Académique Documents
Professionnel Documents
Culture Documents
SIZING
In SI systems,
The valve coefficient is called Kv and it is defined as the
flow of cold water in cubic meter per hour, when the
pressure drop across the valve is one bar.
The conversion between Cv and Kv is
Kv = 1.17Cv
Importance of Sizing
When selecting a valve for a particular application, the
valve coefficient is used to determine the valve size that
will best allow the valve to pass the required flow rate,
while providing stable control.
Importance of Sizing
If valve is undersized
Processsystem can be starved for fluid.
High pressure drop across valve, leading to cavitation.
Inlet Pressure
Outlet Pressure
Vapour Pressure
Cavitation
Flashing
Bubbles
Pressure at vena contracta
Chocked Flow
Formation of Bubbles in the liquid stream caused due to
flashing or cavitation, causes a crowding condition at
vena contracta, tending to limit the flow.
If the valve pressure drop is increased slightly beyond
the point where bubbles begin to form, chocked flow
condition is reached. With constant upstream pressure,
further increase in pressure drop will not produce
increased flow.
Chocked Flow
Actual Flow
Flow
Actual P
Chocked P
P
Liquid Critical Pressure Recovery Factor
Fl=[(P1-P2)/(P1-Pvc)]
Liquid Critical Pressure Recovery Factor
Pvc =Ff Pv
Allowable Pressure Drop
The Allowable Pressure drop is chosen from the
smaller of actual pressure drop or the chocked
pressure drop and is used in determination of
correct Cv.
Pchocked= Fl2(P1-FfPv)
Piping Geometric Factor
The Flow capacity of the valve is affected by by the use
of increasers or reducers ,whuch must be corrected in
the Cv equation usinf Piping Geometry Factor Fp.
Due to change in cross-section by the use of fittings,
first there is an irreversible energy loss due to turbulence
(friction loss),
and second there is the conversion between pressure energy
and velocity energy. If the control
If the downstream piping is the same size as the inlet
piping, then the velocity-energy/pressure-energy
exchange at the outlet is reversed and it cancels the
effect at the inlet. Friction losses are always additives.
Piping Geometric Factor
ISA standard determines fitting friction loss coefficient:
For a reducer at the valve inlet,
K1=0.5(1-(d/D1)2)2
For a expander at the valve outlet,
K1=1-(d/D2)2)2
For velocity- pressue exchange
Reducer at inlet
KB1=1-(d/D1)4
Expander at outlet
KB1=(d/D2)4 -1
Fp=1+((K/1.6010-3)(Ci/d2)2)-1/2
Final Flow Coefficient Calculation
Final Flow Coefficient is calculated is done
according to equation.
Cv=(Q/Fp)(Sg/Pallowable)