Académique Documents
Professionnel Documents
Culture Documents
• Introduction of students.
• Introduction of subject.
• Introduction of instructors.
• Introduction of books and specifications.
Course Outline
Concrete Design Steel Design
• One canal masonary house • Design of Industrial Building
design
• Design of 2D frame • MID TERM
(manual+Etabs)
• Design of 3D Frame (Etabs)
• Design of Steel Bridge
• MID TERM
• Design of Retaining Walls
• Design of Water Retaining
Structures
Theory Part
Quiz - I
Quiz - II
Class Design Calculations
Home Design Calculations
Drawing Sheets
Intro to DOS
• What is DOS?
• Duties of a design engineer
• Industrial Building…Components of it
• Types of frames
• Rigid Frames…Types…advantages
• Depth of Girder
• Trussed Frames
• Bracing
• Review of Beam design
• Beam Column Design
Design Of beams…Review
• Assume self wt….
10% of dead load UDL…
5% of L.L…
3% of factored loads
• Calculate factored loads
• Draw SFD and BMD
• Calculate Cb for each unbraced segment…greater
value more strength
• Assuming compact section w/o LTB get Zs,reqd
Design Of beams…Review
• Select table using slection tables or unbraced
design charts(if Lb>Lm) with the following
criteria:
• Zsel >= Zreqd
• Min wt.
• dmin= Fy L/5500
• Cb>1.0, Lm+Lp
Design Of beams…Review
• Apply all stability checks
• Perform Strength Checks
• Perform serviceability Checks
• Accept section if all checks are staisfied,
otherwise revise section
• Write Final selection
FACTOR (Cb)
• 3. LTB
Capacity Checks
1. Flexure Capacity Check
• Mu bMn b=0.9
Calculate design flexural strength:
1. If Lb Lm Mn = Mp = Zx Fy / 106 (kN – m)
2. If Lm < Lb Lr Mn = Cb [Mp – BF(Lb – Lp)]
Mp (kN – m)
3. If Lb > Lr Mn = CbFcrSx Mp
2. Shear Capacity Check
Vu VVn
Calculate design Shear Strength
h
For 2.24 E / Fyw (= 63.4 for A36 steel) Cv = 1.0
tw
0.9 0.6
vVn Fyw AwCv , (kN )
1000
13
Deflection Check
Find act due to service live loads.
• Note: If Live Loads are not directly known, service
load may be taken equal to Factored load divided
by 2.5
• act L/360 for buildings (OK)
• act L/800 for bridges (OK)
• act L/2500 for sensitive structures (OK)
• (supporting machinery)
Self Weight Check
Value of Cb
Cb = 1.0 for cantilevers or overhangs with unbraced
free ends.
31
12.5 M max
Cb
2.5 M max 3M A 4 M B 3MC
35
Design Curve
For Cb >1.0
Nominal Flexural Strength (Mn)
CbMp
Curve-2 Obtained By Multiplying
Curve-1 With Cb >1.0
Mp
Curve-1
For Cb =1.0
CbMr
Mr
Lp Lm Lr
Lp
CM b p Mp
Cb BF
M p Cb 1
Lp Lr
BF Cb
BF = slope of moment capacity versus unbraced length
for inelastic lateral torsional buckling.
M p Mr
BF
Lr L p
When Cb = 1.0, Lm = Lp 37
Design moment capacity (Mn) is determined for various
cases of unbraced lengths as follows:
Case I: Compact Sections, Cb 1.0, Lb Lm
Mn = Mp = Zx Fy / 106 (kN – m)
Case II: Compact Sections, Cb 1.0, Lm < Lb Lr
Lb L p
M n Cb M p ( M p M r ) M p , (kN m)
L L
r p
For h
2.24 E / Fyw
tw
(= 63.4 for A36 steel) : Cv = 1.0
41
Note:
Vu
1) Average applied shear stress, fv = (LRFD)
dt w
2) Beam is safe in shear when Vu Vn (LRFD)
DEFLECTIONS
Deflection check is a serviceability limit state check and
hence, it is applied using the service loads and not the
factored loads.
Further, for steel structures, this check is usually applied
only using the service live load and the deflection due to
dead loads are not considered.
42
The reason for not including the dead load in the
calculation of deflections is that the structure is given a
negative camber during construction to balance the dead
load deflections.
There are several justifications for limiting service live load
deflections, some of which are as under:
midspan
Pa 3 2
12 EI 4
L a2
4- For overhanging part of beam subjected to UDL
w a3
max 4L 3a
24 EI
P a 2 L a
max
3EI
Selection of Section
i. Zsel Zreq
ii. Minimum weight
iii. d dmin
Fy L
d min For max = L/360
5500
dmin = L /22 for A36 steel and simply supported beams
For max required to be lesser than L /360, like L /500 or
L /800, find (Ix)req from the deflection formula, with only
the live load acting, and select section such that Ix (Ix)req52.
Method 1: Use Of Selection Tables Refernce-1, Page 155
These tables are applicable only if Lb < Lr and Cb = 1
1. Enter the column headed Zx and find a value equal to
or just greater than the plastic section modulus
required.
2. The beam corresponding to this value in the shape
column and all beams above it have sufficient flexural
strength based on these parameters.
3. The first beam appearing in boldface type (top of a
group) adjacent to or above the required Zx is the
lightest suitable section. 53
4. If the beam must have to satisfy a certain depth or
minimum moment of inertia criterion, proceed up
the column headed “Shape” until a beam fulfilling
the requirements is reached.
5. If Cb > 1.0, use Lm in place of Lp for the approximate
selection.
6. If Lb is larger than Lm of the selected section, use the
unbraced design charts.
7. Apply moment capacity, shear capacity, deflection
and all other checks.
8. The column headed bMp may also be used in place
of the Zx column in the above method.
54
55
Method 2: Use Of Unbraced Design Charts
This method is applicable in cases where the above
method is not fully applicable and Lb Lp.
The design charts are basically developed for uniform
moment case with Cb = 1.0.
Following notation is used to separate full plastic, inelastic
LTB, and elastic LTB ranges:
Solid Circle represents Lp
Hollow Circle represents Lr
58
Check the three conditions of compact section for
internal stability, namely,
1. web continuously connected with flange,
2. flange stability criterion, and
3. web stability criterion.
If any one out of the above three is not satisfied, revise
the section.
Sx 2S x
Check self-weight:
Calculated self weight 1.2 assumed self weight (OK)
Otherwise, revise the loads and repeat the calculations.