Security Level: Internal Open

Mobitel Stage4 Huawei BTS3900A


Installation Guide V1.0

2008.9

www.huawei.com
Liu Jiang 60307

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential


2G BTS3900A(outdoor)

APM30 for power


and BBU

Battery cabinet:
184Ah*2

RF cabinet for 6
DRFU

The layout of the BTS3900A is as shown in the picture.


The APM30 and RF cabinet should be near to the cable ladder.
Two battery cabinet should stack.

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 2


Outlook of BTS3900A

BTS3900A cabinet Stacked Battery


cabinet

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 3


The plinth

The BTS should be installed on the steel rack or concrete plinth


For the steel rack, use the bolt and nut to fix the base frame of
cabinet.
For the concrete plinth, use the expansion blot to fix the base frame.

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 4


Install the base

Fix the base to the plinth and check the levelness with level bar, if the
level bar is not in the middle, use the adjusting pad to adjust the
levelness
2 base need to be installed, one is for BTS3900A, one is for battery
cabinet
HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 5
Install the cabinet

Push the cabinet so that the cabinet can be in full contact with the
installation block
Use two bolts to fix the cabinet to the base

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 6


Install the component PSU

Special handle
PMU is needed to
remove the
DRFU
BBU

Install the BBU, DRFU, PMU and


PSU to the cabinet as shown in the
picture.
The BBU should be close to the PDU
panel, without space between PDU
and BBU DRFU

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 7


Connect the DC cable for BBU and DRFU

Load5
Connector to
UPEU on BBU
DC power cable for DRFU

Connect the DC cable to the Load5 of the PDU with OT


terminal. Blue cable as 48v, and black as 0 V. Connect the
power terminal to the UPEU card on BBU.
Connect the power cable to the corresponding DRFU, 6 cables
to 6 DRFU. The other end is already connected.

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 8


Install the CPRI cable for DRFU

GTMU

DRFU
CPRI
cable

Connect the CPRI cable between the GTMU and DRFU, the 6 ports
on GTMU should be connected to the corresponding DRFU. The port
on DRFU should be port0
The CPRI cable route should be at left side of the cabinet, as show in
the picture

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 9


Install E1 cable

UELP

There are two E1 cable, one is


GTMU between GTMU and UELP, the
other is from UELP to MW
The cable between GTMU and
UELP is already made.
GTMU UELP MW

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 10


RF cable

Upper 6
jumper to
be installed
Usually, the
lower 6 jumper
is not needed

S2 S2 PBT
S3
S4

Usually, one cabinet has 6 jumpers, please refer to the picture for the
jumper and RF cable connection.
One end of the jumper is straight DIN connector, the other end (BTS side) is
right angle DIN connector. The connectors need to be made on site.
The configuration of the cell is as showing in the picture:S2, S2 PBT, S3, S4

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 11


Stack two battery cabinet

Wiring
cover cover

Step 3

Step 1 Step 2
Step1:Install the lower cabinet and remove the cover
Step2:Install the wiring cover to the lower cabinet
Step3:Seal the wiring cover with mud.
Step4:Install the upper cabinet on top of the lower cabinet,
fasten the upper cabinet with 4 bolts.
Step 4

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 12


Install the battery
Install the DC
cable to APM30

Install the DC
Upper
cable between
battery
cabinet upper and lower
battery

Battery breaker
Lower K
battery
cabinet

Use the black DC cable as 48V, and red DC cable as 0V.


2 battery banks to be installed in each cabinet.
Attention! Switch off the battery breaker in battery cabinet and APM30 when installing
the battery! Battery terminal

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 13


Install the grounding cable

ECB inside the


cabinet
Install the PGND cable from APM30 to ECB
Install another 2 pcs of equipotential cable from APM30 to upper
battery cabinet and lower battery cabinet

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 14


Connect the AC input cable

PDU

short circuit bar

Install the 4 x 4mm^2 armored cable to the terminal of PDU, L1,L2,L3,N:


brown, black, grey, blue. When 3 phase power is used, the short circuit bar
should be removed; when single phase power is used, install the short
circuit bar.
AC power cable should be protected in the GI pipe , and the armor of the
cable should be grounded with the hose clip

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 15


Lay the AC power cable
Dig a channel between meter cubicle and plinth.
Lay the AC power cable with the protection of GI pipe. Flexible GI pipe should be
used as bend. The armor of the AC cable need to be grounded.
Ground the GI pipe with M8 x 25mm bolt & nut, using 25mm^2 grounding cable
Bury the pipe

Dig the channel and Make the bend with Ground the AC cable
lay the AC cable the Gi flex pipe armor with the hose
clip

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 16


Install the SPD for BTS

Install the SPD box on the meter cubicle, the SPD should
be grounded.

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 17


Alarm Cable
FMUA(COM)------BBU(MON0)

BBU(MON0)

FMUA(COM IN)

Connect the BBU(MON0) and FMUA(COM IN) with the


cable(04070023)

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 18


Alarm Cable
DPMU(COM)------APMI(J1)

One end of the cable is already connected to J1 port of


APMI, the other end need to be connected to COM port
of DPMU

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 19


Alarm Cable
DPMU(RS422)------APMI(RS422)

One end of the cable is already connected to RS422 port


of APMI, the other end need to be connected to RS422
port of DPMU

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 20


Alarm Cable
BBU(MON1)------APMI(TX- TX+,RX- RX+)

Wire Port on APMI


White One pair TX+
Orange TX-
Blue One pair RX+
White RX-

One end of the cable(04080029) is to MON1 port of BBU,


another end need to be cut and connect the wire to the
panel of APMI (TX- TX+,RX- RX+), The connection is as
shown in the table.

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 21


Install battery sensor cable

One end of the battery sensor cable is already connected to the


APMI card BAT_TEM1 port, so connect the other end to one cell of
the battery.

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 22


Connect the door sensor cable

Socket to connect
the 2 sensor

Connect the door sensors of the two battery cabinets and the
APM30 as red line shown in the picture
Connect the sensor cable to the socket of the prior door sensor,
so the connection of the 3 door sensors are serial
HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 23
Antenna system installation

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 24


Antenna system installation
Ground the feeder cable according to the standard in the picture
Antenna azimuth and down tilt should follow the design file strictly.
All the jumper connectors are waterproofed well.
The feeders are arranged neatly, the feeder and jumper labels are
attached neatly and oriented in the same direction.
Use feeder clamp to fix the feeder each meter.

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 25


Installation check key point

Check the grounding cable of cabinets, SPD, Gi pipe, AC power cable,


feeder.
Check the water proof of the feeder and antenna connector.
Check AC and DC power cable color code, complied with the standard.
The cable should be tied neatly. Keep redundancy when cutting the
cable tie.
Antenna height, azimuth and down tilt should follow the design file
strictly.
The signal cable and battery cable outside the cabinet should be
protected with PVC flexible pipe.
All the cables should be labeled with the label provided.
Bring back the rest of the materials and clean the sites after installation.

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 26


Power on the cabinet

AC input DC output
Breaker Breaker

Step1:Switch off all the AC and DC breaker


Step2:Power on the AC input breaker, check the indicator of the PMU and PSU,
For PMU, if RUN is 1s on and 1s off, and ALARM is off, it mean the module is
working normally
For PSU, if the is on, and is off, it means the module is working normally

Step3:Use the multimeter to measure the DC output voltage, the normal


range should be -38.4V to -57V.
Step4:Switch on the DC output breaker for the related module, switch on
the DC output breaker on the DCDU

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 27


Commission the BTS
LIU1

Connect the E1 cable to MW, check the indicator LIU1 on the GTMU, if
its always off, it means the E1 is normal.
After the BTS is on air, make some test call, check the cell broadcast
service and GPRS service.

The following alarm need to be checked on site:


Door alarm of all the 4 cabinets
Water sensor of the cabinet
Temperature and Humidity
Battery sensor
Mains failure and PSU failure

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 28