining cabinets
and same module
cabinets should be
connected in a correct
and reliable way.
.The PGND between
server cabinet and major
communication
equipment should be
interconnected by a
short-circuit cable.
Power Cable and Grounding Cable

support.huawei.com

Page 5
The protection grounding cable of MDF and DDF should be
connected firmly. Those between adjacent frame should be
interconnected and then connected to the nearest protection
ground bar of the customer.
Power Cable and Grounding Cable

support.huawei.com

Page 6
.The power cable and grounding cable must be whole copper core cable
without any connector in between.
.The diameter of the power cable, ground cable or equipotential cable
between cabinets should meet the power distribution requirement of
equipment.
Power Cable and Grounding Cable

support.huawei.com

Page 7
. The power cable, ground
cable should be
distributed with signal
cable separately.
.The spacing between
power cable/ground cable
and signaling cable
outside the cabinet
should satisfy the design
requirements. Generally,
the spacing should be
more than 3 cm.
Power Cable and Grounding Cable
3cm

support.huawei.com

Page 8
.The power cable or ground cable should be distributed and tied
tidily.
.The bending position of the power cable and ground cable should
be smooth.
Power Cable and Grounding Cable

support.huawei.com

Page 9
. The bending position of the power cable and ground
cable should be smooth. It should be taken protective
measures when signaling cables are fixed to
mechanical parts with edges and corners.
Power Cable and Grounding Cable

support.huawei.com

Page 10
1.When making lugs for the power and ground cables, the lugs
should be soldered or crimped firmly.
Power Cable and Grounding Cable

support.huawei.com

Page 11
.The lug handle and bare wire of power cable or grounding cable
should be wrapped with the tube or insulating adhesive tape.
.There is no bare copper wire on the lug or terminal.
.The installation of flat washers and spring washers are correct.
Power Cable and Grounding Cable

support.huawei.com

Page 12
Installation Environment of Equipment
.The equipment room should be far away from any strong
electric field, intense magnetic field, powerful electric wave,
and high heat source. It also needs to meet the
electromagnetic requirements.
.The cleanliness of the equipment room should meet the
requirements of long-term safe operation.

support.huawei.com

Page 13
Installation Environment of Equipment
The temperature and
humidity of the
equipment room should
meet the requirements
of long-term safe
operation.

support.huawei.com

Page 14
Fireproof measures should
be adopted in the equipment
room.
Installation Environment of Equipment

support.huawei.com

Page 15
. The DC voltage and capacity provided by the equipment room
meet the requirements of long-term safe operation.
Installation Environment of Equipment

support.huawei.com

Page 16
Iron Tower
.The surface of Iron tower must be anticorrosive and antirust

Greenfield Tower

Rooftop Tower

Stay Wire Tower

Mast Tower