Preparation Before commencing maintenance, always ensure that The generator prime mover is shut down A Do Not Operate tally / board placed,. Generators supply breaker is off, Auto-start circuits are disabled Generator electric heaters are isolated.
ETHIOPIA MARITIME TRAINING INSTITUTE CHAPTER -
Maintenance General If an alternator is not in use, ensure windings are suitably heated in order to prevent internal condensation forming on its insulation. After maintenance, carry out No-load running checks Synchronizing and loading. On load, check for excess temperature rise load-sharing stability
ETHIOPIA MARITIME TRAINING INSTITUTE CHAPTER -
Maintenance Terminal Box & Cooling All terminal boxes and wiring to the generator should be inspected for damage or frayed insulation tightness of terminal connections. ingress of oil and water. Check that the cooling air-ducting, air intake and exhaust openings and are not blocked and are free of dirt and dust.
ETHIOPIA MARITIME TRAINING INSTITUTE CHAPTER -
Maintenance Rotors with Sliprings Check Rotor slip rings for even wear ,spring pressure by using a pull-type spring balance A pull of around 2-3 lbs. Or 1-1.5 kg is usual Minimum brush lengths (2cm) To bed the brushes 1. Placing a thin strip of glass paper over the slip ring with its cutting surface facing upwards and under the carbon brushes . 2. Pull the glass paper around the slip ring / commutator until the brush surface has the same contour as the slip ring / commutator 3. The last few passes of the glass paper should be made in the normal rotor direction. 4. Remove all traces of carbon dust with a vacuum cleaner. Check to ensure that the air gap between the rotor and stator is satisfactory . This will determine the state of the bearings. Record these values.
ETHIOPIA MARITIME TRAINING INSTITUTE CHAPTER -
Maintenance Stator & Rotor Windings Inspect and clean the generator rotor and stator windings by removing dust with a dry, lint-free cloth or Low-pressure dry compressed air or vacuum cleaner Check alternator windings for signs of oil or water contamination any damage. Minor abrasions to winding insulation Discoloring of insulation
ETHIOPIA MARITIME TRAINING INSTITUTE CHAPTER -
Maintenance Stator & Rotor Windings Compare these with the previous test result. A minimum insulation resistance value is usually taken to the 1M . Generators with very low insulation resistance values (<0.5M) should be given a thorough cleaning and then dried out. If insulation resistance comes up after dried out , windings should be covered with high-quality air- drying insulating varnish. If insulation resistance value remain low during a dry-out, the machine insulation needs to be completely re-impregnated or re-wound .
ETHIOPIA MARITIME TRAINING INSTITUTE CHAPTER -
Maintenance Exciter - AVR Check Generator excitation components viz. transformers, AVR components, rotating diodes, etc, must be kept free of dirt, oil and dampness and contacts for tightness Remember to disconnect / short out any electronic circuit components before insulation resistances testing.