VAV Systems
period one
What Is Variable Air Volume?

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Constant-Volume,
Variable-Temperature System

supply cooling OA
fan coil

SA
thermostat RA

space
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
constant-volume, variable-temperature-system
Full Load

Supply Sensible Heat Gain


Airflow
=
1.085 (Space DB Supply DB)
With these design conditions
space sensible heat gain = 40,000 Btu/hr
space dry-bulb temperature = 75F
supply air dry-bulb temperature = 55F

Supply 40,000 Btu/hr


Airflow
= = 1,840 cfm
1.085 (75F 55F)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
constant-volume, variable-temperature system
Part Load

Supply Space Sensible Heat Gain


DB = DB

1.085 Supply Airflow
With these part load conditions
space sensible heat gain = 20,000 Btu/hr
space dry-bulb temperature = 75F
supply airflow = 1,840 cfm

Supply 20,000 Btu/hr


DB = 75F = 65F
1.085 1,840 cfm
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
constant-volume, variable-temperature system
Applied To Multiple Spaces

single thermostat
Im
fine.

Its stuffy
in here!

Im
Im freezing!
hot!

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


constant-volume, variable-temperature system
Applied To Multiple Spaces

80F
65F

55F

55F 65F

reheat coil
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Terminal Reheat System
EA RA

OA supply PA
fan

cooling reheat
coil coil

thermostat
SA
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Variable-Air-Volume System
EA RA

OA supply PA
fan

cooling VAV
coil box
variable-
speed drive
thermostat SA
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
variable-air-volume (VAV) system
Full Load
With these design conditions
space sensible heat gain = 40,000 Btu/hr
space dry-bulb temperature = 75F
supply air dry-bulb temperature = 55F

Supply 40,000 Btu/hr


Airflow
= = 1,840 cfm
1.085 (75F 55F)

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


variable-air-volume (VAV) system
Part Load
With these part load conditions
space sensible heat gain = 20,000 Btu/hr
space dry-bulb temperature = 75F
supply air dry-bulb temperature = 55F

Supply 20,000 Btu/hr


Airflow
= = 920 cfm
1.085 (75F 55F)

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


why VAV?
Part-Load Energy Savings

Reduced fan energy


Reduced refrigeration energy

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


why VAV?
Comfort
Dedicated terminal units
Dedicated thermostats Im
quite
cozy.

Its nice
in here!

Im Ahhh!
fine.

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


System Comparison
constant-volume, constant-volume,
single zone VAV
terminal reheat
Constant fan energy Constant fan energy Fan energy savings
Nearly constant refrigeration
Refrigeration energy energy
Refrigeration energy
savings savings
Delivers comfort to many
Delivers comfort to spaces inefficiently Delivers comfort to
only one thermal zone Reheat energy increases at many spaces efficiently
part load

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


variable-air-volume system
Building Characteristics

Variable thermal load profiles


Multiple, independently-controlled
spaces
Common return air path

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Variable Thermal Load Profiles

100 east-facing
space
west-facing
percent space load

75 space

50

25

6 12 6
a.m. noon p.m.
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Multiple,
Independently-Controlled Spaces
Dedicated terminal units
Dedicated thermostats

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Common Return Air Path

Space 1 Space 2 Space 3

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV Systems
period two
Components Of A VAV System

American Standard Inc. 1999 Air Conditioning Clinic 2803-8-1999


components of a
VAV System
return air path

relief
fan
supply
supply ductwork
fan
VAV
central box
air handler

thermostat

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Airflow Modulation

rotating
blade damper

air valve

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Rotating Blade Damper

airflow

blade actuator
damper
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Air Valve

airflow

damper actuator
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Near-Linear Performance
100

80 VariTrane
air valve
% nominal airflow

60

40 ce
an
o rm
20 erf rotating
r p
ea blade damper
li n

0 20 40 60 80 100
American Standard Inc. 1999
% wide open position Air Conditioning Clinic TRG-TRC014-EN
VAV Terminal Units

supply
air

terminal heating coil


primary
filter
air terminal mixing fan
airflow
modulation
device
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit types
Single-Duct, Cooling-Only

supply
air

primary
air

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit types
Single-Duct, Cooling-Only
remote source of heat maximum
100% primary
airflow
heating tempering
% airflow to space

minimum
primary
airflow
primary air
0%
design design
heating load space load cooling load
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Space Heating With A VAV System
terminal
mixing fan plenum air

remote
heating heat source
coil
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit types
VAV Reheat

supply
air

primary
air
terminal
heating coil

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit types
VAV Reheat
maximum
100% heating coil active primary
airflow
heating tempering
% airflow to space

minimum
heating
airflow

minimum
cooling
primary air airflow

0%
design design
heating load space load cooling load
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit types
Fan-Powered

warm
plenum air

parallel
cool
primary air

series
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit types
Parallel, Fan-Powered

supply
terminal air
mixing fan

plenum
air

primary
air
terminal
heating coil

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit types
Parallel, Fan-Powered
maximum
100% primary
heating tempering airflow
% airflow to space

plenum air
minimum
primary
airflow
primary air
0%
design design
heating load space load cooling load
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit types
Series, Fan-Powered
terminal
heating coil

supply
primary air
air
plenum
air

terminal
mixing fan
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit types
Series, Fan-Powered
maximum
100%
primary
airflow

heating tempering
% airflow to space

plenum air minimum


primary
airflow
primary air
0%
design design
heating load space load cooling load
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit types
Parallel vs. Series Fan-Powered

Constant airflow to the space


Acoustics

Fan energy consumption

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit types
Single-Duct VAV Systems
central air handler

OA PA
90F 55F

VSD
RA single-duct
EA 80F VAV terminal units

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit types
Dual-Duct
supply
air

warm
primary air

cool
primary air

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


dual-duct system
Variable Air Volume To The Space
maximum
100%
heating tempering primary
airflow
% airflow to space

warm
primary air minimum
primary
airflow
cool primary air
0%
design design
heating load space load cooling load
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
dual-duct system
Constant Air Volume To The Space
maximum
100%
primary
airflow
warm
primary air
% airflow to space

minimum
primary
airflow
cool primary air
0%
design design
heating load space load cooling load
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit types
Single-Fan, Dual-Duct VAV System
central air handler cooling 55F
coil
OA
40F 55F
heating 105F
coil
dual-duct
VSD VAV
terminal
EA RA units
75F

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit types
Two-Fan, Dual-Duct VAV System
OA PA 55F
40F 55F

cooling
air handler dual-duct
VAV
terminal
heating units
air handler
RA PA 105F
EA 75F

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV Terminal Unit Controls

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit controls
Upstream Pressure Affects Airflow

1,000 cfm
0.70 in. wg
static pressure VAV terminal unit
in supply duct (identical damper positions)

1,300 cfm
0.80 in. wg
static pressure
in supply duct
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit controls
Pressure-Dependent Control
Space sensor controls position of the modulating device
Airflow to space depends on SP in upstream duct system

Pressure-Independent Control
Space sensor controls desired airflow
Airflow to space is controlled directly,
independent of SP in upstream duct system

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit controls
Primary Airflow Measurement

airflow

measured
pressure
difference

airflow sensor
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit controls
Terminal Unit Control Technologies

Pneumatic control
Electronic control
Direct digital control (DDC)

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit controls
Pneumatic

primary
air

return bladder pneumatic


spring pressure
damper
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit controls
Pneumatic
Pneumatic Volume Regulator (PVR) provides
pressure-independent control
Pneumatic thermostat directly controls terminal
unit fan and heat source
Minimum and maximum airflow settings
adjusted physically on PVR
Compressed air operates modulation device,
PVR and space thermostat

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit controls
Electronic

gear threaded shaft


primary
air
damper
motor

damper

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit controls
Electronic
Electronic pressure transducer provides
pressure-independent control
Electronic controller positions modulation
device, controls terminal fan and heat source
Minimum and maximum airflow settings
adjusted physically on electronic controller
Electric power supply operates modulation
device and electronic controller

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV terminal unit controls
Direct Digital Control (DDC)

central air handler

DDC/VAV
terminal units
communicating
building automation
American Standard Inc. 1999
system (BAS) Air Conditioning Clinic TRG-TRC014-EN
VAV terminal unit controls
Direct Digital Control (DDC)
Electronic pressure transducer provides
pressure-independent control
Digital controller positions modulation device,
controls terminal fan and heat source
Minimum and maximum airflow settings
adjusted through communication link
Electric power supply operates modulation
device and electronic controller

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Diffusers
flexible
duct

diffuser
sheet metal
supply duct

VAV
primary air
terminal unit
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
diffusers
Linear Slot
linear
slot supply air
Coanda effect diffuser

supply duct

55F 55F

air from
space 5 ft

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


diffusers
Ceiling Compatibility

hanger wire

ceiling tile

cross T

structural T

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


diffusers
Ceiling Compatibility

cross T
air slot flange ceiling
tile
mounting feet

cross T
air slot
structural T
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Supply Duct System
central
air handler

diffuser

flexible
duct
sheet metal
supply duct

VAV
terminal
American Standard Inc. 1999
unit Air Conditioning Clinic TRG-TRC014-EN
Duct Design

Equal friction method


equal static pressure drop per unit length of duct
design can be performed by hand

Static regain method


relatively constant static pressure throughout system
desirable for VAV system duct design
design often requires a computer program

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Duct Design Recommendations
Keep as simple and symmetrical as possible
Locate main runs, branch runs, and terminal units
above hallways or unoccupied spaces
Minimize use of flexible ductwork upstream of
terminal units
Use duct lining or a duct silencer in first duct
section to attenuate supply fan noise
Place balancing dampers upstream of diffusers in
all noncritical branches
Reducing transitions should be several duct
diameters upstream of terminal units
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
VAV Systems
period three
System Configurations

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Perimeter (P) vs. Interior (I) Spaces

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Perimeter Spaces

overhead
heating
perimeter
heating

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


perimeter space heating
Baseboard
heat loss > 450 Btu/hr/ft

cooling-only
VAV terminal unit
baseboard
heating system
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
perimeter space heating
Overhead Supply

diffusers in
center of space
( < 250 Btu/hr/ft )

diffusers blanket
perimeter wall
American Standard Inc. 1999
( 250-450 Btu/hr/ft ) Air Conditioning Clinic TRG-TRC014-EN
perimeter spaces
VAV Reheat
heat loss < 250 Btu/hr/ft

VAV reheat
terminal unit

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


perimeter spaces
Fan-Powered VAV
heat loss < 250 Btu/hr/ft

parallel,
fan-powered VAV
terminal unit

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


perimeter spaces
Dual-Duct VAV
heat loss < 250 Btu/hr/ft warm
primary air

cool
primary air

dual-duct VAV
terminal unit

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Interior Spaces
cooling-only
VAV terminal unit

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


interior spaces
Reheat Required
VAV reheat
terminal unit

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Small Buildings

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Changeover/Bypass VAV System
EA
RA

bypass damper

OA supply PA
fan
VAV
damper

constant-volume supply fan


VAV to spaces SA

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


System-Level Control Modes

Occupied mode
Unoccupied mode
Morning warm-up/cool-down mode

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Occupied Mode
Main supply fan operates continuously
Constant primary-air setpoint
Main supply fan controlled to maintain the
system static pressure setpoint
Outdoor air damper delivers proper amount of
ventilation air
Terminal units maintain respective occupied
space thermostat setpoints

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Unoccupied Mode
Main supply fan operates only as needed to
maintain thermostat setpoints
Main supply fan controlled to maintain the
system static pressure setpoint
Outdoor air damper is closed
Terminal units maintain respective
unoccupied space thermostat setpoints

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Morning Warmup/Cooldown Mode
Main supply fan operates continuously
Main supply fan controlled to maintain the
system static pressure setpoint
Outdoor air damper is closed, unless required
for preoccupancy purge
Terminal units are either fully open or
modulated to maintain their respective
occupied space thermostat setpoints

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV Systems
period four
Fan Modulation

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Fan Performance Curve

fan speed (rpm)


static pressure (in. wg)

performance
curve
2.7

1,0
00
24,000
airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
System Resistance Curve

system
static pressure (in. wg)

resistance
curve
2.7

1.05

15,000 24,000
airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Fan Operating Point

performance system
curve resistance
static pressure (in. wg)

curve
2.7 A
operating
point

1,0
00
rpm
24,000
airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
"Riding The Fan Curve"
new system
resistance
curve
static pressure (in. wg)

3.15 B
system
2.7 static increase A resistance
curve

1,0
00
airflow

rpm
reduction

18,000 24,000
airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Forward-Curved Centrifugal Fan
horsepower
15 20 25
static pressure (in. wg)

3.15 B

2.7 A

unstable
operation

1,0
00
rpm
18,000 24,000
airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Fan Modulation Curvestatic pressure (in. wg)

fan modulation
sensor point curve

airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Fan Control Loop

static pressure
supply sensor
fan

controller

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV Fan Modulation

new system
resistance
static pressure (in. wg)

curve
system
resistance
A curve
fan modulation B
curve

airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Fan Modulation Methods

Discharge dampers
Inlet vanes
Fan speed control
Variable-pitch blade control

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Discharge Dampers

supply
fan
discharge
dampers

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Discharge Dampers

new system
resistance
static pressure (in. wg)

curve
system
damper resistance
SP loss A curve
fan
modulation B
curve

airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Fan Inlet Vanes

inlet
vanes

supply
fan

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Fan Inlet Vanes

new system
resistance
static pressure (in. wg)

curve
system
resistance
B A curve
fan
modulation
curve
80 90 inlet vane
100
position (%)

airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Fan Speed Control

supply
fan

variable-
speed drive

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Fan Speed Control
new system
fan speed curves (rpm) resistance
curve
static pressure (in. wg)

system
A
resistance
curve
B
fan modulation

1,0
curve

90
80

00
0r
0r

rpm
pm
pm

airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Variable-Pitch Blade Control

adjustable
pitch
blades

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Variable-Pitch Blade Control
new system
resistance
stall
curve
total pressure (in. wg)

region
system
resistance
B A curve
50
fan modulation
45
curve 40
35

blade pitch angle

airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Fan Modulation Comparisons
100

90 BI fan with
discharge
80 dampers
70
AF fan with
% design BHP

60
inlet vanes
50

40
FC fan with FC fan with
30 discharge inlet vanes
20
dampers
10
frequency
0 inverter
10 20 30 40 50 60 70 80 90 100
% design airflow
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Controlling System Static Pressure

Fan outlet static pressure control


Supply duct static pressure control
Optimized static pressure control

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Fan Outlet Static Pressure Control
sensor located
at fan outlet

VAV
terminal units
supply
fan

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Supply Duct Static Pressure Control
sensor located approximately
2/3 down supply duct

VAV
terminal units
supply
fan

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Optimized Static Pressure Control
sensor located damper
at fan outlet static positions
pressure
supply sensor
fan
VAV
terminal
communicating units
BAS

fan speed or
inlet vane position
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
static pressure control
Part-Load Comparison

control airflow fan SP brake % full-load


method (cfm) (in. wg.) horsepower power

full load 24,000 2.70 22 ---


part load
fan outlet 18,000 2.13 13 60%
supply duct 18,000 1.85 12 55%
optimized 18,000 1.52 9.5 43%

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV Systems
period five
Application Considerations

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


System-Level Ventilation

RA

OA PA

VAV #1 VAV #2 VAV #3


primary air (PA) 3000 = 1000 + 1000 + 1000
OA required 700 = 200 + 200 + 300
ventilation fraction 0.20 0.20 0.30

ASHRAE Standard 62-1989 (Equation 6-1)


American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Ventilation Reset
outdoor airflow
measurement RA central air handler
and control with controls

OA PA

VAV terminal units


with DDC controls

communicating BAS
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Freeze Protection For Coils

RA
80F

warm air
OA
mixed air
10F

cold air
cooling
coil

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Measures To Prevent Coil Freeze-Up
Drain coils during cold weather
Keep water in motion
Add glycol to the water
Use face-and-bypass dampers to limit
amount of cold airflow through coil
Preheat the outdoor air
(heating coil, heat recovery)

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Part-Load Space Humidity Control
part-load space conditions ...
CV system = 75F DB / 66% RH
VAV system = 75F DB / 58% RH

mixed air
supply air

55F 60F 75F

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Part-Load Supply Air Tempering
overcooled space conditions ...
68F DB / 74% RH

RH
0%
7

supply air

55F 68F

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Building Pressure Control
EA
RA

OA supply PA
fan

SA
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
building pressure control
Direct Pressurization Control
EA
RA

relief
fan

OA supply PA
fan

controller

outdoor representative SA
static pressure space static
American Standard Inc. 1999
pressure Air Conditioning Clinic TRG-TRC014-EN
VAV Systems
period six
Review

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Review Period 1
EA
RA

OA PA

VAV
central
box
air handler

thermostat
SA
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Review Period 2

fan-powered
VAV terminal unit

single-duct, cooling-only dual-duct


VAV terminal unit VAV terminal unit
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Review Period 3

perimeter spaces interior spaces

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


Review Period 4

new system
fan performance resistance
static pressure (in. wg)

curve curve
system
resistance
curve
fan modulation B A
curve

airflow (cfm)
American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN
Review Period 5

System-level ventilation
Freeze protection for coils
Part-load space humidity control
Building pressure control

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN


VAV Systems
A Trane Air Conditioning Clinic

American Standard Inc. 1999 Air Conditioning Clinic TRG-TRC014-EN