Gematronics

Controller
MODEL SC1UDC+
Data to controller
Getronics
ENT on the main
screen pressing

Main Menu> 5-Advanced Browsing with the arrows on


the screen
Enter the password using the right arrow button.
The password is: ******** (eight times *)
Main Menu> 5-Advanced> 1-Setup to scroll through the
arrows to the screen
Press the ENTER button
The data must be filled in according to the table.
A specified
# LCD Display Description
value
1 RESERVED - RESERVED -

2 FLOATING VOLT Output floating charge setup. 54.4

3 EQUAL VOLT Output equalizing charge setup. 57.0

4 BATT TEST VOLT Rectifier voltage gets reduced to this value during battery test. 45.5

test alarm threshold voltage. If the battery voltage descends to this level
5 BATT TEST ALARM during a battery test, the battery fails the test and a “battery test fail” 46.0
alarm is generated.

Alarm is generated when battery voltage descends to this level in


6 EQ LO ALARM-V
equalizing charging mode. 49.0

Alarm is generated when battery voltage rises to this level in equalizing


7 EQ HI ALARM-V
charging mode. 58.0

Alarm is generated when battery voltage descends to this level in floating


8 FL LO ALARM-V
charging mode. 47.0

Alarm is generated when battery voltage rises to this level in floating


9 FL HI ALARM-V
charging mode. 56.0

Alarm is generated when battery voltage descends to this level in floating


10 FL LLO ALARM-V
charging mode. 45.0

Alarm is generated when battery voltage rises to this level in equalizing


11 EQ LLO ALARM-V
charging mode. 47.0

Voltage at which LVD1 is triggered.


12 LVD1 VOLTAGE
(To set LVD2 voltage, see option 36 below.) 43.0

13 TIME SETUP Time setup for LCD display.

14 DATE SETUP Date setup for LCD display.

15 SITE ID Unique site identifier number.

16 ENAB AUTO EQ Automatic equalizer - feature enable/disable. No

17 ENAB TEMP COMP temperature compensation - feature enable/disable. No

18 TEMP COMP VALUE Coefficient, mV / °C (relative to ). 60mV

19 TEST TOP TIME Maximum permitted duration of battery test (minutes). 30min

20 TEST PERIOD Interval between automatic battery tests (days). 30days

21 EQUL TOP TIME Max. permitted duration of equalizing charge mode (hours). 1hours

22 EQUAL PERIOD Interval between automatic equalizing charging (days). 30 days


23 EN CURR LIM Current limiting: enable/disable. yes

24 CURR LIM VALUE Current limiting value (amps). A20


LCD A specified
# Description
Display value

ENABLE
25 Automatic battery test: enable/disable. YES
AUTO TEST

LVD hysteresis (in volts). This parameter


enables you to define the sensitivity of the
LVD HYST LVD to voltage changes when the dc
26 1 volt
VOLT voltage is at the LVD trigger threshold. A
value greater than zero prevents the LVD
from rapidly “hiccupping” open and closed.

0-255 (for use by communication


27 SOFT-ID 222
protocol).
AC LO Trigger voltage for “Ac input voltage low”
28 185
ALARM-V alarm.
AC HI Trigger voltage for “Ac input voltage high”
29 254
ALARM-V alarm.

OVER TEMP Trigger temp. for battery temperature


30 45
ALRM alarm.

Set backlight duration (“long” stays on for


31 BACKLIGHT 1
4 minutes).

Audible alarm duration – 15 seconds or


BUZZER
32 non-stop. (The audible alarm can always 1
DUR
be silenced by pressing the ESC key.)

DC TOO HI Trigger voltage for DC voltage too high


33 58 volt
ALM alarm.

OVER
34 Trigger level for overload alarm (amperes). 250A
LOAD ALM

EN RMT
35 Enable / disable remote command feature. yes
COMND
LVD2
36 Trigger voltage level for LVD2. 44VOLT
VOLTAGE
Checking alerts
Main Menu> 3-Alarms
Determining number of suppliers
Main Menu> 5-Advanced> 2-Config
Press the ENTER button
Use the arrows to determine the number of suppliers on the
site.

# LCD DISPLAY Description

Number of actual rectifier modules in the Number of P,S


1 NUM OF RECTS
system. 2\3

2 BATT CAPACITY capacity in Ah. AH100

3 HI/LO CAP is high capacity or low capacity. LOW


Communication rate: 9600 bps or 2400
4 BAUD 9600
bps.
5 NUM OF LVDS Set number of LVDs. 1
Number of batteries in the system (1 or
6 NUM OF BATTS 1
2).

7 AC 380/230 V AC input is 380 V or 230 V. 230

Number of slots in the system, whether


8 NUM OF SLOTS they are occupied with the controller or a 2
rectifier or they are empty.

Defines whether the ac voltage


measurement is taken from the rectifiers
or from a central measurement BY
9 AC IN REF
transformer. transformer
(The central measurement transformer is a
special order item; consult your vendor.)

10 NUM OF PHASES Define number of input ac phases: 1 or 3. 1


‫קביעת מגעים‬
‫יבשים‬
Main Menu >5- Advanced > 3 assn dry hot

OUTPUT DRY CONTACT #


ALARM
ALARM DESCRIPTION
#
1 2 3 4 5 6

1 X AC input voltage exceeds maximum settings

2 X AC input voltage is lower than minimum

3 X DC voltage exceptionally low – Equalizing or floating

4 X DC voltage below minimum – Equalizing or floating

5 X X DC voltage exceeds maximum – Equalizing or floating

6 X circuit breaker is OPEN


7 temperature exceeds maximum

8 X Last battery test failed (non-volatile message)

9 X circuit breaker is OPEN


10 Dry In is OPEN

11 X Communication with rectifier(s) – No response

12 X LVD forced OPEN


13 X -UNUSED-

14 X One or more load circuit breakers are open

15 -UNUSED-
16 X AC input surge has blown
17 X test time-stamp
18 X Equalizer test time-stamp

19 X DC voltage exc. high – switches OFF 1 by 1 until DC within range

20 X Overload
21 -UNUSED-
22 -UNUSED-
23 -UNUSED-
24 -UNUSED-
25 -UNUSED-
26 X CNVCOM
27 X HI- 24V
28 X LO-24V
29 -UNUSED-
30 -UNUSED-
31 X Controller time-stamp

32 -UNUSED-
IP Setting
ENT on the main screen pressing
5-Advanced> Scrolls using the arrows to the screen
Press the ENT button
Enter the password using the right arrow button.
The password is: ******** (eight times *)
Press the ENT button
8-Comms to browse using arrows to screen
Press the ENT button twice
SET IP
010.10Z.SSS.150 Using the arrows to browse to the
address
Press the ENT button
MASK
255.255.255.000 Using the arrows to browse to the
address
Press the ENT button
GTWY
010.10Z.SSS.254 Using the arrows to browse to the
address
When finished, press the ENTER button
. 3 times ESC has to click