AC Drive Training

LCP & MCT 10

Trainer: Stephen Tarrant


Drive Safety and Precautions
FREQUENCY CONVERTERS CAN CONTAIN DANGEROUS VOLTAGES.
NO DISSASSEMBLY SHOULD BE ATTEMPTED WITH POWER
APPLIED. REMOVE POWER TO THE FREQUENCY CONVERTER AND
WAIT AT LEAST 40 MINUTES TO ALLOW THE REQUENCY
CONVERTER CAPACITORS FULLY DISCHARGE.

ALWAYS CHECK VOLTAGE LEVELS WITH A TRUE RMS


MULTIMETER BEFORE ATTEMPTING MAINTENANCE.
CHECK ON BOTH AC AND DC VOLTAGE BETWEEN ALL
TERMINALS AND ALSO TO GROUND.
USE PROPER ELECTRO-STATIC DISCHARGE (ESD )
PROCEDURES TO PREVENT DAMAGE TO SENSITIVE
COMPONENTS.

IF A DRIVE MUST BE OPENED, PRESS AN EMERGENCY STOP


TO PREVENT DRIVES BEING RESTARTED
Information
• The Danfoss Manuals are an invaluable source
of information.
– FC300 Service Manual
• Information about hardware fault finding and repair
– FC300 Programming Guide
• Information about all parameters
– FC300 Operating Instructions
• Information about alarms, warnings and trouble-
shooting
LCP
• Functions
– Displays the drive / motor
status
– Allows the user to view
and change parameters
– Displays alarms and
warnings
– Can store parameters in
internal memory.
Local Control Panel (LCP)

Backlit LCD Display

LCP Operation
Mode Buttons
Menu Navigation
Buttons

Status Lights

Drive Operation
Mode Buttons
LCP - Status
• Possible to view
information on the
display
• Press to cycle between:
– Current
– Voltage
– Power
– Frequency
– Speed Press to cycle
– between
Torque
displayed
– Reference % values.
– Etc…
LCP – Main Menu

Press the Main Menu


button to view
parameters.

Use the up and


down arrow keys,
OK and Back
buttons to navigate
the menus
LCP – Main Menu
• Main Menu Menu Sub-Menu Parameters

– Parameters
arranged Language

according Basic Settings


Motor Speed Unit

Regional Settings

to function Operating State at Power


Up

Operation / Display
Setup Operations Active Setup

LCP Display ...

LCP Custom Readout ...

Main Menu
Configuration Mode
General Settings
Load and Motor
LCP – Main Menu
• Main Menu Menu Sub-Menu Parameters
X-** *-X* *-*X
– Parameters
are
numbered
according
to position. Main Menu 2-** Brakes 2-20 Release Brake Current

2-2* Mechanical Brake 2-22 Activate Brake Speed

2-23 Activate Brake Delay


LCP – Main Menu
Changing Parameters

Press the OK
button again
to save the
parameter
Press the OK change.
button to edit
a parameter
and use the
up and down
arrows to
cycle through
values.
LCP - Alarms
Press to open the
alarm menu. Press to open an
information page.

Press to view the


alarm details.
LCP Alarms
DC voltage high [A5]
Alarm name and number can be found in the
Operating Instructions Section 6.

Operating time given in


seconds of drive operation
LCP Alarms
Drive Faults

Fault Type Alarm / Trip


Warning Alarm / Trip Lock

Typical Fault
Current Limit (W30)
Live Zero Error (W2) Over Current (A13)

Warning displayed on Drive immediately Drive immediately


Effect
drive. Drive continues
to operate.
stops operation and
closes brakes.
stops operation and
closes brakes.

Completely power
Remedy
No remedy necessary. Press the reset button. down the DC Link and
restart the drive.
LCP Communication Parameters
Typical STS Drive Layout and Communication Addresses RS-485 End of
RS-485 RS-485
Line Resistor
Terminals Datalink

68 69 68 69 68 69 68 69 68 69

S801 S801 S801 S801 S801

ADDRESS ADDRESS ADDRESS ADDRESS ADDRESS


5 1 2 3 4

TROLLEY /
BOOM DRIVE
AFE SLAVE AFE MASTER AFE SLAVE HOIST DRIVE 1 HOIST DRIVE 1 HOIST DRIVE 2 HOIST DRIVE 2 TRAVEL DRIVE
LEFT RIGHT FC 1 FC2 FC 1 FC 2

Liebherr PLC

RS-232 to RS-485
Converter RS232
Datalink
Typical STS Drive Layout and Communication Addresses
during Loading of Firmware

68 69 68 69 68 69 68 69

68 69
Only leave the RS-485
connected on the drive
S801 S801 S801 S801
being programmed Disconnect allS801
other
drives from the RS485
Switch on the End of network.
ADDRESS ADDRESS Line Resistor on the ADDRESS ADDRESS ADDRESS
5 1 2 3 4
Control Card

Change to Comms
Settings on Drive
Remove any option
cards on the drive being
programmed. (MCB102
TROLLEY /
BOOM DRIVE
for Encoders, etc.)
AFE SLAVE AFE MASTER AFE SLAVE HOIST DRIVE 1 HOIST DRIVE 1 HOIST DRIVE 2 HOIST DRIVE 2 TRAVEL DRIVE
LEFT RIGHT FC 1 FC2 FC 1 FC 2

Connect the serial


cable from the RS232-
485 Converter to the
Crane PC Set Baud Rate to 9600
LCP Communication Parameters
• RS485 Communication
Parameters can only be set
through the LCP
• Set the Drive Address [831]
as per the drawing
• Set the Baud Rate [832] to
115,200
LCP Communication Parameters
Menu Sub-Menu Parameters
X-** *-X* *-*X

8-30 Protocol
Protocol for FC port
[FC]

8-31 Address
Address for the FC
8-** Comm. and port (1-126)
Main Menu Options
[See the S1 drawing to
8-3* FC Port Settings find the correct
address for each
drive.]

8.32 FC Port Baudrate


Baudrate for the FC
port.
[115,200 kbps for
normal operation]
LCP DIP Switches
• Switches S201 (A53) and
S202 (A54) are used to
select a current (0-20 mA)
or a voltage (-10 to +10V)
configuration of the
analog input terminals 53
and 54.
• Switch S801 (BUS TER.)
can be used to enable
termination on the RS-
485 port (terminals 68
and 69).
LCP – Other Features
• Digital inputs and
output can be
readout in the 16-6X
parameters.
• Details of the
parameters can be
found in the
Programming Guide.
Drive Signals
IGBT RELEASE
Allows IGBTs to switch DRIVE
PIN
on and removes Safe- 37
Stop from drive.

START SIGNALS START PIN


These signals HOISTING 18

determine the desired START PIN


direction. LOWERING 19

QUICK STOP TERMINAL 27

When this signal is set QUICK STOP

to 0, the hoist stops


quickly with full
braking torque.

PARAMETER SET TERMINAL 32

Used to change PARA. SET 2

between parameter
TERMINAL 33
sets. E.g. Trolley and
PARA. SET 3
Boom drives
BRAKE
BRAKE RELAY RELAY
The brake relay needs
24V supply from the
brake circuit.
LCP – Copy Parameters
• Good idea to
copy parameters
to LCP after
loading from
MCT10.
• Select parameter
0-50 from the
operation menu.
• Select All to LCP
and press OK.
RS232-485 Converter

• Dipswitches on the
RS232/RS485
converter should be
set as shown in the
S1 drawing.
VLT MCT 10
VLT® Motion Control Tool MCT 10

• MCT 10 Set-up software


One tool for all drives and power sizes
Explorer-like project view
On- and offline commission
Flexible fieldbus support
Option programming
Oscilloscope function
MCT10 - Opening a Parameter File
• Danfoss drive parameters stored in ‘.ssp’ files
• One file contains parameters of all drives
• Stored in D: drive crane folder in Fc
• Open this file… D:\Prj\IRXXXX_XX\Fc\
MCT 10 - Main Window

Menus and
Toolbar

Parameter
Pane

Folder Pane
MCT10 – Network and Project
• Network – Drives currently connected to the PC
– Grouped under two folders:
• Serial Interface
• USB Interface
– Possible to view all parameters on-line and make
individual changes
• Project – Drive parameters stored in the PC
MCT10 – Network and Project
Serial
Network
(RS485)

TROLLEY DRIVE

USB

TRAVEL 1 DRIVE TRAVEL 2 DRIVE

HOIST DRIVE

Parameters stored
on the PC’s
Hard Disk
MCT10 – Viewing Project Parameters
• Project parameters arranged for each drive.
– AFE
– Hoist 1
– Hoist 2
– Travel
– Trolley / Boom
• Each drive is possible of changing between 4
different sets of parameters called Setups.
MCT10 - Downloading from PC to a Drive
Write to Drive

RIGHT-CLICK

Which drive
parameters are
being written to.
MCT10 - Uploading from Drive to PC
Read from Drive

RIGHT-CLICK

Which drive
parameters are
being read from.
MCT10 - Comparing Parameters
• It is possible to
RIGHT-CLICK

compare
parameter sets
between any two
drives.
• Click on the first
drive that you
wish to compare
parameters on.
MCT10 - Comparing Parameters

SELECT DRIVE TO
COMPARE WITH
SELECT DRIVE SELECT DRIVE
SETUP SOURCE 1 SETUP SOURCE 2

CLICK COMPARE
MCT10 – Comparing Parameters

LIST OF PARAMETER
DIFFERENCES

CLICK SAVE TO SAVE


THE LIST OF
PARAMETER CLICK CANCEL TO
DIFFERENCES CLOSE
MCT10 – Scope Function
• Useful tool for fault
finding and diagnostics
• Right-click on project
and select New – Scope
Folder
• Click on the scope
folder and the add
channel window will
appear.
• Select a drive and
parameter to monitor.
MCT10 – Scope Function

Start Data Aquisition:


Left-click here to begin
data aquisition.

Channel Window:
Right-click here to
add a new scope
channel.