Controller
MODEL SC1UDC+
Data to controller
Getronics
ENT on the main
screen pressing
4 BATT TEST VOLT Rectifier voltage gets reduced to this value during battery test. 45.5
test alarm threshold voltage. If the battery voltage descends to this level
5 BATT TEST ALARM during a battery test, the battery fails the test and a “battery test fail” 46.0
alarm is generated.
19 TEST TOP TIME Maximum permitted duration of battery test (minutes). 30min
21 EQUL TOP TIME Max. permitted duration of equalizing charge mode (hours). 1hours
ENABLE
25 Automatic battery test: enable/disable. YES
AUTO TEST
OVER
34 Trigger level for overload alarm (amperes). 250A
LOAD ALM
EN RMT
35 Enable / disable remote command feature. yes
COMND
LVD2
36 Trigger voltage level for LVD2. 44VOLT
VOLTAGE
Checking alerts
Main Menu> 3-Alarms
Determining number of suppliers
Main Menu> 5-Advanced> 2-Config
Press the ENTER button
Use the arrows to determine the number of suppliers on the
site.
15 -UNUSED-
16 X AC input surge has blown
17 X test time-stamp
18 X Equalizer test time-stamp
20 X Overload
21 -UNUSED-
22 -UNUSED-
23 -UNUSED-
24 -UNUSED-
25 -UNUSED-
26 X CNVCOM
27 X HI- 24V
28 X LO-24V
29 -UNUSED-
30 -UNUSED-
31 X Controller time-stamp
32 -UNUSED-
IP Setting
ENT on the main screen pressing
5-Advanced> Scrolls using the arrows to the screen
Press the ENT button
Enter the password using the right arrow button.
The password is: ******** (eight times *)
Press the ENT button
8-Comms to browse using arrows to screen
Press the ENT button twice
SET IP
010.10Z.SSS.150 Using the arrows to browse to the
address
Press the ENT button
MASK
255.255.255.000 Using the arrows to browse to the
address
Press the ENT button
GTWY
010.10Z.SSS.254 Using the arrows to browse to the
address
When finished, press the ENTER button
. 3 times ESC has to click