Académique Documents
Professionnel Documents
Culture Documents
Transformer Specification
Overview
Background
Picture of MEAs Transformer
Single Line Diagram
General Information
Transformer Specification
Conclusion
2
Background
Picture of MEAs Transformer
Background
Single Line Diagram
24 kV
MEA Station
416/240V
Low Voltage Customer
5
Background
General Information
Number of Purchase
: 1,000 units / year
Service Area : 3,191.60 sq.km.
Transformer Specification
Reference Standard
IEC 60076-1(2000) :
Power Transformers Part 1 : General
Thailand Industrial Standard
TIS 384 (1992) :
Standard for Power Transformer
7
Transformer Specification
Test Requirement
Type Test
: Temperature Rise
: Lightning Impulse
: Short Circuit Test
Transformer Specification
Test Requirement
Routine Test
: According to Standard (All unit)
: Temperature Rise (1 Unit)
: Lightning Impulse (1 Unit)
Transformer Specification
Ratings & Features
Type of Cooling : ONAN
Rated Power : 45, 75, 112.5, 150,
225, 300, 500 & 1,000 kVA
Phase : 1 or 3 phases
Overhead, Outdoor & Mineral-OilFilled
10
Transformer Specification
Ratings & Features
High voltage winding : 24 or 12/24 kV
Low Voltage Winding : 416/240V
Temperature Rise
: Winding < 65 K
: Top Oil < 65 K
11
Transformer Specification
Ratings & Features
Connection : Dyn 1
BIL : 125 kV (for 24 or 12/24 kV)
: 30 kV (for 416/240 kV)
Tap : -4 x 2.5 %
12
Transformer Specification
Ratings & Features
Impedance Voltage
: up to 4.4% (45-225 kVA)
: more than 6.5% (300-1,000 kVA)
13
Transformer Specification
General Requirement
Installation Type
: Concrete Pole for 45-300 kVA
: Platform for 500-1,000 kVA
Provided with Lightning Arrester
Bolted Type Transformer Tank Cover
14
Transformer Specification
General Requirement
Maximum Weight
: 1,250 kg
: 1,650 kg
: 1,800 kg
: 4,500 kg
Transformer Specification
Tank & Cover
Constructed of Steel with
Adequate Thickness
Steel cover and electrically bonded to
Tank.
16
Transformer Specification
Core & Coil
Made of Grain Oriented, Low Loss,
High Permeability, Silicon Steel Strip
Not Shift in Any Direction during
Shipping & Installation
17
Transformer Specification
Winding
Either Copper or Aluminum
Foil Type Secondary Winding
Withstand Thermal & Mechanical
Effects by External Short Circuit
18
Transformer Specification
Accessories
up to 300
Tap Changer
yes
500 and up
yes
Dual Switch
yes
yes
Thermometer
no
yes
no
yes
Lifting Facilities
yes
yes
Lightning Arrester
yes
yes
19
Transformer Specification
Accessories
up to 300
500 and up
no
yes
Circuit Breaker
yes
no
Supporting Lug
yes
no
Sampling Valve
no
yes
20
Tap Changer
-4 x 2.5 %
Rating Voltage
21
12 kV or 24 kV
Selection
22
Bushing
High Voltage
Bushing
23
Low Voltage
Bushing
24
Bushing Cover
Cover
Bushing
25
Thermometer
26
27
Lifting Facilities
28
Lightning Arrester
29
30
31
Other
Supporting Lug
Sampling Valve
32
Nameplate
Earthing Point
33
Transformer Specification
Loss (Watt) - Single Phase
kVA
No Load
Load
50
145
420
75
200
540
100
240
700
167
320
1,170
333
500
2,340
34
Transformer Specification
Loss (Watt) - Three Phases
kVA
No Load
Load
45
160
360
150
300
1,000
300
480
1,860
500
670
3,030
1,000
1,000
6,400
35
Conclusion
36