DUCT WORK INTRODUCTION
www.ACMV.org
VOLUME FLOW RATE
For Blower
200 CFM
Supply Flow Rate = Return Flow Rate
OA
1600 CFM
SA
Positive
MA Pressure
RA 1600 CFM
1400 CFM Area
WWW.ACMV.ORG
VOLUME FLOW RATE
200 CFM
@ Room
Supply Flow Rate > Return Flow Rate
OA
1600 CFM
SA
Positive
RA MA Pressure
1600 CFM
1400 CFM Area
WWW.ACMV.ORG
SYSTEM PRESSURES
Duct system is pressurized by three
pressures
Static pressure – air pressure in the duct
Velocity pressure – pressure generated by
the velocity and weight of the air
Total pressure
Static pressure plus velocity pressure
equals total pressure
STATIC PRESSURE
Probe located on
the surface of the Static pressure
duct
Airflow
Duct
TOTAL PRESSURE
Probe located in the
duct, facing into the
direction of airflow Total pressure
VELOCITY PRESSURES
Velocity pressure
Total pressure
Static pressure
𝟐
𝟏𝟎𝟎𝟎
𝑽𝒆𝒍𝒐𝒄𝒊𝒕𝒚 𝑷𝒓𝒆𝒔𝒔𝒖𝒓𝒆 𝑽𝑷 =
𝟒𝟎𝟎𝟓 0.006”
𝟐
𝟐𝟎𝟎𝟎
𝑽𝒆𝒍𝒐𝒄𝒊𝒕𝒚 𝑷𝒓𝒆𝒔𝒔𝒖𝒓𝒆 𝑽𝑷 =
𝟒𝟎𝟎𝟓
0.25”
𝟐
𝟑𝟎𝟎𝟎
𝑽𝒆𝒍𝒐𝒄𝒊𝒕𝒚 𝑷𝒓𝒆𝒔𝒔𝒖𝒓𝒆 𝑽𝑷 =
𝟒𝟎𝟎𝟓
2.24”
WWW.ACMV.ORG