SYSTEM
--Ranjan Das
Dy.Supdt.(operation)
GOVERNING SYSTEM
KWU TURBINE(BHEL)
*HYDRAULIC
*EHC
*Normally EHC kept in service,backed
Up with HYDRAULIC governor
*In case of any fault of EHC , HYDRAULIC
governor taken into service
FUNCTION OF GOVERNING
1)starting of turbine
2)Droop &load control
3)turbine protection
It has an online feature of ATT(automatic
turbine testing)for checking of healthiness
of governing protection devices
Oil :
source
1)control oil(CO)
2)trip oil(TO) CO
3)start up oil CO
4)aux start up oil
CO
5)hp sec oil TO
6)IP sec oil TO
7)primary oil Primary oil pump
Lub oil/FRF
FLOW DIAGRAM
CO
RTS
RTS
CO
SG
SD
STARTING OIL
TO
AFUP
EHC INPUT
CO
HYD CONV
TRIP VALVE
CO
EHC
CONVERTER
O/S trip device
TO
FUP
TO
IP SEC OIL
HP SEC OIL
FUP
thrust bearing trip device
TURBINE PROTECTION
RTS,Trip valve involved in protection system
b)Mechanical tripping
Electrical protection(through RTS)
Mechanical tripping
Axial shift hi
Condenser vacuum low
TG overspend trip (bolt-1 3300 rpm,2-3330 rpm)
Main trip valve handle
protection
DEVICES INVOLVED
1)RTS(electrical protection)
2)TRIP VALVE
3) THURST BEARING TRIP DEVICE
4) OVERSPEED TRIP DEVICE
5) LOW VACUUM TRIP DEVICE
CO
CO
CO
RTS
RTS
TRIP VALVE
Trip oil
Aux trip oil
LOW VACUUM TRIP DEVICE
THURST BEARING
TRIP DEVICE
OVERSRTSPEED
TRIP DEVICE
TRIP VALVE
CO
TRIP VALVE
STOP V/V
AUX. START UP
OIL(RESETTING)
TRIP OIL
AUX SEC OIL CKT/EHC CKT
STARTING OF TURBINE
A)Resetting of stop valve/ trip valve/protection device
B)opening of stop valve/ control valve
1)STARING DEVICE/LOAD LIMITING DEVICE
OPENING OF CONTROL
VALVE
HOW AUX START OIL IS PREPARED ?
HOW HYD. CONVERTOR/FUP WORK?
SELECTION OF HYDRAULIC
& EHC
MINIMUM SELECTION OF
HYDRAULIC
& EHC
LOAD CONTROL/DROOP
(LOAD LIMITING DEVICE)
LOAD CONTROL/DROOP
CHANGING OPENING OF CONTOL VALVE
CONTROL VALVE OPENING CHANGES OF HP/IP SEC OIL
PRESSURE
HP/IP SEC OIL PR CHANGES DUE TO CHANGE IN PR OF AUX
SEC OIL (HYDRAULIC) & EHC INPUT SIGNAL (EHC )
DROOP
CHANGE OF LOAD DUE TO FREQUENCY
PRIMARY OIL ACT AS DROOP AGENT FOR
HYDRAULIC
IN EHC INTERNAL/EXTERNAL DROOP
EHC INTERNAL DROOP-STARTS AT 50.5 HZ.M/C
COMPLETELY UNLAOD IN 4 HZ
EHC EXTERNAL DROOP(LOADING/UNLOADING)50 MW/HZ,LIMITER 5% OF LOAD (10/25 MW)
NR
NRTD/NRLIM
ERROR SIGNAL
NACT
Speed control before syn. (barring speed to 3000 rpm).100% load can be achieved but
normal practice 10% load
NR given in UCB desk/auto synchronoscope /SGC turbine
NR changes at the rate of 2160 rpm/min upto 2820,360 rpm/min after 2820 rpm
When turbine trips NR follows actual speed by 120 rpm,after synchronization when load
controller takes over NR tracks actual speed (more than actual speed by 15 rpm) in frequency
range of 2940 to 3060 rpm.
SPEED CONTROL
NRTD/NRLIM is coming through which determines acceleration rate
Speed control has DN/DT feature .in critical speed range (700 2850 rpm) if DN/DT <100 rpm/min
speed will come to barring speed
Actual speed measured by hall probes
LOAD CONTROL
Frequency influence
PR
load
gradient
PRTD
TSE
10 V
margin
PRf
PR
PRMAX
PID
Error
signalx
Pact
PRESSURE CONTROL
Initial pressure mode
Limit pressure mode (M/C will come to load control)
Throttle pressure (pressure before control valve) set at
UCB
Based on actual throttle pressure measurement error signal
is generated .
MIN of load & pressure control is selected.