Académique Documents
Professionnel Documents
Culture Documents
Seminar 4:
Power Transformers
Textbook Reading: Chapter 3
Overview
Topics covered in this lecture:
Ideal
Transformer
Lossless transformer:
Example 3.1
Real Transformers
Real transformers
have losses
have leakage flux
have finite permeability of magnetic core
Real power losses
resistance in windings (i2 R)
core losses due to eddy currents and
hysteresis
Eddy currents arise because of
changing flux in core
Eddy currents are reduced by
laminating the core
Hysteresis losses are proportional
to area of BH curve and the
frequency
Hysteresis losses are reduced by
using material with a thin BH curve
10
Transformer Example
A single phase, 100 MVA, 200/80 kV transformer has the following test data:
short circuit: 30 kV, with 500 kW losses
open circuit: 20 amps, with 10 kW losses
Determine the model parameters.
From the short circuit test
100 MVA
30 kV
I sc
500 A, R e jX e
60
200kV
500 A
2
Psc Re I sc
500 kW R e 2 ,
Hence X e 602 22 60
From the open circuit test
Gc
-jBm
rc 2002 kV 4 M 10kW
8
R
Poc c GcV
25
10
S
2
10ockW c
200kV
200 kV
20
A
8 10, 000 16
R
jX
jX
Xm
m
Gc e jBm e
2010A 4 S 10,
000
Bm 10
625 10 10 4 S
200kV
11
Example 3.2
12
Example 3.2
(cont.)
13
Per-Unit Calculations
A key problem in analyzing power systems is the large number
of transformers.
It would be very difficult to continually have to refer
impedances to the different sides of the transformers
This problem is avoided by a normalization of all variables.
This normalization is known as per unit analysis.
actual quantity
quantity in per unit
base value of quantity
14
2.
3.
4.
5.
15
Example 3.3
16
17
Per-Unit Solution
Advantages of using the normalization and per-unit system are:
The transformer turn-ratio equivalent circuit can be eliminated;
Device parameters fall into a narrow range;
The voltage throughout the power system is normally close to unity.
Rules for base quantities:
The value of Sbase is the same for the entire power system of concern.
The ratio of voltage bases on either side of a transformer is selected to
be the same as the ratio of the transformer voltage ratings.
When several components are involved, the individual ratings may be
different. To convert a given impedance into the equivalent impedance:
18
100
X e 0.0369
0.0683 p.u.
54
100
X e 0.10
0.0286 p.u.
350
230 2
0.0286
15.1
100
actual quantity
base value of quantity
ZB = (VB)2/SB
19
Per-Unit Example
Solve for the current, load voltage and load power in the circuit shown
below using per unit analysis with an SB of 100 MVA, and voltage bases of
8 kV, 80 kV and 16 kV.
8kV 2
Left
ZB = (VB)2/SB
ZB
0.64
100 MVA
Z BMiddle
IB = VB/ZB = SB/VB
80kV 2
64
100 MVA
16kV 2
2.56
100 MVA
0.22 30.8 p.u. (not amps)
Z BRight
Original Circuit
1.00
3.91 j 2.327
VL 1.00 0.22 30.8
I
p.u.
2
V
SL
L 0.189 p.u.
Z
SG 1.00 0.2230.8 30.8p.u.
VL I L*
0.22
30.8
Amps
275
30.8
Middle
I Middle
Example 3.4
actual quantity
base value of quantity
21
22
23
Three-Phase Per-Unit
Procedure is very similar to 1 except we use a 3 VA base, and use line to
line voltage bases:
1.
2.
Pick a voltage base for each different voltage level, VB. Voltages are
line to line.
3.
ZB
VB2, LL
S B3
( 3 VB ,LN ) 2
3S 1B
VB2, LN
S 1B
5.
3
1
1
S
3
S
S
B
B
B I1
I3B
B
3 VB , LL
3 3 VB , LN VB , LN
Exactly the same current bases as with single phase!
p.u.
2
V
SL
L 0.189 p.u.
Z
SG 1.00 0.2230.8 30.8p.u. V Actual 0.859 30.8 27.6 kV 23.8 30.8 kV
L
VL I L*
300 MVA
1250 Amps (same current!)
3 138 kV
I Actual
25
Middle 0.22 30.8 Amps 275 30.8
Example 3.5
actual quantity
base value of quantity
26
27
Y-Y Connection
28
Per-phase model:
29
- Connection
Magnetic coupling with AB/ab, BC/bb & CA/ca
VAB
I
1 I
1
a, AB , A
Vab
I ab a I a a
3 Detailed Model:
Per-phase model:
To use the per phase equivalent we need to use the delta-wye load
transformation. Per phase analysis similar to Y-Y except impedances are
decreased by a factor of 3.
Key disadvantage is - connections can not be grounded; not commonly
30
used.
-Y Connection
VAB
V
a, AB Van Vab 3 Van30
Van
a
VAB 30
V 30
and Van 3 An
a
a
For current we get
I AB 1
I a a I AB
I ab a
Hence Vab 3
I A 3 I AB 30 I AB
a a
1
I A30
3
1
I A30
3
Y- Connection
Per-phase model:
32
Example 3.6
33
34
35
Example 3.7
36
37
Example 3.8
38
Three-Winding Transformers
39
Example 3.9
40
Example 3.10
41
Autotransformers
Autotransformers are transformers in which the primary and secondary
windings are coupled magnetically and electrically.
This results in lower cost, and smaller size and weight.
The key disadvantage is loss of electrical isolation between the voltage
levels. This can be an important safety consideration when a is large.
For example in stepping down 7160/240 V we do not ever want 7160 on
the low side!
42
Example 3.11
43
44
45
Example 3.12
46
47
48
49
Distribution Transformer
Radiators
W/Fans
LTC
Phase-Shifting Transformers
Phase shifting transformers are used to control the phase angle across the
transformer.
Since power flow through the transformer depends upon phase angle, this
allows the transformer to regulate the power flow through the transformer.
Phase shifters can be used to prevent inadvertent "loop flow" and to prevent
line overloads.
51
Example 3.13
53
54
55
230/115 kV Transformer
230 kV
surge
arrestors
115 kV
surge
arrestors
Oil Cooler
Radiators
W/Fans
Oil
pump
56
Summary
The Ideal Transformer
Equivalent Circuits
The Per-Unit System
Three-Phase Transformers
Three-Winding Transformers
Autotransformers
Load Tap Changing Transformers
57