Agenda
TSE Introduction
Characteristics & Selling Points
Model Selection
Advantages Over Key Competitors
FAQ
Q&A
TSE Introduction
by short-circuit capability
Class PC
MTSE
TSE
RTSE
Class CC
ATSE
Hospital
Bank
Office building
Business center
Others
Industry
Manufacturing center
Mining
Power plant
Others
Infrastructure
Airport
Port
Tunnel
Communication
Others
Agenda
TSE Introduction
Characteristics & Selling Points
Model Selection
Advantages Over Key Competitors
FAQ
Q&A
Characteristics (1/5)
Compact NS as switching device
(NS100/160/250/400/630)
Terminal
Trip unit
Handle
Power supply
insulation module
Manual / automatic
operation interlock
Operating circuit breaker
(Compact NS)
Characteristics (2/5)
Multi-9 as switching device (C65)
Motor mechanism module
Handle
C65
Power supply
insulation module
Manual / automatic
interlock shutter
Characteristics (3/5)
2 types of control units applied to both Multi-9 and
Compact NS circuit breakers
B controller
(external type)
A controller
(built-in type)
DIP switch
10
Characteristics (4/5)
General characteristics
Compliance with standard
Pollution degree
IEC60
ATNS are certified for operation in pollutiondegree III environment as defined by IEC60947
ICE/CN 60068-2-30
damp heat (95% relative
humidity at 55)
ICE/CN 60068-2-52 salt
mist (severity level 2)
IEC/CN 600-2-56
-25
Tropicalisation
Ambient temperature
11
Characteristics (5/5)
Technical characteristics
12
13
When
circuit breaker contacts adhere to each
other or
handle breaks due to fault;
ATNS will not switch to prevent connection
to both supplies at the same time
14
alarming signals
Protection against non-execution
If the breaker fails to perform proper function within 5 seconds the switching
15
U-shaped rod
16
Power supply
insulation module
Auto/manual interlock
17
18
A type
B type
Optional
Modbus optional
AC220V 50/60Hz
AC220V 50/60Hz
Agenda
TSE Introduction
Characteristics & Selling Points
Model Selection
Advantages Over Key Competitors
FAQ
Q&A
20
Model Selection(1/2)
Dimensions for ATNS63
mm
G1
H1
K1
L1
P1
P2
P3
ATNS-63 N/H
142
157
445
70.5
220
55.5
190
167
465
17
130
161
6.5
Note:
4P ATNS shares same size with 3p ATNS
Handle not fixed
22
Model Selection(2/2)
Dimensions for ATNS100/160/250/400/630
mm
G1
H1
K1
L1
P1
P2
P3
P4MAX
ATNS 100/160/250
N/SX/H 3P
142
177
460
78
220
63
190
187
480
20
145
176
131
6.5
ATNS 100/160/250
N/SX/H 4P
142
212
530
78
220
63
190
222
550
20
145
176
131
6.5
280
242
580
97
285
82
255
257
610
20
180
232
188
280
287
670
97
285
82
255
302
700
20
180
232
188
23
Agenda
TSE Introduction
Characteristics & Selling Points
Model Selection
Advantages Over Key Competitors
FAQ
Q&A
24
26
ABB DPT/SE
Compact ATNS
Controller
Protection
Auxiliary
protection
Operation mode
Operation
mechanism
Delay
0.5 30S
Communication
Indication
Signal light
Power isolation
27
ABB DPT
Compact ATNS
Product series
63 250A
63 630A
Controller
Single controller
Protection
Auxiliary
protection
Operation refusal
Operation mode
Delay
0.2 30S
A type: 0 30S
B type: 0 255S continuously adjustable
Flip mechanism
Communication
None
Display
Signal light
Power isolation
None
28
SIRCOVER/VE,SIRCOVER/VS
-SIRCOVER/VE: In 250A 3150A;
-SIRCOVER/VS: In 63A 630A;
-Marks in above figure: SMVE,SMVS;
Basic characteristics
-Conform to GB14048.3;
-Rich installation accessories: bridge, supporting terminal,
terminal shield, etc.;
-DC motor driven, operational for remote control.
Double-pole and double-throw contact structure
29
SOCOMEC VS
Compact ATNS
Product series
63 3150A
63 630A
Standard compliance
GB14048.3
GB14048.11
1.8~2.8s
1.5~3s
Controller
OEM
Operation mode
Communication
Indication
Signal light
Power isolation
None
Utilization type
AC23A/AC23B
AC33B
Electrical durability
125A 1000
100A 10000
30
UA/BA
Compact ATNS
Product series
100 6300A
63 630A
Dimensions
Price
Cheaper
Controller
UA/BA
A/B
Operation mode
Communication
Indication
Signal light
Power isolation
Yes
Yes
Complicated
Mechanical interlock
31
Agenda
TSE Introduction
Characteristics & Selling Points
Model Selection
Advantages Over Key Competitors
FAQ
Q&A
32
FAQ(1/8)
About controllers
1.B controller does not have generator cool down function, or yes?
Re: B controller does have the function to start and stop generators.
2. For B controller, sticker for identifying ATNS specification displays only its rate such as Ir = 100A for
ATNS100. Can customer use it with other rating?
Re: Sure. (For TMD trip unit, 0.8-1 In adjustable)
3. Can I use other controller with ATNS such as UA controller?
Re: No for UA. Customer is not advised to use controllers other than ATNS controller to assure better
performance, but you can if your controller meet specific requirements.
4. Do we have other control voltage beside 220V AC for the controller?
Re: Till now, no.
5. In controller B, There is facility for fire indication. Could you confirm if the ATNS detect the fire, and
what happen the next, Is it only give indication or signal only, or ATNS will change to OFF position.
Re: ATNS will respond to fire signal but the product itself is not supposed to detect fire. When receiving fire
signal, the product will switch to OFF position automatically and shed the non-priority equipments (those not
related to fire production equipment). ATNS will return to primary position if only fire signal disappears.
33
FAQ(2/8)
About controllers (Continued)
6. If the Normal Source CB is tripped. Does the ATNS change to the replacement source or to the off
position?
Re: ATNS will not transfer to replacement source if CB tripped due to current fault to avoid further fault. Instead
it will stay still and LED on faceplate will indicate tripped signal. When the fault has been removed, please retrip CB unit by handle and push Automatic/manual operation switch to Automatic position , then push reset
button on controller to clear up the tripped indication , ATNS will return to normal automatic operation state.
7. For controller B, 255s is short because the required warm up time for generator is 7 minutes.
Re: We can work on that if necessary to change, technically no problem.
8. Need to improve the range of ATS controller auxiliary control supply. It should have at least +/- 10%
tolerance to prevent burning of the controller as some of the customer has a higher system voltage in their
plant.
Re: Control voltage for ATNS controller ranges from 85% to 115%.
9. Can you sell the controller in separate?
Re: Yes.
10. Do the controllers have self-failure detection function?
Re: No.
34
FAQ(3/8)
About installation and maintenance
1.If component in ATNS is damaged, can customer order only that component?
Re: Yes.
2. Customer asked about the maintenance period and how to do maintenance.
Re: Not decided yet.
3. Can customer adjust mechanical part of ATNS? For example, a rod at toggle switch may be error
after operating for a long time.
Re: Customers are not supposed to replace the mechanical parts by themselves.
4. If the CB is broken could we change the breaker only, Is it the same breaker with always use and
what accessories inside the breaker.
Re: CB can be replaced during maintenance in case of damage happening, but rearrangement of wiring will
be needed for accessories such as OF and SD. Technical support will be available from the manufacturer
when necessary. The breaker is normal CB, and inside which, 2 OF, 1 SD, 1SDE and 1 SDE adapter is
needed.
5. Can we use reverse power (incoming from the bottom, not from top) ? Because I see the power for
control, they take from top terminal. And in application usually incoming busbar from bottom. then to
the load.
Re: In china market most customers prefer incoming power from the top. As what you see the controller
power come from top voltage sampling wires, so if you want to reverse power and incoming from the bottom,
what we need to modify is just moving the voltage sampling wires to the bottom of CB. If you do have
volume demand in Indonesia market as this requirement, we can provide customized products.
35
FAQ(4/8)
About installation and maintenance (continued)
For B type controller
36
FAQ(5/8)
About handles
1. A lever arm, used for manual mode, is not locked with its slot.
Re: Handle is not supposed to be locked with its slot.
2. Where can customer hang or keep a lever arm? (For example, NW has
a place for keeping a lever arm.
Re: Customers can hang the lever arm inside switchboard. We may develop
the ergonomics function later.
3. The design of handle is not good enough because the key could be
damage if we use it often. And how about the compact NS630 is it the
same design because the force to lift up the toggle is heavier than NS100
Re: The test on handle was conducted strictly according to IEC 60947-617.2.4.2.2 (10% manually operation, >660 times) with satisfactory result.
Handles for NS630 and NS100 are not in same design; its much better in
terms of handle length and toggle strength.
Please send us the picture and we will conduct investigation into the matter if
any problem takes place during application.
37
FAQ(6/8)
About accessories
1. How can customer install auxiliary such as SD, SDE or MN by himself? QC sticker is adhered
between a mask motor mechanism module and plate so if he opens that mask, warranty may be
expired.
Re: Customers are not supposed to replace or add SD ,SDE and MN by themselves. Schneider After Sales
Service engineers have to offer the service.
2. How long will communication cable be available? Sometimes customers panel comprises B
controller on the top and breaker in the bottom. The existing communication cable is not long
enough.
Re: 2 meters are available.
3. Can we add on additional accessories?
- OF auxiliary switch
- SDE auxiliary switch
- MX shunt trip release
Re: Yes.
4. Do we have the coupling accessories for the present Compact ATNS?
Re: Yes. The coupling accessory can be used for any CB-type TSE.
38
FAQ(7/8)
About power supply insulation module
1. Dont you have indicator of fuse in power supply module. Customers
cant know fuse status.
Re: Fuse status can be indicated by LED.
2. What is the input voltage rating to the isolation module ?
Re: AC220V.
39
FAQ(8/8)
Other questions
1. Ratings should be more flexible or higher than 630A?
Re: We are working on ATNS 800~1250A; for rating higher than 1250A, UA/BA ATS is
recommended.
40
41
Q&A