Compact ATNS Training Seminar

Conducted by Jinxian Wang


& Jamie Song

Building a New Electric World

Agenda
TSE Introduction
Characteristics & Selling Points
Model Selection
Advantages Over Key Competitors
FAQ
Q&A

TSE Introduction

TSE, transfer switching equipment, equipment containing one or

more switching devices for disconnecting load circuits from one


supply and connecting to another supply (according to IEC)
TSE Classification (according to IEC)

by short-circuit capability

by method of controlling transfer

Class PC

MTSE

TSE that is capable of making and


withstanding, but is not intended for
breaking short-circuit currents
Class CB

Manually transfer switching equipment

TSE

TSE provided with over-current releases


and the main contacts of which are capable
of making and are intended for breaking
short-circuit currents

RTSE

Remote operated switching equipment

Class CC

ATSE

TSE that is capable of making and withstanding,


but is not intended for breaking short-circuit
currents. TSE based on devices fulfilling the
requirements of IEC 60947-4-1

Automatic transfer switching equipment

TSE Application (1/3)

For maximum continuity of service


4

TSE Application (2/3)

In a wide range of applications


5

TSE Application (3/3)


Buildings

Hospital
Bank
Office building
Business center
Others

Industry

Manufacturing center
Mining
Power plant
Others

Infrastructure

Airport
Port
Tunnel
Communication
Others

Agenda
TSE Introduction
Characteristics & Selling Points
Model Selection
Advantages Over Key Competitors
FAQ
Q&A

Characteristics (1/5)
Compact NS as switching device
(NS100/160/250/400/630)
Terminal

Motor mechanism module

Trip unit

Handle

Power supply
insulation module

Manual / automatic
operation interlock
Operating circuit breaker
(Compact NS)

Characteristics (2/5)
Multi-9 as switching device (C65)
Motor mechanism module

Handle

C65
Power supply
insulation module

Manual / automatic
interlock shutter

Characteristics (3/5)
2 types of control units applied to both Multi-9 and
Compact NS circuit breakers
B controller
(external type)

A controller
(built-in type)

DIP switch

10

Characteristics (4/5)
General characteristics
Compliance with standard

Pollution degree

IEC60

947-1 General rules


IEC60 947-2 Circuit breakers
IEC60 947-3 Switch, disconnectors, switchdisconnectors and fuse-combination units
IEC60 947-5 Control circuit devices and switching
equipment
IEC60 947-6-1 Multiple function equipment-Transfer
switching equipment

ATNS are certified for operation in pollutiondegree III environment as defined by IEC60947

ATNS General characteristics


55
Devices must be derated
for temperature higher than
40 (65 for motor
protection)
Storage temperature:
-50~85

ICE/CN 60068-2-30
damp heat (95% relative
humidity at 55)
ICE/CN 60068-2-52 salt
mist (severity level 2)
IEC/CN 600-2-56

-25

Tropicalisation

Ambient temperature

We are applying for CQC certificate for ATNS in China

11

Characteristics (5/5)
Technical characteristics

Rated operational voltage: 380/415V


Rated operational current: 1A630A
Number of poles: 2P/3P/4P
Mechanical durability 6600
Utilization type: AC33B
Control voltage: AC220V
Minimum switching time 2S/3S

12

Selling Points (1/7)


Reliable mechanical interlock

One motor driven transfer


Improved product reliability thanking

to reduced mechanical structural


components
Operating rod linear movement to

avoid handle breakage

13

Selling Points (2/7)


Anti-adhesion protection

When
circuit breaker contacts adhere to each
other or
handle breaks due to fault;
ATNS will not switch to prevent connection
to both supplies at the same time

14

Selling Points (3/7)


Effective protection against fault
Protection against short-circuit fault
In case of short-circuit fault, the circuit breaker will trip and stop power

supply to the load


meanwhile the internal electrical interlock prevents ATNS from switching to

assure system and equipments safety


Protection against mistaken wiring
If the phase line is connected to the neutral by mistake, ATNS will generate

alarming signals
Protection against non-execution
If the breaker fails to perform proper function within 5 seconds the switching

signal is sent, the controller will generate alarming signals

15

Selling Points (4/7)


Innovative U-shaped operating rod to assure quick
break of MCB

U-shaped rod

16

Selling Points (5/7)


Higher withstand voltage and safer auto/manual
interlock
Power supply insulation module increases the level of
withstand voltage;
Impulse withstand voltage 8KV/S
Power frequency withstand voltage 3000V
Manual/automatic interlock

Handle not permitted to


insert under auto mode

Power supply
insulation module

Auto/manual interlock

17

Selling Points (6/7)


Intelligent controller
Replace digital logic circuit control with microcomputer control
Integrate more software contents in hardware design to help reduce
cost and improve compatibility
Friendly parameter-setting programs
Strong fault tolerance capability
Multiple operation modes
Self-throw and self-reset
Self-throw without self-reset
Mutual backup

18

Selling Points (7/7)


2 types of controller to meet diversified demands
Controller
3-postion switch
"Normal"supply on
"Replacement"supply on
Stop(both "Normal" and "Replacement" supply off)
Automatic operation

A type

B type

Monitoring of "Normal"supply and automatic transfer

Phase failure, voltage loss

Monitoring of "Replacement"supply and automatic transfer


Generator set startup control
Delayed shutdown (adjustable) of generator set
Load shedding and reconnection of non-priority circuits (DC24V)
Self-throw and self-reset
Self-throw without self-reset
Mutual backup
Test
By test button on controller front panel
Indications
Circuit breaker status indication: on, off and fault trip
Normal and Replacement supply status indication
Parameter setting indication
Other functions
Transfer delay
Return transfer delay
Protection(alarm) against mistaken neutral connection to phase
Non-execution protection (5s after switching signal sent)
Communication
19
Control voltage

Optional

Phase failure, voltage loss


Undervoltage, overvoltage
Phase failure, voltage loss
Undervoltage, overvoltage

0s 5s 15s 30s precision<5% 0~255 continuously adjustable


0s 5s 15s 30s precision<5% 0~255 continuously adjustable

Modbus optional
AC220V 50/60Hz
AC220V 50/60Hz

Agenda
TSE Introduction
Characteristics & Selling Points
Model Selection
Advantages Over Key Competitors
FAQ
Q&A

20

Model Selection(1/2)
Dimensions for ATNS63

mm

G1

H1

K1

L1

P1

P2

P3

ATNS-63 N/H

142

157

445

70.5

220

55.5

190

167

465

17

130

161

6.5

Note:
4P ATNS shares same size with 3p ATNS
Handle not fixed

22

Model Selection(2/2)
Dimensions for ATNS100/160/250/400/630

mm

G1

H1

K1

L1

P1

P2

P3

P4MAX

ATNS 100/160/250
N/SX/H 3P

142

177

460

78

220

63

190

187

480

20

145

176

131

6.5

ATNS 100/160/250
N/SX/H 4P

142

212

530

78

220

63

190

222

550

20

145

176

131

6.5

ATNS 400/630 N/H 3P

280

242

580

97

285

82

255

257

610

20

180

232

188

ATNS 400/630 N/H 4P

280

287

670

97

285

82

255

302

700

20

180

232

188

Handle not fixed

23

Agenda
TSE Introduction
Characteristics & Selling Points
Model Selection
Advantages Over Key Competitors
FAQ
Q&A

24

Advantages Over Key Competitors(1/6)


Comparison with ABB
ABB: Class CB
Previous products: DPT/SE,DPT/TE
DPT/SE: for the automatic switching between two utility
powers or utility power and gasoline/diesel generator;
DPT/TE: for automatic switching between two utility
powers with bus tie circuit breaker;
New product: DPT
Power switching products for end switching control
Conventional thermal current: 63A,125A,160A 250A
Switching devices: S260,S1,S2,S3,S5
Our new products are used to compete against ABB
DPT/SE .

26

Advantages Over Key Competitors(3/6)


Comparison with ABB DPT/SE
Items

ABB DPT/SE

Compact ATNS

Added value for users

Controller

PLC, complicated programming,


large size

A and B type intelligent controller

More flexible design, easy to test, saving


installation space.

Protection

Voltage loss, under-voltage, overvoltage, phase failure

Auxiliary
protection

Trip alarming, phase failure


alarming, operation refusal
alarming

Operation refusal, protection against


mistaken wiring, protection against
adhesion, fire protection control

More reliable, safer

Operation mode

Automatic, forcible N, forcible


R, stop

Self-throw and self-reset, Self-throw and


without self-reset, mutual backup,manual

Meet local market demand

Operation
mechanism

Two motor driven mechanism

Single motor driven mechanism, bidirection rotation

Incorporate mechanical linkage improves


reliability and easy to install.

Delay

0.5 30S

Model A controller: 0 30S


Model B controller: 0 255S can be
adjusted continuously

Meet diversified needs

Communication

Unspecified in the samples

Model B controller: 485 interface,


modbus protocol

Easy for intelligent control

Indication

Signal light

Signal light, model B controller: LED


display

Easy and convenient operation and


maintenance

Power frequency withstand voltage is


3000V, impulse withstand voltage 8Kv.

Assure safety of equipment and load as


well as continuous power supply.

Power isolation

Unspecified in the samples

Voltage loss, under-voltage, over-voltage,


phase failure

27

Advantages Over Key Competitors(4/6)


Comparison with ABB DPT

ABB DPT

Compact ATNS

Added value for users

Product series

63 250A

63 630A

More complete product series

Controller

Single controller

A and B type intelligent controller

More flexible design, saving space

Protection

Voltage loss, under voltage,


over voltage, loss failure

Voltage loss, under voltage, over voltage,


loss failure

Auxiliary
protection

Operation refusal

Operation refusal, protection against


mistaken wiring, fire protection control

More reliable and safer

Operation mode

Self-throw and self-reset,


manual

Self-throw and self-reset, Self-throw and


non self-reset, mutual backup,manual

Meet diversified needs

Delay

0.2 30S

A type: 0 30S
B type: 0 255S continuously adjustable

Meet diversified needs

Flip mechanism

Model 63A: extended handle


flip mechanism

Model 63A U-shape flip mechanism

Solve the problem of breakable prolonged


handle to assure the quick breaking of MCB.

Communication

None

Type B controller: 485 interface,


Modbus protocol

Easy for intelligent control

Display

Signal light

Signal light, Type B controller: LED


display

Easy and convenient operation and


maintenance

Power isolation

None

Power frequency withstand voltage is


3000V, impulse withstand voltage 8Kv.

Assure safety of equipment and load as well


as continuous power supply.

28

Advantages Over Key Competitors(5/6)


Comparison with ABB DPT
SOCOMEC: Class PC
Products:

SIRCOVER/VE,SIRCOVER/VS
-SIRCOVER/VE: In 250A 3150A;
-SIRCOVER/VS: In 63A 630A;
-Marks in above figure: SMVE,SMVS;
Basic characteristics
-Conform to GB14048.3;
-Rich installation accessories: bridge, supporting terminal,
terminal shield, etc.;
-DC motor driven, operational for remote control.
Double-pole and double-throw contact structure

29

Advantages Over Key Competitors(6/6)


Comparison with SOCOMEC
Items

SOCOMEC VS

Compact ATNS

Product series

63 3150A

63 630A

Standard compliance

GB14048.3

GB14048.11

Minimum transfer time

1.8~2.8s

1.5~3s

Controller

OEM

Completed designed and produced by Schneider

Operation mode

Self-throw and self-reset, manual

4 types: Self-throw and self-reset, Self-throw and


non self-reset, mutual backup,manual

Communication

Unspecified in the samples

Model B controller 485 interface, Modbus


protocol

Indication

Signal light

Signal light, Model B controller LED display

Power isolation

None

Power frequency withstand voltage 3000V,


impulse withstand voltage 8Kv

Utilization type

AC23A/AC23B

AC33B

Electrical durability

125A 1000

100A 10000

30

Comparison with UA/BA ATS


Items

UA/BA

Compact ATNS

Product series

100 6300A

63 630A

Dimensions

Larger size, ATS 100A with height


198mm

Smaller size, ATNS 100A with height 145mm

Price

Much more expensive

Cheaper

Controller

UA/BA

A/B

Operation mode

Self-throw and self-reset, forced


on N, forced on R, manual

Self-throw and self-reset, Self-throw and non selfreset, mutual backup,manual

Communication

Applicable for UA150

B controller 485 interface, Modbus protocol

Indication

Signal light

Signal light, B controller LED indication

Power isolation

Yes

Yes

Installation and maintenance

Complicated

Supply with whole set, easy to install and maintain

Mechanical interlock

Complicated design with 2 motors

Single motor driven mechanism

31

Agenda
TSE Introduction
Characteristics & Selling Points
Model Selection
Advantages Over Key Competitors
FAQ
Q&A

32

FAQ(1/8)
About controllers
1.B controller does not have generator cool down function, or yes?
Re: B controller does have the function to start and stop generators.
2. For B controller, sticker for identifying ATNS specification displays only its rate such as Ir = 100A for
ATNS100. Can customer use it with other rating?
Re: Sure. (For TMD trip unit, 0.8-1 In adjustable)
3. Can I use other controller with ATNS such as UA controller?
Re: No for UA. Customer is not advised to use controllers other than ATNS controller to assure better
performance, but you can if your controller meet specific requirements.
4. Do we have other control voltage beside 220V AC for the controller?
Re: Till now, no.
5. In controller B, There is facility for fire indication. Could you confirm if the ATNS detect the fire, and
what happen the next, Is it only give indication or signal only, or ATNS will change to OFF position.
Re: ATNS will respond to fire signal but the product itself is not supposed to detect fire. When receiving fire
signal, the product will switch to OFF position automatically and shed the non-priority equipments (those not
related to fire production equipment). ATNS will return to primary position if only fire signal disappears.

33

FAQ(2/8)
About controllers (Continued)
6. If the Normal Source CB is tripped. Does the ATNS change to the replacement source or to the off
position?
Re: ATNS will not transfer to replacement source if CB tripped due to current fault to avoid further fault. Instead
it will stay still and LED on faceplate will indicate tripped signal. When the fault has been removed, please retrip CB unit by handle and push Automatic/manual operation switch to Automatic position , then push reset
button on controller to clear up the tripped indication , ATNS will return to normal automatic operation state.
7. For controller B, 255s is short because the required warm up time for generator is 7 minutes.
Re: We can work on that if necessary to change, technically no problem.
8. Need to improve the range of ATS controller auxiliary control supply. It should have at least +/- 10%
tolerance to prevent burning of the controller as some of the customer has a higher system voltage in their
plant.
Re: Control voltage for ATNS controller ranges from 85% to 115%.
9. Can you sell the controller in separate?
Re: Yes.
10. Do the controllers have self-failure detection function?
Re: No.

34

FAQ(3/8)
About installation and maintenance
1.If component in ATNS is damaged, can customer order only that component?
Re: Yes.
2. Customer asked about the maintenance period and how to do maintenance.
Re: Not decided yet.
3. Can customer adjust mechanical part of ATNS? For example, a rod at toggle switch may be error
after operating for a long time.
Re: Customers are not supposed to replace the mechanical parts by themselves.
4. If the CB is broken could we change the breaker only, Is it the same breaker with always use and
what accessories inside the breaker.
Re: CB can be replaced during maintenance in case of damage happening, but rearrangement of wiring will
be needed for accessories such as OF and SD. Technical support will be available from the manufacturer
when necessary. The breaker is normal CB, and inside which, 2 OF, 1 SD, 1SDE and 1 SDE adapter is
needed.
5. Can we use reverse power (incoming from the bottom, not from top) ? Because I see the power for
control, they take from top terminal. And in application usually incoming busbar from bottom. then to
the load.
Re: In china market most customers prefer incoming power from the top. As what you see the controller
power come from top voltage sampling wires, so if you want to reverse power and incoming from the bottom,
what we need to modify is just moving the voltage sampling wires to the bottom of CB. If you do have
volume demand in Indonesia market as this requirement, we can provide customized products.
35

FAQ(4/8)
About installation and maintenance (continued)
For B type controller

36

FAQ(5/8)
About handles
1. A lever arm, used for manual mode, is not locked with its slot.
Re: Handle is not supposed to be locked with its slot.
2. Where can customer hang or keep a lever arm? (For example, NW has
a place for keeping a lever arm.
Re: Customers can hang the lever arm inside switchboard. We may develop
the ergonomics function later.
3. The design of handle is not good enough because the key could be
damage if we use it often. And how about the compact NS630 is it the
same design because the force to lift up the toggle is heavier than NS100
Re: The test on handle was conducted strictly according to IEC 60947-617.2.4.2.2 (10% manually operation, >660 times) with satisfactory result.
Handles for NS630 and NS100 are not in same design; its much better in
terms of handle length and toggle strength.
Please send us the picture and we will conduct investigation into the matter if
any problem takes place during application.

37

FAQ(6/8)
About accessories
1. How can customer install auxiliary such as SD, SDE or MN by himself? QC sticker is adhered
between a mask motor mechanism module and plate so if he opens that mask, warranty may be
expired.
Re: Customers are not supposed to replace or add SD ,SDE and MN by themselves. Schneider After Sales
Service engineers have to offer the service.
2. How long will communication cable be available? Sometimes customers panel comprises B
controller on the top and breaker in the bottom. The existing communication cable is not long
enough.
Re: 2 meters are available.
3. Can we add on additional accessories?
- OF auxiliary switch
- SDE auxiliary switch
- MX shunt trip release
Re: Yes.
4. Do we have the coupling accessories for the present Compact ATNS?
Re: Yes. The coupling accessory can be used for any CB-type TSE.

38

FAQ(7/8)
About power supply insulation module
1. Dont you have indicator of fuse in power supply module. Customers
cant know fuse status.
Re: Fuse status can be indicated by LED.
2. What is the input voltage rating to the isolation module ?
Re: AC220V.

39

FAQ(8/8)
Other questions
1. Ratings should be more flexible or higher than 630A?
Re: We are working on ATNS 800~1250A; for rating higher than 1250A, UA/BA ATS is
recommended.

40

Give the best of the New Electric World


to everyone, everywhere, at any time

41

Q&A