GE Consumer & Industrial
Multilin
Protection Fundamentals
By
John Levine
2
GE Consumer & Industrial
Multilin
Outline
Introductions
Tools
Enervista Launchpad
On Line Store
Demo Relays at Levine
ANSI number
Training CDs
Protection Fundamentals
3
GE Consumer & Industrial
Multilin
Objective
We are here to help make your job easier.
This is very informal and designed around
Applications. Please ask question. We
are not here to preach to you.
The knowledge base in the room varies
greatly. If you have a question, there is a
good chance there are 3 or 4 other people
that have the same question. Please ask
it.
4
GE Consumer & Industrial
Multilin
Tools
5
GE Consumer & Industrial
Multilin
6
GE Consumer & Industrial
Multilin
Demo Relays at L-3
7
GE Consumer & Industrial
Multilin
Relays at L-3
8
GE Consumer & Industrial
Multilin
9
GE Consumer & Industrial
Multilin
GE Multilin Training CDs
10
GE Consumer & Industrial
Multilin
ANSI Symbols
11
GE Consumer & Industrial
Multilin
Conversion of Electro-Mechanical
to Electronic sheet
12
GE Consumer & Industrial
Multilin
PowerPoint presentations at:
http://l-3.com/private/ieee/
13
GE Consumer & Industrial
Multilin
Protection Fundamentals
14
GE Consumer & Industrial
Multilin
Desirable Protection Attributes
Reliability: System operate properly
Security: Dont trip when you shouldnt
Dependability: Trip when you should
Selectivity: Trip the minimal amount to clear the fault or
abnormal operating condition
Speed: Usually the faster the better in terms of
minimizing equipment damage and maintaining system
integrity
Simplicity: KISS
Economics: Dont break the bank
15
GE Consumer & Industrial
Multilin
Art & Science of Protection
Selection of protective relays requires
compromises:
Maximum and Reliable protection at minimum
equipment cost
High Sensitivity to faults and insensitivity to
maximum load currents
High-speed fault clearance with correct
selectivity
Selectivity in isolating small faulty area
Ability to operate correctly under all
predictable power system conditions
16
GE Consumer & Industrial
Multilin
Art & Science of Protection
Cost of protective relays should be
balanced against risks involved if
protection is not sufficient and not
enough redundancy.
Primary objectives is to have faulted
zones primary protection operate first,
but if there are protective relays
failures, some form of backup
protection is provided.
Backup protection is local (if local
primary protection fails to clear fault) 17
20
GE Consumer & Industrial
Multilin
Instantaneous Overcurrent Protection (IOC) &
CTI
Definite Time Overcurrent
Relay closest to fault operates
first
Relays closer to source
t operate slower
Time between operating for
same current is called CTI
(Clearing Time Interval)
CTI
50 50
+2 +2
Distribution
Substation
21
GE Consumer & Industrial
Multilin
(TOC) Coordination
Relay closest to fault operates
first
Relays closer to source
t operate slower
Time between operating for
same current is called CTI
CTI
Distribution
Substation
22
GE Consumer & Industrial
Multilin
Time Overcurrent Protection (TOC)
Selection of the
curves uses what is
termed as a time
multiplier or time
dial to effectively
shift the curve up or
down on the time axis
Operate region lies
above selected curve,
while no-operate
region lies below it
Inverse curves can
approximate fuse 23
curve shapes GE Consumer & Industrial
Multilin
Time Overcurrent Protection
(51, 51N, 51G)
Multiples of pick-
up
24
GE Consumer & Industrial
Multilin
Types of Protection
Differential
current in = current out
Simple
Very fast
Very defined clearing area
Expensive
Practical distance limitations
Line differential systems overcome this using
digital communications
26
GE Consumer & Industrial
Multilin
1 pu
IP
CT-X CT-Y IP
Differential
IS IS
Note CT polarity
Relay dots
IR-X IR-Y
This is a
+1
through-current
1 + (-1) = 0 representation
Current, pu
0 Perfect
waveforms, no
-1 saturation
DIFF CURRENT
27
GE Consumer & Industrial
Multilin
Differential
2 pu 2 pu
IP
Fault
CT-X CT-Y IP
X
IS IS
Note CT
IR-X
Relay
IR-Y polarity dots
This is an
+2
internal fault
2 + (+2) = 4
representation
Current, pu
Perfect
0
-2 waveforms, no
DIFF CURRENT
saturation
28
GE Consumer & Industrial
Multilin
Types of Protection
Voltage
Uses voltage to infer fault or abnormal condition
May employ definite time or inverse time curves
May also be used for undervoltage load shedding
Simple
May be slow
Selectivity at the cost of speed (coordination stacks)
Inexpensive
29
GE Consumer & Industrial
Multilin
Types of Protection
Frequency
Uses frequency of voltage to detect power
balance condition
May employ definite time or inverse time curves
Used for load shedding & machinery
under/overspeed protection
Simple
May be slow
Selectivity at the cost of speed can be expensive
30
GE Consumer & Industrial
Multilin
Types of Protection
Power
Uses voltage and current to determine
power flow magnitude and direction
Typically definite time
Complex
May be slow
Accuracy important for many applications
Can be expensive
31
GE Consumer & Industrial
Multilin
Types of Protection
Distance (Impedance)
Uses voltage and current to determine impedance of fault
Set on impedance [R-X] plane
Uses definite time
Impedance related to distance from relay
Complicated
Fast
Somewhat defined clearing area with reasonable accuracy
Expensive
Communication aided schemes make more selective
32
GE Consumer & Industrial
Multilin
X ZL
Impedance
Relay in Zone 1 operates first
Time between Zones is called
CTI
R
T2 ZB
ZA
T1
21 21
A B
Source
33
GE Consumer & Industrial
Multilin
Typical
Generation-typically at 4-
Bulk
20kV Power
Transmission-typically at 230- System
765kV
Receives power from transmission
system and transforms into
subtransmission level
Subtransmission-typically at 69-161kV
~
Generator XFMR Bus Line Bus XFMR Bus Motor
37
GE Consumer & Industrial
Multilin
Zone Overlap
1. Overlap is accomplished by the locations of CTs, the key
source for protective relays.
2. In some cases a fault might involve a CT or a circuit breaker
itself, which means it can not be cleared until adjacent
breakers (local or remote) are opened.
CTs are located at both sides of CTs are located at one side
CB-fault between CTs is cleared from of CB-fault between CTs is sensed
both remote sides by both relays, remote right side
operate only.
38
GE Consumer & Industrial
Multilin
What Info is Required to Apply Protection
1. One-line diagram of the system or area involved
2. Impedances and connections of power equipment,
system frequency, voltage level and phase sequence
3. Existing schemes
4. Operating procedures and practices affecting
protection
5. Importance of protection required and maximum
allowed clearance times
6. System fault studies
7. Maximum load and system swing limits
8. CTs and VTs locations, connections and ratios
9. Future expansion expectance
10.Any special considerations for application. 43
GE Consumer & Industrial
Multilin
C37.2:
Device
Numbers
Partial listing
44
GE Consumer & Industrial
Multilin
One Line Diagram
Non-dimensioned diagram showing how
pieces of electrical equipment are
connected
Simplification of actual system
Equipment is shown as boxes, circles and
other simple graphic symbols
Symbols should follow ANSI or IEC
conventions
45
GE Consumer & Industrial
Multilin
1-Line Symbols [1]
46
GE Consumer & Industrial
Multilin
1-Line Symbols [2]
47
GE Consumer & Industrial
Multilin
1-Line Symbols [3]
48
GE Consumer & Industrial
Multilin
1-Line Symbols [4]
49
GE Consumer & Industrial
Multilin
1-Line [1]
50
GE Consumer & Industrial
Multilin
1-Line [2]
3-Line
52
GE Consumer & Industrial
Multilin
CB Trip Circuit (Simplified)
55
GE Consumer & Industrial
Multilin
Lock Out Relay
58
GE Consumer & Industrial
Multilin
CB Coil Circuit Monitoring:
T with CB Closed; C with CB Opened
+
Relay
52/a
or
52/b
Breaker
T/C
Coil
52/a for trip circuit
52/b for close circuit
-
59
GE Consumer & Industrial
Multilin
CB Coil Circuit Monitoring:
Both T&C Regardless of CB state
Relay Relay
Breaker Breaker
60
GE Consumer & Industrial
Multilin
Current Transformers
Current transformers are used to step primary system
currents to values usable by relays, meters, SCADA,
transducers, etc.
CT ratios are expressed as primary to secondary;
2000:5, 1200:5, 600:5, 300:5
A 2000:5 CT has a CTR of 400
61
GE Consumer & Industrial
Multilin
Standard IEEE CT Relay
Accuracy
IEEE relay class is defined in terms of the voltage a CT
can deliver at 20 times the nominal current rating
without exceeding a 10% composite ratio error.
100 V = 20 * 5 * (1ohm)
200 V = 20 * 5 * (2 ohms)
400 V = 20 * 5 * (4 ohms)
800 V = 20 * 5 * (8 ohms)
62
GE Consumer & Industrial
Multilin
tandard IEEE CT Burdens (5 Amp)
(Per IEEE Std. C57.13-1993)
Application Burden Impedance VA @ Power
Designation (Ohms) 5 amps Factor
Relaying B1 1 25 0.5
B2 2 50 0.5
B4 4 100 0.5
B8 8 200 0.5
64
GE Consumer & Industrial
Multilin
Voltage Transformers
Voltage (potential) transformers are used to isolate
and step down and accurately reproduce the scaled
voltage for the protective device or relay
VT ratios are typically expressed as primary to
secondary; 14400:120, 7200:120
A 4160:120 VT has a VTR of 34.66
VP
VS
Relay
66
GE Consumer & Industrial
Multilin
Typical CT/VT Circuits
Secondary Circuit
69
GE Consumer & Industrial
Multilin
System Grounding
Limits overvoltages
Limits difference in electric potential through local
area conducting objects
Several methods
Ungrounded
Reactance Coil Grounded
High Z Grounded
Low Z Grounded
Solidly Grounded
70
GE Consumer & Industrial
Multilin
System Grounding
1. Ungrounded: There is no
intentional ground applied to
the system-however its
grounded through natural
capacitance. Found in 2.4-
15kV systems.
72
GE Consumer & Industrial
Multilin
System Grounding
73
GE Consumer & Industrial
Multilin
Basic Current Connections:
How System is Grounded
Determines How Ground Fault is Detected
Medium/High Low/No
Resistance Resistance 79
Ground Ground GE Consumer & Industrial
Multilin
Substation Types
Single Supply
Multiple Supply
81
GE Consumer & Industrial
Multilin
Industrial Substation Arrangements
(Typical)
82
GE Consumer & Industrial
Multilin
Utility Substation Arrangements
(Typical)
Single Bus, 1 Tx, Dual supply Single Bus, 2 Tx, Dual 2-sections Bus with HS Tie-Breaker,
Supply 2 Tx, Dual Supply
83
GE Consumer & Industrial
Multilin
Utility Substation Arrangements
(Typical)
Bus
1
Bus 2
Main bus
Aux. bus
Main
Reserve
Transfer
Bus 1
breaker
Tie
Bus 2
96
GE Consumer & Industrial
Multilin
Contribution to Faults
97
GE Consumer & Industrial
Multilin
Fault Types (Shunt)
98
GE Consumer & Industrial
Multilin
AC & DC Current Components
of Fault Current
102
GE Consumer & Industrial
Multilin
Useful Conversions
105
GE Consumer & Industrial
Multilin
Per Unit System
Establish two base quantities:
106
GE Consumer & Industrial
Multilin
Per Unit Basics
107
GE Consumer & Industrial
Multilin
Short Circuit Calculations
Per Unit System
Vpu = Vactual
Vbase
Ipu = Iactual
Ibase
Zpu = Zactual
Zbase 108
GE Consumer & Industrial
Multilin
Short Circuit Calculations
Per Unit System
MVAbase x 1000
I base =
3 x kV L-L base
kV2L-L base
Z base = MVA
base
109
GE Consumer & Industrial
Multilin
Short Circuit Calculations
Per Unit System Base Conversion
2
Zpu2 =Zpu1 x kV base1 x MVAbase2
kV 2base2 MVAbase1
110
GE Consumer & Industrial
Multilin
A Study of a Fault.
123
GE Consumer & Industrial
Multilin
Arc Flash Hazard
125
GE Consumer & Industrial
Multilin
Protective Relaying Methods
of Reducing Arc Flash Hazard
Bus differential protection (this FlexCurve for improved
reduces the arc flash energy by coordination opportunities
reducing the clearing time Employ 51VC/VR on feeders
Zone interlock schemes where fed from small generation to
bus relay selectively is allowed improve sensitivity and
to trip or block depending on coordination
location of faults as identified Employ UV light detectors with
from feeder relays current disturbance detectors
Temporary setting changes to for selective gear tripping
reduce clearing time during
maintenance
Sacrifices coordination
129
GE Consumer & Industrial
Multilin
Arc Flash Hazards
131
GE Consumer & Industrial
Multilin
Arc Pressure Wave
132
GE Consumer & Industrial
Multilin
Copy of this presentation are at:
www.L-3.com\private\IEEE
136
GE Consumer & Industrial
Multilin
Protection Fundamentals
QUESTIONS?
137