Vous êtes sur la page 1sur 43

1

TIA Portal: First steps

TIA Portal

Target

This guidance shows the essential first steps of a simple TIA Portal configuration
In use are a S7-1515, Scalance X208 Switch and TBEN-L1- modules,
also TIA version #13

TBEN-L1-16DIP

TBEN-L1-16DXP

TIA Portal

Creating a project

Create new project


and define a path

TIA Portal

Creating a project

Project is prepared.
Change to project view now.

TIA Portal

Creating a project

Choose
Devices & networks

TIA Portal

Configuration
The related window is open now
and the usual hardware-catalog is availale

TIA Portal

Configuration

Select the connected PLC in the harware-catalog


Select the connected PLC in the harware-catalog
Notice the correct version-number!
Notice the correct version-number!
If this number is not clear
If this number is not clear
go ahead with unspecific CPU 1500!
go ahead with unspecific CPU 1500!

TIA Portal

Configuration
The PLC is integrated now

TIA Portal

Configuration
Go on in the same way with the switch

TIA Portal

10

Configuration
and the connected modules.
(in this case 1 x TBEN-L1-16DIP, followed by a TBIL-L1-16DXP)

TIA Portal

11

Configuration

Hier wurde das letzte Modul hinzugefgt.


The last module was added here.
Beachten Sie in diesem Bild,
Note, that the devices are still Not assigned !
dass die Gerte noch Nicht zugeordnet sind

TIA Portal

12

Allocate device name and IP-address

and change to the device view to General

Assign the PLC


by help of a doubleclick

At the correct port it is


possible to set the IP-address now

Still factory settings.


Well change them soon
(next pages)

TIA Portal

13

Allocate device name and IP-address

New subnet assigned

IP-address assigned

PROFINET name can be


assigned automatically

TIA Portal

14

Allocate device name and IP-address

The unused interface should be in a different


address-area and should also be not networked

TIA Portal

15

Allocate device name and IP-address

The PLC shows the interconnection by help of a green line now within the network view.
But this is not the topology view!

TIA Portal

16

Add subnet

By a click on Not assigned it is possible to allocate each device


to the PLC_1 subnet.

TIA Portal

17

Configure the switch

As ever:
Tag device within the network view and change by help of a doubleclick to the device view

Subnet assigned

IP-address assigned

PROFINET device name can be assigned automatically

TIA Portal

18

Configure the modules


The TBEN-L1-16DIP and 16DXP are configured in the same way

TBEN-L1-16DIP

TBEN-L1-16DXP

PROFINET device name has to be assigned manually.


They have to be interconnected to
the PLC later on, too.

TIA Portal

19

Assign device name

Tag device and change to


the context-menue

Use Assign device name

TIA Portal

20

Assign device name

A new graphic user interface will be open


where youre able to select and to allocate
further devices
The device filter
is quite useful

Assign name!

TIA Portal

21

Assign device name

Go on with the TBEN-.. modules

TIA Portal

22

Assign device name

Name, MAC-ID, etc..,


fit together
Just assign in a final step

TIA Portal

23

Assign device name

An error occured!
What is the reason ??

TIA Portal

24

Assign device name


For more details click on that icon:

TIA Portal

25

Assign device name

It shows, that the assignment


was not finished!

TIA Portal

26

Assign device name

Assignment of device name


is working fine now!

TIA Portal

27

Assign device name

Finally the last module (16DXP)

TIA Portal

28

Load configuration
Tag PLC and compile

TIA Portal

29

Load configuration

If a connection to this PLC was never


done before you have to take care
of Extended download to device now.
Just Start search

TIA Portal

30

Load configuration

PLC was found!

TIA Portal

31

Load configuration

Loading configuration
is in progress now

TIA Portal

32

Load configuration

Just finish

Message window on the lower right shows status of progress

TIA Portal

33

Load configuration
Finally Go online

TIA Portal

34

Load configuration
Completed!
Online and everything is on status green!

Verbunden!

TIA Portal

35

Topology scan
Go to topology view

TIA Portal

36

Topology scan

Compare offline/online status

Message window on the lower right shows status of progress

TIA Portal

37

Topology scan
Comparsion shows still some differences
between the interconnections:

TIA Portal

38

Topology scan

Normally it is sufficient to apply

TIA Portal

39

Topology scan

All interconnections are set


to apply now

TIA Portal

40

Topology scan

Synchronize these settings now

TIA Portal

41

Topology scan
Status is green!
No more differences!

TIA Portal

42

Topology scan
PLC has adopted the topology!

TIA Portal

43

Thats it!

You did it!

2014 by O.H.

TIA Portal

Vous aimerez peut-être aussi