Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. No reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. No reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. No reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Stafford Krishnakumar VENKATARAMAN J uly, 2011 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 2 MiCOM 40 Series : Building blocks for a total solution MiCOM_2 P340 Generator Protection Relays P440 Distance Protection Relays P540 Line Differential and Unit Protection P940 Frequency Protection Relays P240 Universal Motor Protection Relay P840 Autoreclose Relays P740 Busbar Protection Relays P140 Feeder Management Relays P640 Transformer Differential Protection ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 3 MiCOM 40 Series Comprehensive Protection Solutions at all Power System levels: Generation Integrated Generator Protection Transmission Distance Protection Line Differential Distribution Feeder Management Loadshedding Industrial Motor Management Interconnection Protection ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 4 Features for Flexible Solutions Programmable LEDs Programmable Scheme Logic Secure Comprehensive Recording Flexible Communications Configurable Interface Dual Rated CT Inputs ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 5 MiCOM 40 Series Benefits Optimised Costs High Level of Integration Increased Plant Availability Comprehensive Monitoring Post Fault Analysis Tools Condition Based Maintenance Adaptable to evolving systems Flexibility Download/monitor port Minimal Spares Holding ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 6 MiCOM 40 Series Benefits Familiarity
Common Protection Elements
Product Evolution
Common Hardware Menu Access & Navigation Support Software Technical Documentation Reduced Training
Settings Structure New Products New Communications Options ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 7 Front Panel Programmable LEDs Alarm viewer Menu browser Fixed function LEDs Security seal ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 8 P145 Features - New User Interface Tri-Color LEDS Alarm viewer Menu browser Fixed function LEDs Function Keys HotKeys Tri-Color LEDS ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 9 MiCom ALSTOM Offering: Feeder Protection Selector With voltage vector Shift & dynamic line rating ? One box solution With mimic diagram ? Autoreclose required ? Check Synchronism Required? Function keys for control & test operations Required? 8 binary inputs +8 relay contacts Sufficient ? P341 Distributed Generation Interconnection Feeder Protection C264P Feeder relay with Integrated bay control P145 Feeder Management Relay with autoreclose, Check synchronism & Function keys P141 Feeder management relay P142 Feeder management Relay with autoreclose P143 Feeder management Relay with autoreclose & check synchronism Yes Yes Yes Yes Yes No No No No No Yes No START ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 10 MiCom ALSTOM Offering: Voltage & Frequency Protection With IEC 61850 Protocol? Selector No P941 Voltage & Frequency Management relay 8 binary inputs +8 relay contacts Sufficient? P943 Voltage & Frequency Management relay Function key for contact & test operation Required? P145 Feeder management relay With auto-reclose, check synchronism & function keys Yes No No No P141 Feeder Management relay Yes Yes P143 Feeder management relay With auto-reclose & Check synchronism P142 Feeder management relay With auto reclose Yes Yes No START 16 binary inputs +14 relay contacts Sufficient ? Sum total of binary I/O points required greater than 23? ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 11 P14x Features Comprehensive Feeder Protection
PROTECTION FUNCTIONS OVERVIEW P141 P142 P143 P144 P145 50/51/67 Dir / Non dir, Inst. / time delayed phase O/C (Six stages) 50N/51N/67N Dir / Non dir, Inst. / time delayed earth fault 67N Sensitive directional earthfault 67W Wattmetric earthfault YN Neutral admittance protection 64 Restricted earthfault Blocked overcurrent Selective overcurrent Cold load pickup 51V Voltage controlled overcurrent 46 Dir / Non dir, negative sequence O/C 49 RMS thermal overload 37P/37N Phase and Neutral undercurrent 27 Under Voltage 59 Over Voltage 59N Residual Over Voltage (Neutral displacement) ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 12 P14x Features Comprehensive Feeder Protection
PROTECTION FUNCTIONS OVERVIEW P141 P142 P143 P144 P145 47 Negative sequence over voltage 81U Under Frequency (9 stages) 81O Over Frequency (9 stages) 81R Rate of change of frequency protection (9 stages) 81RF Freq. sup. rate of change of freq. protection (9 stages) 81RAV Average rate of change of freq. protection (9stages)
Frequency based load restoration (9 stages) BC Broken Conductor 50BF Circuit Breaker Failure VTS Voltage transformer supervision CTS Current transformer supervision 49SR Silicon rectifier overload protection 79 4 shot 3 pole auto reclose - 25 Check synchronising - - - 2nd harmonic blocking 32R/32L/32O Phase segregated power Sensitive power ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 13 P14x Features Comprehensive Feeder Protection
FUNCTIONS OVERVIEW P141 P142 P143 P144 P145 Rate of change of voltage protection 128 virtual inputs Logic gates quantity (maximum) 300 300 300 300 300 SR gates (maximum) 128 128 128 128 128 Read Only Mode Function keys - - - - 10 Programmable LEDs (tricolour) - - - - 18 Digital inputs (maximum)* 8 16 32 32 Output relays (maximum)* 8 15 32 32 Front communication port (RS232) Rear communication port (RS485/Optic/Ethernet)* ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 14 P14x Features Comprehensive Feeder Protection
FUNCTIONS OVERVIEW P141 P142 P143 P144 P145 Second rear communication port (RS232/RS485)* Option Option Option Option Option Redundant rear Ethernet port (optical) Option Option Option Option Option Time Synchronisation port (IRIGB mod/demod)* Option Option Option Option Option InterMiCOM teleprotection Option Option Option Option Option
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 15 Management or Protection? Measurements Self Diagnostics & Commissioning Tools Bay Monitoring & Control Communications Fault Analysis Tools Comprehensive Protection ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 16 Comprehensive Protection ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 17 Protection Needs Solid PR0 PP0 TP0 TPI PPI PRI B/S Resistive Petersen coil TR0 TRI Protection functionality required is system dependent ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 18 Plain Radial Feeders Time delayed phase overcurrent Time delayed earth fault Thermal overload Auto-reclose (Auto-reclose with sequence co-ordination) Breaker failure Broken conductor detection Negative sequence overcurrent 51 51N 49
79 50BF 46 46BC CB CB Busbar Busbar ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 19 REF CT SBEF CT Transformers/Transformer Feeders Instantaneous phase O/C Time Delayed Standby Earth Fault Restricted Earth Fault 50 64 51SBEF LBCB HVCB Busbar Busbar Inrush Blocking ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 20 67 67N Directional phase O/C Directional earth fault Parallel Feeders LVCB HVCB REF CT SBEF CT LVCB HVCB REF CT SBEF CT Busbar Busbar ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 21 Overcurrent Protection Fully flexible overcurrent protection Six independent stages Choice of directionality (per stage) Operative for close-up faults Enhanced flexibility for schemes e.g. Blocked overcurrent protection Parallel feeders Current T 0 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 22 Overcurrent Protection (2) Six independent stages IDMT/DT stage 1, 2 & 5 DT on stages 3, 4 & 6 Each stage: Non directional Directional forward Directional reverse Memory polarising IEC & IEEE IDMT curves IEC Curves Current (Multiples of Is) 0.1 1 10 100 1000 1 100 10 Operating Time (s) IEC SI IEC VI IEC EI IEC LTS ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 23 Overcurrent Protection (3) Comprehensive setting ranges 8% - 400% stages 1, 2 & 5 8% - 3200% stages 3, 4 & 6 TMS range: 0.025 to 1.2 Time dial: 0.01 to 100 Definite time: 0 to 100s Phase segregated contacts/indication Per stage starts & blocking inputs Adjustable reset time IEEE Curves 0.1 1 10 100 1 10 100 Current (Multiples of Is) Operating Time (s) US MI US VI US EI US I US SI ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 24 Application of Two IDMT Curves (1) First IDMT Curve I>1 FWD Busbar CB 3 CB 1 Busbar CB 4 CB 2 CB 5 67 Second IDMT Curve I>2 67 3 4 P141 1 P141 2 P142 5 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 25 67 First IDMT Curve I>1 FWD 67 Second IDMT Curve I>2 67 Busbar CB 3 CB 1 Busbar CB 4 CB 2 CB 5 3 4 P141 1 P141 2 P142 5 Application of Two IDMT Curves (2) ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 26 Overcurrent Protection Current setting Existing practices Sensitivity Relay thermal withstand Load current reversal Time setting IDMT Definite time Time 1/2 3/4 5 3/4 DIR I FL
I 3f LV I 3f HV ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 27 Earth Fault Protection Standard E/F Derived Directional E/F Derived Sensitive E/F Standard E/F Measured Sensitive Directional E/F Directional E/F Measured Wattmetric E/F High Impedance REF Low Impedance REF Neutral Voltage Displacement ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 28 51 51N Time delayed phase overcurrent Time delayed earth fault (EF2) 51SEF Sensitive earth fault 64 Frame Leakage (EF1) 64 Trf. Restricted E/F (low impedance differential) Earth Fault Application Frame Leakage Busbar Busbar Frame SEF EF1 Frame to earth Fault (EF2) a,b,c ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 29 51N Time delayed earth fault (EF2) = BACKUP TRIP 51SEF SEF Pick up + 64 Frame Leakage (EF1) = TRIP Earth Fault Application Frame Leakage Busbar Busbar Frame SEF EF1 Frame to earth Fault (EF2) a,b,c ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 30 Application DEF Negative Sequence Polarisation Busbar CB CB Busbar CB CB P141 1 P141 2 3 4 3 Limb VT Fault direction is determined by comparison of the Negative Phase Sequence (NPS) voltage with NPS current Directional earth fault 67N ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 31 LV HV CB Residual Overvoltage (Neutral Displacement) A Phase to Earth Fault 59 5 Limb VT V A 59 CB Busbar
Application of Residual Overvoltage Protection (Neutral Displacement) V B V C V A Trip CB ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 32 Earth Fault Protection Example Scheme: Benefits Line CTs for DEF and non-DEF Single neutral CT for SBEF and low Z REF No external differential connection Different ratios permissible Polarising options for DEF Allows 3-limb VTs 1000/1A 200/1A 1000/1A IDMT DEF IDMT E/F SBEF Low Z REF
High Z REF ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 33 Low Impedance REF (1) No stabilising resistor No non linear resistors Line CTs - Ratio 1000/1 F In ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 34 Back-Up Protection Two options are available in P14* relays:- Voltage controlled overcurrent Relatively simple to set Requires sufficient voltage dip for initiation Negative phase sequence overcurrent Not dependent on voltage dip Responsive to phase-phase or phase-earth faults Directional capability More complex setting calculation ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 35 Problems:- Fault current may be less than rating of incomer Grading with generator protection Grading on interconnected systems Back-Up Protection (1) P14* 11kV Busbar P14* 100A 100A 100A Load Load Load 3.3kV Fault 2MVA 5% 2000A Source Load 100A ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 36 Application Voltage Controlled Overcurrent Protection (51V) Voltage Controlled Overcurrent CB 2 CB 2 CB 3 51V 51V CB2 CB2 I substation full load
Time CB 3 Busbar ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 37 HV LV CB Negative sequence overcurrent 46 Earth Fault 46 I1 + I2 + I0 I1 + I2 I0 Application Negative Sequence Overcurrent ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 38 Circuit Breaker Failure Two stage Fast reset External initiation Blocking scheme compatible Backtrip Retrip Trip From other device BF INIT ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 39 Overload Protection (1) Overcurrent protection designed for fault condition Thermal replica provides better protection for overload Current based Flexible characteristics Single or dual time constant Reset facility Non-volatile
Current Time ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 40 Voltage Protection (1) Reasons for voltage deviations: Regulation problems Load variation Fault conditions Requirements of protection depends upon application: Line or phase voltage measurement Operation for all or any phase Suitable time delays Alarm/Trip P14* under/over voltage elements suitable for all applications ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 41 Application Negative Sequence Overvoltage Motor CB Negative Sequence Overvoltage Loss of upstream phase supply 47 Motor 47 a b c Block CB Close Busbar ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 42 Broken Conductor Protection (1) Majority of system faults are a result of short circuits Easily detectable Possibility of open circuit faults exist Difficult to detect with conventional protection ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 43 Broken Conductor Detection (2) Existing detection methods; Combination of under/overcurrent logic Negative phase sequence overcurrent Consider suitability for all load conditions P14* uses a ratio technique: I 2 is high for open circuit fault condition I 1
Benefit: Load conditions have minimal effect ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 44 Application of Broken Conductor Protection I 2 / I 1 is high for open circuit fault condition Benefit: Load conditions have minimal effect HV LV CB Broken Conductor Open Phase BC BC HV LV BC ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 45 CT Supervision A B C I O
V O
& T Alarms Blocking Event record ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 46 VT Supervision Alarms Event record Blocking Adaptive setting If and 2f logic 3f on load logic 3f on energisation logic MCB digital input VTS A B C ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 47 Cold Load Pick-up Logic Benefits: No requirement to use alternate setting groups May eliminate need for earth fault stabilising resistor Security /dependability on energisation Potential applications: Motor feeders HV transformer earth fault protection Switch On To Fault (SOTF) Air conditioning Resistive heating Energisation current profile Time Current Energisation period characteristic Normal load characteristic ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 48 Blocked Overcurrent Protection Established technique providing: Improved fault clearance times Reduced grading stages In order to facilitate this function, P14* provides: Per stage start signals Per stage blocking inputs Supervised field supply Interaction with CB failure logic Block high-set element Feeder 1 CB fail backtrip Feeder 2 Feeder 3 Incomer ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 49 Programmability & Customerisation ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 50 Programmability Multiple settings groups Assignable inputs, outputs and LEDs Programmable scheme logic & & 1 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 51 Flexibility using Programmable Scheme Logic User programmable scheme logic Timers Relay contacts LEDs Protection elements Fixed scheme logic Optos Control & & 1 Gate Logic Communication ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 52 Monitoring Circuit Trip Trip Opto Trip coil 52a 52b Circuit breaker Opto ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 53 Ease of Use With Programmable Scheme Logic (1) Opto Signal added and selected from list L7 52-A ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 56 Programming the Relay ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 57 Application Programmable Scheme Logic (1) CB CB Busbar Busbar Programmable Scheme Logic PSL PSL Status Manual CB Close Phase to Earth Fault Manual Close + SEF Pickup = Instantaneous Trip ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 58 Application Programmable Scheme Logic (2) L7 52-A ISEF>START PU 1000 & R1 SEF INST TRIP LED 1 (Unlatched) Opto Signal for CB status added Timer with Pulse function added Internal SEF Pickup signal added LOGIC Gate added Trip mapped to Contact and LED Indication ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 59 80% of overhead line faults are transient or semi-permanent Minimising supply interruptions is essential Trend to total system automation
AUTO RECLOSE AIDS SUPPLY CONTINUITY Programming the Relay ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 60 Auto-Reclose Benefits of P142 and P143 Traditionally dedicated, discrete device Many versions due to differing philosophies and requirements Benefits of integrating protection and auto-reclose:- Reduced panel space Reduced wiring Reduced cost Integrated auto-reclose logic needs to be flexible:- Single and multi-shot Ability to co-ordinate with other reclosing equipment Check synchronising Variety of operating modes CB monitoring ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 61 Application Auto Reclose (1) Transient Fault CB CB Busbar Busbar Tele- control Auto Live Line Non Auto 79 Auto-reclose (Auto-reclose with sequence co-ordination) 79 Healthy AR in progress Dead Time Auto Close AR Lockout Successful Close ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 62 Tele- control Auto Live Line Non Auto Auto-reclose (Auto-reclose with sequence co-ordination) AR in progress Dead Time Auto Close AR Lockout Successful Close CB CB Busbar Busbar 79 79 Healthy Application Auto Reclose (2) Permanent Fault ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 63 16% 3.8 16km 10miles Fault Locator ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 64 Power Protection - 32R, 32L and 32O Phase Segregated Power protection Single Phase or 3 phase setting Phase segregated Under / Over power protection 2 stage power element Each stage can be set to Reverse Power Over Power Low Forward Power Can be applied as per the requirement: Non urgent shutdown LFP Prime mover failure RP Simple Over load alarm OP Loss of load protection LFP ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 65 Sensitive Power Protection 2 stage power element Each stage can be set to Reverse Power Over Power Low Forward Power Single phase power using the SEF input Minimum setting of 0.5% Pn DDBs for sensitive power start & trip of each stage
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 66
Check Sync. enhancements Sync. check 1 (Phase Angle check) Sync. check 2 (System Angle check) Live Line / Dead Bus Dead Line / Live Bus Dead Line / Dead Bus System split detector Undervoltage monitor Differential voltage monitor Voltage Correction factor, kSM: 0.1 to 3.0 - NEW Phase angle correction factor, kSA: -150 to +180 degrees - NEW ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 67 Check Sync. enhancements Check Synchronising 25 GCB Generator Busbar ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 68 Applications: 1.Synchronising the Generator VT with the VT after the step up Generator transformer. 2.VTs with higher ratio can be used in case of non availability of matching VTs. Check Sync. enhancements ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 69 Four different frequency elements It is not possible to have an estimate of the generation deficit in the system using frequency alone df/dt changes as frequency decreases but can be used to have an estimate of overload. f+df/dt can be used to speed up load shedding during severe overloads (no need to time delay) f+ f/ t gives a much better estimate than f+df/dt during power swings. The elements can be combined for better response ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 70 Advanced Frequency Protection Summary Ensures that the power system operates within the declared frequency tolerance band In the event of insufficient generation, ensures that supply is maintained to as many of the more important consumers as possible Managed load shedding schemes Reliable and fast Highly accurate 9 Stages each for the following features: Under Frequency Over Frequency Rate of Change of frequency Frequency supervised rate of change of frequency Average rate of change of frequency Load restoration ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 71 In the current implementation (v43 and below) of Voltage Transformer secondary setting, the minimum setting range for Phase to Phase voltage is only 320 volts for the 440V module. v44 firmware provides an enhancement in such a way that the minimum setting can be from 196v phase to phase. Applications: 1. Voltage transformers with a non standard VT secondary voltage, which are common in some countries 2. Reduces the extra hardware, IVT
VT with Phase Phase setting from 196V ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 72
Fault data now available in DNP3.0 Protocol. Latest fault data can be mapped. Ease of trouble shooting
Fault data in DNP3.0 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 73 Rate of change of voltage (dv/dt) feature Enhancement: dv/dt similar to P923 function 2 stages of rate of change of voltage independently settable
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 74 Enhancement: Detects high inrush current flows that occurs when transformers or machines are energised. Setting to block the over current / earth fault protection if the level of second harmonic/fundamental exceeds in phase or neutral current. Can be phase selective or across all phases. In practise the second harmonic level may not be same for all the phases during inrush. Displays second harmonic currents for IA, IB and IC as measurements as percentage of fundamental. Second Harmonic Restraint ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 75 Configurable datasets: customisable GOOSE messages customisable Reports Buffered Reports Control functionality for various functions in P14x Increased Virtual I/O for GOOSE publishing/subscribing Transmit analogue values in GOOSE Select Active Setting Group service Improved 'IED Configurator Support above functionality Improved usability E.g. due to configurable datasets, the configuring of a GOOSE message to publish, and the configuring of subscribing to GOOSE messages, including from non-Alstom IEDs, is much more user-friendly (Quick Pick selection). P14x - IEC 61850 Enhancement ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 76 Programmable curve generation (will be available by end Mar 2011) Programmable curves: 2 curve programmable on Pick up 2 curve programmable on Reset Specific software Design curve by 255 point or by formula ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 77 Programmable curve generation (will be available by end Mar 2011) Programmable operate curves: Modification of multiple point up to 255 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 78 Programmable curve generation (will be available by end Mar 2011) Programmable reset curves: Modification of multiple point up to 255 or by formula ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 79 Enhancement: DNP3 over ethernet is based on the DNP3 serial evolution which was introduced at P140v35 software. It is physically realised by means of the ZN0049 100Mbps Ethernet card. The first rear port is the Courier port which is configurable as K-Bus or RS485. Supports Courier tunnelling. SNTP time synchronisation is supported
DNP3 over Ethernet ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 80 Redundancy allows to have 2 alternate paths from a source to a destination. 2 kind of redundancy: Active redundancy: both links are active at the same time Passive redundancy: one link is active, the other one is in standby mode Main layer 2 redundancy protocols: STP, ANSI/IEEE 802.1D-2004: Spanning Tree Protocol is an algorithm used to create loop free logical topologies in switching. RSTP, IEEE 802.3w: Open standard, but reconfiguration time is around hundreds of milliseconds, which does not reply to substation automation network requirements (Gooses) SHP Self Healing Protocol: Proprietary protocol applied to double ring topologies, network convergence time < 1ms DHP Dual Homing Protocol: Proprietary protocol applied to double star topologies Ethernet Redundancy Redundancy answering the constraints ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 81 2 redundant Ethernet ports. That is, one is active at a time. Ports use same IP address and MAC address. Both ports support RSTP (Rapid Spanning Tree Protocol) standard, in order to implement the redundancy. When the active link fails (for example, external switch failure or cut fiber/cable), then the other port becomes active and the link to the client is restored in a time determined by the RSTP algorithm (depends on the quantity of switches and other nodes in the Ethernet network, e.g. several hundreds of milliseconds). Physically, the 2 ports are both 1300nm multimode fiber (100BaseFX, ST connectors). Effectively the Ethernet network architecture is star. It can be ring connected, then the RSTP algorithm ensures there is no actual loop.
Redundant Ethernet - Open (RSTP) ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 82 2 redundant Ethernet ports. That is, one is active at a time. Ports use same IP address and MAC address. Both ports support the proprietary Self Healing mechanism, in order to implement the redundancy. When the active link fails (for example, external switch failure or cut fiber/cable), the Self Healing Mechanism restores the connection in less than 1 millisecond <- our differentiator. Physically, the 2 ports are both 1300nm multimode fiber (100BaseFX, ST connectors). Fiber Ring architecture
Redundant Ethernet - Self Healing Ring ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 83 When a fibre is broken Detection by the both end stations Self healing of the ring using the two networks << 1 ms recovery time MiCOM H35 MiCOM H35 MiCOM H35 MiCOM H35 PACiS Ethernet IEC61850 ring network Normal conditions PACiS Ethernet IEC61850 ring network Self Healed MiCOM C264 + SWR20x MiCOM C264 + SWR20x MiCOM C264 + SWR20x MiCOM C264 + SWR20x Ethernet Self Healing ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 84 2 redundant Ethernet ports. Both ports active; receiving nodes use first received message. Ports use same IP address and MAC address. Both ports support the proprietary Dual Homing mechanism, in order to implement the redundancy. When either link fails (for example, external switch failure or cut fibre /cable), there is zero changeover time. Interoperable with third-party external Ethernet switches Physically, the 2 ports are both 1300nm multimode fiber (100BaseFX, ST connectors) Fibre Star architecture
Redundant Ethernet (Dual - Homing Star) ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 85 8 EIA (RS 232) InterMiCOM/Control Commands, End - End 8 digital signals from PSL end A - PSL end B for various commands A B 52 52 850nm 1300nm 1550nm or MUX 8 8 & > 1 & > 1 PSL PSL ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 86 InterMiCOM
For long distance communication, fibre optic converters may be used as shown. The maximum distance between the converter and the P14x relay should be 15 metres. InterMiCOM teleprotection via a fibre optic ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 87
The existing configuration has varied opto input time stamping, which is not consistent. New improved configuration has an opto input time stamping accuracy of 1msec Improved time stamping is available across all protocols for use by PACiS or other SAS / SCADA. Opto input time stamps will match disturbance recorder transitions.
Improvement in opto input time stamping ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 88 P145 Features Function Keys 10 Programmable Function Keys Drives 10 associated ddb signals in PSL 10 associated LEDs 2 Modes of Operation Normal Toggled Can be set to Locked Single Function key press at a time Keypress duration > 200msec. ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 89 Load Encroachment (Blinder) Impedance based feature avoids tripping for heavy load flows Provided for phase fault elements Based on positive sequence impedance DDBs for blinder ON, Forward & reverse load 2 Load Blinder Setting In [3500] POC Column [3591] Blinder Status = FWD+REV VISIBLE [3592] I> Block (POC Stage 1,2 & 5) [3594] FWD Z1<Impedance [Range = 0.1- 500 Ohm, Step=10m] [3595] FWD Z1 Angle [Range = 5 - 85 Degree, Step=1] [3597] REV Z1<Impedance [Range = 0.1- 500 Ohm, Step=10m] [3598] REV Z1 Angle [Range = 5 - 85 Degree, Step=1] [359A] Blinder V< Block [Range = 10- 120 V, Step=1] [359B] Blinder I2>Block [Range = 80m- 4 A, Step=10m] = DISABLED INVISIBLE [3592]-[359B] = FWD VISIBLE [3592] I> Block (POC Stage 1,2 & 5) [3594] FWD Z1<Impedance [Range = 0.1- 500 Ohm, Step=10m] [3595] FWD Z1 Angle [Range = 5 - 85 Degree, Step=1] [359A] Blinder V< Block [Range = 10- 120 V, Step=1] [359B] Blinder I2>Block [Range = 80m- 4 A, Step=10m] VISIBLE [3592] I> Block (POC Stage 1,2 & 5) [3597] REV Z1<Impedance [Range = 0.1- 500 Ohm, Step=10m] [3598] REV Z1 Angle [Range = 5 - 85 Degree, Step=1] [[359A] Blinder V< Block [Range = 10- 120 V, Step=1] [359B] Blinder I2>Block [Range = 80m- 4 A, Step=10m] = REV ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 90 Voltage restrained over current protection
In addition to the existing Voltage Controlled over current protection Provides back up protection for uncleared phase faults on the generator busbar or on a feeder from the busbar Selectable as DT or IDMT characteristic Three pole trip only but indication for faulty phase ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 91 Setting changes through IEC 103 protocol
selecting the over current setting ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 92 Setting changes through IEC 103 protocol editing the over current setting ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 93 Setting changes through IEC 103 protocol read the updated over current setting ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 94 Improvements in CB fail algorithm Improvements in the existing CB fail algorithm to distinguish CT discharge current decays and CT saturation, when fault currents are interrupted in large magnitude at high X/R ratios. Pickup accuracy will be as per existing design. The CB Fail undercurrent pickup settings are to have the same setting range and step value as the existing design. The CBF timer settings are to have the same setting range as the existing design but the step size changed to 1ms (from 10ms). Improvements in the performance of the CB Fail fast undercurrent. ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 95 Cyber security Cyber security concerns: Px4x, C264, PACIS family, MiCOM H series Technology implementation: At IED level: 4 levels of Password + PWD complexity Disable unused application and physical ports Account validity time, log off after x min of inactivity Store security logs in the relay Display a user banner before any access attempt External to the IEDs: Antivirus Security patch management NERC compliant by the end of cyber security phase 1 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 96 Monitor bits in the PSL Useful for testing purposes. Allows the user to select the status of which DDB signals can be observed in the Test port status cell or via the monitor / download port. As provided in P54x Eight monitor bits are provided for mapping ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 97 P145 Applications Full Scheme Solution
Combine with P991(test block) and P891(trip/close module) Full 19 rack mounted scheme Cost effective solution Reduce wiring and engineering costs! ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 98 P145 Applications Scheme Application-example ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 99 P891 Features Removable PB Cover/Guard Other Label set available Trip Pushbutton Close Pushbutton Universal Power Supply ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 100 Setting the Relay Highly integrated Protection & Control solution Large number of settings Configuration simplified by:- Configuration column in menu Local communication port on relay front plate Comprehensive support software ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. MiCOM ALSTOM P140 Series Feeder Management Relays- Aug,2010 - P 101 The Configuration Column Default setting restoration Setting group manipulation Enabling/disabling Protection & Control functions Menu cell visible www.alstom.com