3D Modeling
Project Description:
Zayed College for Nursing and Optics is located at An-Najah National Universitys
new campus- next to the faculty of medicine.
Load combinations :
Structural Materials:
Concrete:
Load Assumptions:
8
Dead Load:
Slab own weight: 5.54 KN/m2
Live Load
10
10
11
3D Model
12
Slab modifiers
Modification Factors
An-najah National university
13
Columns:
Torsional constant: 0.7
Moment of inertia about 2 axis: 0.7
Moment of inertia about 3 axis: 0.7
14
Sap Verifications
Compatibility
Compatibility check
An-najah National university
15
Equilibrium
Total live load manually = 3306.3 KN.
16
1:2
2
(manually)
8
1:2
510:(50)
+ 3 =
-203=77KN.m
2
2
902.55
=
= 73.55KN.m
8
8
17
18
19
I= importance factor, I= 1
20
21
Load patterns:
22
Load cases:
Scale factor=
gI
R
=1.83 for U1
Earth quake x
An-najah National university
23
Load cases:
Scale factor=
gI
R
=1.83 for U2
23
Earth quake y
An-najah National university
24
Load cases:
Scale factor=
gI
R
=1.83
Earth quake z
An-najah National university
25
Load cases:
Eigen Vectors analysis needs more than 700 modes
Ritz Vectors analysis needs only 21 modes to reach 90% participating mass ratios
Modal case
An-najah National university
26
Period T Check
T =0.377 seconds as shown:
27
Base Reactions
An-najah National university
28
V max:
29
Footing Design
Single Footing
Combined Footing
Wall Footing
30
31
Single Footing
q all = 400 KN/m2
It has a dimensions of 2*2 m
Thickness = 450 mm
Shear Checks :
6 16 / m in both directions.
32
Combined Footing
q all = 400 KN/m2
It has a dimensions of L = 4m , B = 2.6m .
Thickness = 800 mm
Shear Checks :
33
Combined Footing
Longitudinal Reinforcement
As = 4004mm13 20
34
Wall Footing
q all = 400 KN/m
It has a dimensions of B = 2m
Thickness = 550 mm
Reinforcement
35
Design of columns
36
The check is done for both x and y direction for first and last floors
37
38
Slenderness Check
In project1, columns were assumed short. 3D model is used to recheck that assumption.
Lu = 3.7 m
K conservatively assumed 1
R= 0.3 h =0.30.4= 0.12
Alignment chart for non-sway frames
KLu 13.7
=
=
r
0.12
M1
30.83 34- 12 40
M2
M1, M2 for all columns make double curvature
-ve M1
Short columns
M2
An-najah National university
39
Columns Design
40
Design Of Beams
41
area method and 1-D structural model for each beam is analyzed
and designed using SAP2000.
Final output was taken from 3-D model.
41
42
42
limitation) .
43
44
Steel reinforcement
Minimum steel reinforcement
45
Steel reinforcement
Main steel reinforcement
46
Steel reinforcement
Shear reinforcement
47
Steel reinforcement
Torsion reinforcement
48
49
Design of slabs
The structural system of Zayed College is one way ribbed
slab(31 cm ) with drop beams.
50
51
52
Vc =29.2 KN
Vu =27.3 KN
Vc=29.2>Vu=27.3 no need for shear reinforcement , but use
18/20 cm for bar fixation .
53
54
55
56
Stairway Design
Stair dimensions
Going = 30 cm
Riser = 16.5 cm
Slab thickness = 20 cm
57
Stairway Design
Stair Loading
Dead load = 14.1 KN/m
Live Load = 7.9 KN/m
Check for deflection
58
Stairway Design
Check for
shear
Vc > Vu Ok
59
Stairway Design
Design for flexure
60
Stairway Design
Area of steel from sap
59
60
61
62
63
64
(= 0.0025)
As min= 0.00251000300= 750mm2
Use 510/m& 510/m in both horizontal and vertical
directions
65