Vous êtes sur la page 1sur 64

Substation Automation Products, February 2016

Integrated Engineering Tool 5.3


Introduction

© ABB Group
February 7, 2018 | Slide 1
1MRG014136
Contents

 Introduction
 Navigation Concept & Editors
 Sample Engineering Workflows
 Edition 2 – SCL Implementation Conformance Statement
 Comparision IET600 vs. PCM600 IEC 61850 System engineering
 FAQ
ABB’s SA tool landscape
Tool suite for engineering, integration and testing

System engineering
IET600

Substation Automation System

Stations Bus

.scd

Process Bus

Process
Interface

System testing IED configuration


ITT600 SA Explorer PCM600

© ABB Group
February 7, 2018 | Slide 3
IET600 Integrated Engineering Tool

 A comprehensive engineering tool to design and


configure the complete IEC 61850-based
substation automation system
 Graphical editor for specification of
substation topology
 Graphical editor for specification of physical
communication network topology
 Import, utilization and creation of SCL
conform files
 Configuration of communication
subnetworks
 Flexible configuration of datasets, Report
Control Blocks (RCB) and Goose Control
Blocks (GCB)
 Define dataflow and RCB/GCB clients
 Generate a complete description of the
substation (SCD file)
 Generation of XLS Signallists documenting
the complete IEC 61850 dataflow
© ABB Group
February 7, 2018 | Slide 4
IET600
Editors for Design & Engineering of IEC 61850 SAS

Design Substation Topology Configure IEC 61850 dataflow Communication Addresses

IET600
Overview of IEDs Network Configuration

© ABB Group Compare & Merge SCL files Document SA System


February 7, 2018 | Slide 5
IET600 – Editors Communication network editor

HMI/GW Signal IED Section Communication


Editor HMI/GW Section
AP/Server
LD
LN
LN

Report
LN

S/S Section IED1


AP/Server

Communication Subnetwork
LD
LN

Bay1 LN
DS CB
LN
DS CB

IED2
AP/Server
VL1 LD
LN
Bay2 LN
DS CB
LN
DS CB

Goose
Bay1 Bay2 Bay3 IED3
AP/Server
LD

Bay3 LN
LN
DS CB
LN
DS CB

SLD editors for bay &


voltage level Editor for mapping of Muliple Editors for
functions to primary horizontal & vertical
© ABB Group equipment dataflow configurations
February 7, 2018 | Slide 6
Integrated Engineering Tool IET600
Overview of Engineering Editors

 Design Substation Topology


 Easily define the substation topology, including
substation, voltage level, bays and primary
equipment
 Graphical single line representation of the
substation
 Map primary equipment to IEDs according to
IEC 61850

 Configure Communication Networks


 Graphical representation of the physical
communication network
 Clear overview, easy filtering and editing of
communication parameters and settings
 Easily assign IEDs to subnetworks
© ABB Group
February 7, 2018 | Slide 7
Integrated Engineering Tool IET600
Overview of Engineering Editors

 Configure station wide IEC 61850 dataflow


 Comprehensive editors to configure datasets and
control blocks for MMS reports, GOOSE and
Sampled values
 Powerful matrix tables to easily manage the
system wide IEC 61850 dataflow

 Document IEC 61850-based substation


 Export documentation of system wide IEC 61850
dataflow in Excel Format
 Export a complete SCD file including substation
section with primary equipment

© ABB Group
February 7, 2018 | Slide 8
Integrated Engineering Tool IET600
Overview of Engineering Editors

 Compare and Merge SCL files


 Compare and merge dialogs provide support for
reimport of SCL data
 Preview content in import file
 Compare content to data in project
 Merge data or cancel import

© ABB Group
February 7, 2018 | Slide 9
Integrated Engineering Tool IET600
Feature Overview
IET600 IET600
Functions
v.5.2 v.5.3
IED related SCL file handling
• ICD - import / export ●/● ●/●
• IID* - import / export ●/● ●/●
• CID - import / export ●/- ●/-
System related SCL file handling
• SSD - import / export (optional feature acc. IEC 61850) - /- - /-
• SCD - import / export ●/● ●/●
• SED* - import / export -/- ●/●
IEC 61850 Data flow engineering
• Dataset - manual creation / import ●/● ●/●
• control blocks - MMS / GOOSE / Sampled Values ●/●/● ●/●/●
• Substation to substation communication - ●
Define Substation section
• Primary equipment (S/S,VL, Bay, EQ) ● ●
• Functions & Sub-functions - ●
Grafical Editors
• Substation Single line diagram ● ●
• Physical communication network - ●

Logical Node mapping to primary objects in substation section ● ●

XLS Export IEC 61850 Dataflow Signallist ● ●

Supported IEC 61850 SCL versions


• 2003 Rev.A ● ●
• 2007 Rev.B - ●
© ABB Group
February 7, 2018 | Slide 10
Integrated Engineering Tool IET600
Summary

 Latest generation of ABB IEC 61850 system


integration tool reflecting all experience and
knowhow gathered during standardization and
project execution.
 Robust tool implementation, hardened in hundreds of
IEC 61850 based SA Systems engineered by ABB
and partners.
 Proven system integration capabilities of various
conformance tested 3rd party IEDs.
 Future proof implementation incl. preparation for
upcoming standards.
 Built on state of the art software technology with
support for Windows 7/8 native 64Bit and multi-core
CPUs.
 Key system integration tool used in the UCA certified
conformance test center – «ABB System Verification
& Validation Center».

© ABB Group
February 7, 2018 | Slide 11
Contents

 Introduction
 Navigation Concept & Editors
 Sample Engineering Workflows
 Edition 2 – SCL Implementation Conformance Statement
 Comparision IET600 vs. PCM600 IEC 61850 System engineering
 FAQ
IET600 - Overview
Modern and Intuitive Engineering Environment

Menu for quick access to grouped functionality per editor

Navigation pane
for context
oriented
Editors for detailed design and engineering
navitagation &
filtering

Detailed properties
Logging and messages

© ABB Group
February 7, 2018 | Slide 13
IET600 – built for IEC 61850 SA
Navigation Concept follows IEC 61850 SCD file structure
IET600
navigation
IEC 61850-6 SCL file object model trees

IEC 61850
SCD file

 IEC 61850 Context oriented navigation


 General goal to minimize amount of clicks to navigate and filter on engineering data

© ABB Group
February 7, 2018 | Slide 14
IET600 applies IEC 81346 in Substation Automation
Naming structuring principle & reference designation
 IEC 81346 defines
 Functions: Task performed by
object
 Product: Where functions are
assigned
 Location: Position of the object
within circuit
 Structure designations of equipment
in electrical circuit diagrams
 Reference designation to
unambiguously identify an object
 By default IET600 uses these
designations when creating a new
system (manually editable)

© ABB Group
February 7, 2018 | Slide 15
IET600 – Basic Tool Concept
Context-oriented Navigation
1.
4. 1. Select the context

2. Select the node of interests

3. Select the task


2.
4. Perform the task
4.

1. 3.

© ABB Group
February 7, 2018 | Slide 16
IET600 – Basic Tool Concept
Node Types in Tree Structure

Nodes can appear in multiple trees


The selected node type defines the available editor
Editor tabs are always shown - Grey colouring indicate that editor is not
available for selected node!

Each node can appear in multiple trees

© ABB Group
February 7, 2018 | Slide 17
IET600 – Basic Tool Concept
Navigation Filter on Active Editor

All IEDs in the Station

All IEDs in a Voltage Level

All IEDs in a Bay

Navigation in the tree structure is


setting a view filter on engineering
data in the active editor
© ABB Group
February 7, 2018 | Slide 18
IET600
Editors for Design & Engineering of IEC 61850 SAS

Design Substation Topology Configure IEC 61850 dataflow Communication Addresses

IET600
Overview of IEDs Network Configuration

© ABB Group Compare & Merge SCL files Document SA System


February 7, 2018 | Slide 19
IET600 – Editors Communication network editor

HMI/GW Signal IED Section Communication


Editor HMI/GW Section
AP/Server
LD
LN
LN

Report
LN

S/S Section IED1


AP/Server

Communication Subnetwork
LD
LN

Bay1 LN
DS CB
LN
DS CB

IED2
AP/Server
VL1 LD
LN
Bay2 LN
DS CB
LN
DS CB

Goose
Bay1 Bay2 Bay3 IED3
AP/Server
LD

Bay3 LN
LN
DS CB
LN
DS CB

SLD editors for bay &


voltage level Editor for mapping of Muliple Editors for
functions to primary horizontal & vertical
© ABB Group equipment dataflow configurations
February 7, 2018 | Slide 20
IET600
Graphical Editor to Define Substation Topology

 Easily define the substation


topology, including substation,
voltage level, bays and primary
equipment
 Graphical single line
representation of the
substation
 Map primary equipment to
IEDs according to IEC 61850

© ABB Group
February 7, 2018 | Slide 21
IET600 – Overview
Engineering Tasks

Client-Server
communications are
point to point
Realtime communications
are broadcast
Network traffic
performance can be
IEC 61850
optimized by using
“managed ethernet
switches”

© ABB Group
February 7, 2018 | Slide 22
IET600
Configure Communication Networks
 Clear overview of communication
parameters and settings
 Easily assign IEDs to subnetworks
 Versatile filtering functions to quickly
navigate through parameters

© ABB Group
February 7, 2018 | Slide 23
IET600 - Overview
Graphical Editor to Define Communication Network Configuration

 Easily define the complete


substation-wide communication
network configuration
 Use substation tree structure to
navigate/highlight the
equipment that belongs to a
bay
 Printout diagram for system
documentation

© ABB Group
February 7, 2018 | Slide 24
IET600
Configure IEC 61850 Dataflow

 Powerful editor to easily define IEC


61850 dataflow between IEDs incl. the
HMI

 Import from SCD/CID files or create


manually :
 Datasets

 Configure communication services


 Report Control Blocks (RCB)
 Goose Control Blocks (GCB)
 Sampled Value Control Block

© ABB Group
February 7, 2018 | Slide 25
IET600 – Communication Engineering
Communication Subnetwork Editor

Define Subnetwork properties:


• IP Address
• Subnetwork name IP Address
• Application type
• Configuration version

© ABB Group
February 7, 2018 | Slide 26
IET600 – Communication Engineering
Dataset Editor
 Datasets can either be either imported with an IED or created manually

All datasets below the selected node Content of


Selected
dataset

IEC61850 Model to select dataset entries

© ABB Group
February 7, 2018 | Slide 27
IET600 – Communication Engineering
Create new datasets

© ABB Group
February 7, 2018 | Slide 28
IET600 – Communication Engineering
RCB Editor
 RCBs can either be either imported with an IED or created manually
 Show dataset entries for each RCB

View/configure RCB properties:


• IED/LD/LN for RCB
• Status
• Name of attached dataset
• Conf. Rev.
• Buffered
• Buffer Time
• Number of Enabled Clients
• ...

© ABB Group
February 7, 2018 | Slide 29
IET600 – Communication Engineering
RCB Clients

Sender Receivers

© ABB Group
February 7, 2018 | Slide 30
IET600 – Communication Engineering
GCB Editor
 GCBs can either be either imported with an IED or created manually
 Show dataset entries for each RCB

View/configure GCB properties:


• IED/LD/LN for GCB
• Status
• Name of attached dataset
• Conf. Rev.
• t(max)
• MAC Address
• APP ID
• ...

© ABB Group
February 7, 2018 | Slide 31
IET600 – Communication Engineering
GCB Clients

Sender Receivers

© ABB Group
February 7, 2018 | Slide 32
IET600 Communication Engineering
Support for IEC 61850 -9-2 Sampled Values
 New support for process bus applications
 Engineering workflow same as for GOOSE
 Dataset editor is in common
 New editors for SVCB and publisher/subscriber mapping

Receivers
Sender
© ABB Group
February 7, 2018 | Slide 33
IET600 Send to:
Signal Client Engineering • Client HMIs
• Client GW/Proxy

Configure:
• Select (“Sel”)
• Grouping (“Grp”)
• Group Index (“GrpI”)

Mapping
table for
Signals of Selected Node
HMI and GW
clients

© ABB Group
February 7, 2018 | Slide 34
IET600 Configure:
NCC Data Configuration • Address
• Signal Handling
• Command Type
• Transmission Class
• Scale Name
• Send Triggers

Configure NCC
Signals of Selected Node
signal properties

© ABB Group
February 7, 2018 | Slide 35
IET600 – Communication Engineering
Input Section Viewer & Editor

For selected 3rd party IEDs


it might be required to edit
the IEC 61850 input section
 Right mouse click on filter
column of resp. Row and
select «Change Parent LN»

View all Dataset content


received by selected IED

© ABB Group
February 7, 2018 | Slide 36
IET600
Compare & Merge SCL Files

IED in imported File IED in IET project


 Compare and merge dialogs provide
support for reimport of SCL data
 Preview content in import file
 Compare content to data in
project
 Merge data or cancel import
© ABB Group
February 7, 2018 | Slide 37
IET600 – IED Engineering
Logical Node Mapping Table
 LN Mapping table to map IEC 61850 LN to primary equipment in Substation section

SLD for selected


LN Mapping table
node

© ABB Group
February 7, 2018 | Slide 38
IET600 – IED Engineering
Logical Node Mapping Table
Fill Down can be
used to map all
LNs to the Bay. Selection of
additional IEDs
which will provide
LNs.

© ABB Group
February 7, 2018 | Slide 39
IET600
Manage IED Information
 Easily import ICD files from IED
Engineering Tools to IED functionality
according to IEC 61850
 Clear overview of IED Status
 List of all IEDs in a projects
 Names, IED Types, Manufacturer
 Software & Configuration Revisions
 Change dates
 Windows Users name
 PCM Template Name
 Modified flag to indicate changes
since the last SCD export

© ABB Group
February 7, 2018 | Slide 40
IET600 – IED Engineering
Define IED Capabilities
 Open IED Capabilities editor from the IET Main menu > Options > Appearance
 Change default IED settings per IED type to cope with potential integration issues

© ABB Group
February 7, 2018 | Slide 41
IET600 – Import/Export
Export SCD File
 Export SCD file from Home menu or context menu (project node)

© ABB Group
February 7, 2018 | Slide 42
IET600 – Import/Export
Export IEC 61850 Signal List
 Signal list for documentation of IEC 61850 communication in the substation

© ABB Group
February 7, 2018 | Slide 43
Contents

 Introduction
 Navigation Concept & Editors
 Sample Engineering Workflows
 Edition 2 – SCL Implementation Conformance Statement
 Comparision IET600 vs. PCM600 IEC 61850 System engineering
 FAQ
IET600 – Tool coherences IEC 61850
Sample Workflow in IET600 not using Substation Section
1. Import .ICD files for IED/GW/HMI
2. Create Subnetwork and assign IEDs to it IED Section Communication
3. Define addresses Section
4. Configure dataflow HMI/GW
5. Export .SCD AP/Server
LD
LN
LN

Report
LN

Communication Subnetwork
S/S Section IED1
AP/Server
LD
LN
LN
DS CB
LN
DS CB

IED2
AP/Server
LD
LN
LN
DS CB
LN
DS CB

Goose
IED3
AP/Server
LD
LN
LN
DS CB
LN
DS CB

© ABB Group
February 7, 2018 | Slide 45
Integrated Engineering Tool IET600
Sample IEC 61850 engineering workflow
IET600 IED Section Communication
HMI/GW Section
1. Create Substation section AP/Server
LD
(Bay, Voltage level)
LN
2. Import .ICD files for LN

IED/GW/HMI

Report
LN

3. Map logical nodes to

Communication Subnetwork
S/S Section IED1
primary equipment AP/Server
LD
4. Create Subnetwork and LN
assign IEDs to it Bay1 LN
DS CB
5. Define addresses LN
DS CB
6. Configure dataflow
7. Export .SCD VL1 IED2
AP/Server
LD

mapping LN
Bay2 LN
DS CB
LN
DS CB

Goose
Bay1 Bay2 Bay3
IED3
AP/Server
LD

Bay3 LN
LN
DS CB
LN
DS CB

© ABB Group
February 7, 2018 | Slide 46
Integrated Engineering Tool IET600
Engineering the substation section in SCD files

 SCD with «Substation Section»  SCD without «Substation Section»


 Slightly more engineering effort  Minimum engineering effort
 Integral system documentation incl. information  Communication addressing and dataflow
on primary equipment and functional allocation information only
 High reuse factor for station level IEDs and in  Low reuse factor throughout the engineering
testing tools during testing/commissioning and testing process beyond «get it running»

The engineering & usage of the substation section is declared as


© ABB Group
February 7, 2018 | Slide 47
optional by IEC 61850-6 but nevertheless highly recommended
Contents

 Introduction
 Navigation Concept & Editors
 Sample Engineering Workflows
 Edition 2 – SCL Implementation Conformance Statement
 Comparision IET600 vs. PCM600 IEC 61850 System engineering
 FAQ
IEC 61850 Edition 2
SCL implementation conformance statement (SICS)

PICS Protocol Implementation Conformance Statement:  What is a SICS – SCL Implementation


Which Communication services are supported ...
PIXIT Protocol Implementation Conformance
Conformance Statement in Ed.2 ?
Extra Information for Testing:  Part of IEC 61850-6 (Annex)
Restrictions and Limitations found in a device ...
MICS Model Implementation Conformance Statement:  Official conformance statement for
Models supported ... engineering tools (equivalent to PICS for
TICS Tissue Implementation Conformance Statement:
Which tissues have been
the IEDs)
implemented: www.tissue.iec61850.com  Defines mandatory/optional features for
SICS SCL Implementation Conformance Statement:
tools to improve interoperability among
Which aspects of SCL have been implemented in a
Tool vendor IED and system tools

Improved interoperability
 Allows judging the degree of
interoperability between different
engineering tools, system tools as
well as IED tools.

© ABB Group
February 7, 2018 | Slide 49
IEC 61850 Edition 2
System Configuration Tool Certificate

 IET600 is the world wide first IEC 61850


Ed.2 certified System Configuration Tool
 Tested by DNV-GL
 Certified 2016-02
 IET600 5.3 SICS available on ABB
Library

© ABB Group
February 7, 2018 | Slide 50
IEC 61850 Edition 2
SCL implementation conformance statement (SICS)

 IED configurator conformance statements


 .icd export
 .scd import
 .iid export
 Tool functionality

 System configurator conformance


statements
IEC 61850-6  .icd and .iid import and usage
 Communication engineering
 Data flow engineering
 .scd substation section handling
 .scd modification, export, import
 .sed handling

© ABB Group
February 7, 2018 | Slide 51
IEC 61850 Edition 2 – New features
SCL Extension

System configuration tool


System  New SCL extensions
configuration tool
 IID: Instantiated IED Description –
Describes the instantiated data
model of an IED
 SED: System Exchange Description
– Describes interface data exchange
between different projects
IED configuration tool

IEC 61850-6 (Ed.2)

© ABB Group
February 7, 2018 | Slide 52
Contents

 Introduction
 Navigation Concept & Editors
 Sample Engineering Workflows
 Edition 2 – SCL Implementation Conformance Statement
 Comparision IET600 vs. PCM600 IEC 61850 System engineering
 FAQ
ABB tools
Comparision IET600 vs. PCM600 (1/2)
 ABB offers two tools with IEC 61850 system engineering capabilities
 PCM600 – free IED engineering tool with optimized dataflow engineering for ABB products
 IET600 – vendor neutral, full-blown system engineering tool acc. Ed.2 definition (SICS)

HMI HMI
Gateway

MMS MMS MMS

WAN
GOOSE GOOSE

Sampled Values & GOOSE


PCM600 for IEC 61850 engineering

IET600 for IEC 61850 engineering MU MU

Legend: ABB products


3rd party IEDs
© ABB Group
February 7, 2018 | Slide 54
ABB tools
Comparision* IET600 vs. PCM600 (2/2)
Functions PCM600 v.2.5 IET600 v.5.3
IED related SCL file handling
• ICD - import / export -/● ●/●
• IID* - import / export Client only / ● ●/●
• CID - import / export -/● ●/-
System related SCL file handling
• SSD - import / export -/- ● /-
• SCD - import / export ●/● ●/●
• SED* - import / export -/- ●/●
IEC 61850 Data flow engineering
• Dataset - manual creation / import ●/● ●/●
• control blocks - MMS / GOOSE / Sampled Values ● / ● / IED specific ●/●/●
• Substation to substation communication - ●

Define Substation section


• Primary equipment (S/S,VL, Bay, EQ) - ●
• Functions & Sub-functions - ●

Grafical Editors
• Substation Single line diagram - ●
• Physical communication network - ●
Logical Node mapping to primary objects in substation
- ●
section

XLS Export IEC 61850 Dataflow Signallist - ●

Supported IEC 61850 SCL versions


• 2003 Rev.A ● ●
• 2007 Rev.B - ●
stand-alone
Sales Free of charge
product for sale

© ABB Group
February 7, 2018 | Slide 55
* Comparision of IEC 61850 relevant features only
Contents

 Introduction
 Navigation Concept & Editors
 Sample Engineering Workflows
 Edition 2 – SCL Implementation Conformance Statement
 Comparision IET600 vs. PCM600 IEC 61850 System engineering
 FAQ
IET600
FAQ - Software Update
 How do I get bugfix versions ?
 IET600 has a on-demand “check for updates” function
 Direct «download/save as» of the new setup is now possible
 Anonymus - no registration in ABB software library needed anymore !
 Only upgrades that work for the actually running available license will be offered
 Typically changes on the 3rd digit (e.g. 5.2.15 against 5.2.16) are available

© ABB Group
February 7, 2018 | Slide 57
IET600
FAQ - Versions in parallel
 Can different versions of IET600 be installed in parallel ?
 IET600 has no restriction in terms of having several 5.x versions installed in parallel
 The IET600 «Manage Projects» shows with which tool version a project stored on the PC has been
engineered with
 If a project was created with an older version  it must be migrated before opening
 If a project was made with a newer version  it can’t be opened

© ABB Group
February 7, 2018 | Slide 58
IET600
FAQ - Support for Virtual Machines
 Can IET600 run in a virtual machine ?
 Yes, just make sure that the IET600 can access the USB Port of the host PC

Host PC

Virtual Machine
IET600 tool IET600 tool
installation package
IET600 tool (incl. IET600
pre-requisits (SQL, Feature OK!
Microsoft dotNET upgarde) licenced ?

USB Key locked


 IET600 in VM must be
able to access USB port

© ABB Group
February 7, 2018 | Slide 59
IET600
FAQ - Order variants & versioning concept
Variants Order Code

IET600 5.3 Single licence IET600-5x

IET600 5.3 Multi licence (10x) IET600-5x-M10

Upgrade IET600 5.3 Single Licence IET600-5x-UG


From PCM600 Engineering Pro (including IET600 5.1) or IET600 5.2

Upgrade IET600 5.3 Multi Licence (10x) IET600-5x-UG10


From PCM600 Engineering Pro (including IET600 5.1) or IET600 5.2

 IET600 Versioning Concept


 Version A.B.x.y
 A.B = Major version
 x.y = Service pack / bug fix

 New licenses are typically required for new major versions (A.B)
 No new licenses required for service packs/bug fixes (x.y)
 Customers can download service packs/bug fixes from ABB SA Software Library
with the embedded «check for update» function

© ABB Group
February 7, 2018 | Slide 60
IET600 5.3
Package

 The software is packaged in a case with CD and USB licence key


 Licensing with USB licence key allows
 Flexible usage on different PCs (one at a time)
 Supports virtual PC environments
 No online registration or activation of license required

 CD content :
1. IET600 Prerequisites 5.1.2
 SQL Server 2008 SP3 (SP3 on WinXP required)
 Windows Installer 4.5
 .NET Framework 3.5 & 4.0
2. ABB IET600 Setup - 5.3.x
3. IET600 Installation Guide
4. IET600 User Manual
5. IET600 release notes

© ABB Group
February 7, 2018 | Slide 61
IET600 5.3
Package
 Supported operating systems :
 Windows 7 / 8
 Windows 2008 Server / 2003 Server (SP2)
 Windows Vista SP1
 Windows XP SP3

 The minimum hardware requirements are:


 300 MB of free hard disk space
 Dual-core processor
 3 GB RAM
 2.5 GB page file size

 The recommended hardware requirements for medium to big


projects are:
 300 MB of free hard disk space
 64bit operating system (IET600 runs as native 64Bit application)
 Quad-core processor
 8 GB RAM
 SSD recommended for system drive

© ABB Group
February 7, 2018 | Slide 62
© ABB Group
February 7, 2018 | Slide 63
Aspects of IEC 61850 System Integration
Engineering & Documenting a IEC 61850 System
Logical Structure of an SCL file (e.g. .SCD)
Functional Oriented
Identification
(From Logical Node Reference
Mapping to S/S Section)

Communication Oriented
Identification (by subnetworks)

Product Oriented
Identification
(From ICD file)
© ABB Group
February 7, 2018 | Slide 64