IMPROVED REACTIVE POWER
CAPABILITY WITH GRID CONNECTED
DOUBLy FED INDUCTION GENERATOR
CONTENT
INTRODUCTION
DOUBLY FED INDUCTION GENERATOR
OPERATION
REACTIVE CHARACTERISTICS OF DFIG
MODELLING OF DFIG
CAPABILITY CURVE OF DFIG
CONCLUSION
REFERENCE
INTRODUCTION
The reactive power capability (RPC) curve of DFIG considering three
limitations( rotor voltage, rotor current, stator current) for reactive
power/consumption.
It is established that the total reactive power generation is limited by
rotor voltage at low speeds and by rotor currents at higher speed.
Selection of partial rated converter rating is crucial in terms of cost,
efficiency, operating speed range and reactive power capability.
The effect of converters rating on the enhancement of RPC of DFIG
IS analyzed.
Complete capability curves of DFIG for different stator voltages are
developing considering grid side converter(GSC) contribution towards
RPC
OPERATION OF DFIG
OPERATION OF DFIG
The DFIG consists of a 3 phase wound rotor and a 3 phase wound stator.
As the rotor rotates the magnetic field produced due to the ac current also
rotates at a speed proportional to the frequency of the ac signal applied to
the rotor windings.
The speed of rotation of the stator magnetic field depends on the rotor
speed as well as the frequency of the ac current fed to the rotor windings.
The whole system consists of two back to back converters a machine side
converter is used to control the active and reactive powers by controlling
the d-q components of the rotor ,torque and speed of the machine.
Grid side converter is used to maintain a constant dc link voltage and
ensures the unity power factor operation
REACTIVE CHARACTERISTICS
It facilitates flow of active DFIG
power from generation sources
to load centers and maintains bus voltages within
prescribed limits.
Stable operation of power systems requires the availability
of sufficient reactive generation.
The presence of power electronics control in DFIG makes
them a fast acting dynamic reactive resource as
compared to direct grid connected synchronous
generators.
Reactive power capability for a wind plant is a significant
additional cost compared to conventional units which
possess inherent reactive capability.
MODELLING OF DFIG
The doubly fed induction generator has been used for years for
variable speed drives.
From the figure that at 100% plant output, the use of the capability
curve does not give much additional reactive support compared to the
0.95 leading operation.
Wind parks will very seldom operate continuously at 100% output in
the periods of operation below 100%, there is significant additional
reactive power available that could aid in improved system
performance.
CONCLUSION
The operation of DFIG wind farm implementing a
capability curve paves the way for regulatory changes.
In general guidelines for interconnecting wind farm are
used a restricted power factor.
When DFIG work with capability curve, fully utilizing the
potential of DFIG wind farm may be obtain at no extra
cost to the wind farm owner.
As the levels of wind penetration continues to increase
the reactive power the certain point it should be in limit.
At the 100% penetration the limit of reactive power in
both CC and RPF are almost same.
REFERENCE
S.Chandrasekaran, C.Rossi, D.Casadei, A.Tani, Improved
Control Strategy of Wind Turbine with DFIG for Low Voltage Ride
Through Capability International Symposium on Power Electronics,
Electrical Drives, Automation and Motion, 2012, Sorrento, Italy.