FLAME SCANNER
Presented By
Vishal Laddha
C&I
INTRODUCTION
•PRINCIPLE PURPOSE OF FLAME SAFEGUARD SUPERVISIORY SYSTEM IS
TO ENSURE THAT IT IS SAFE TO LIGHT THE BOILER AND CONTINUE
BOILER OPERATION.
UV Type : 10 nm to 400 nm
Visible light Type : 380 nm to 740 nm
IR Type: 700 nm to 1 mm
“BHELSCAN” uses visible spectrum for flame sensing.
•AN IDEAL FLAME SCANNER DETECTS A FLAME OF
INTEREST WHILE TOTALLY IGNORING OTHERS AND IS
UNAFFECTED BY CHANGES IN AMBIENT CONDITIONS.
It senses the visible light given off by the flame and can recognize a coal/oil
flame by its characteristic fluctuations.
The scanner head assy. is normally installed in the wind box assembly
Scanner head
LOG. AMP.
PHOTO VOLTAGE
DIODES TO
CURRENT
CONVERTER
LED
FEEDBACK
FIBER OPTIC
CABLE
SCANNER
HOUSING
SCANNER HEAD
ASSEMBLY
FLAME SCANNER ASSEMBLY:-
SCANNER HEAD
SPACER LENS BODY
PLUG
Cooling air passes through the guide pipe, the flexible hose and
between the scanner head and housing. The air is discharged into the
furnace by removing any heat picked up from the hot combustion air.
The scanner head should not be exposed to a continuous temperature
above 300°F without cooling air.
After shutting down the unit, scanner cooling air must be maintained
until furnace conditions are such that the scanner assembly cannot
overheat.
ELECTRICAL COMPONENTS:-
The electrical components of the BHELSCAN system are
contained in the scanner housing assemblies and the card
rack assembly.
A photo diode located in each scanner housing assembly
converts visible light (flame signal) observed by the
scanner head into an electrical equivalent signal.
The scanner housing output signal is an AC current signal,
which is sent to the card rack assembly for processing.
In the card rack assembly, each current flame signal is
converted into a voltage flame signal. The voltage flame
signal is then separated into intensity and frequency
components.
An intensity signal indicates the magnitude of the flame
brightness on 2½ digit LED display(Range is 0-100%).
A fault signal is established if the intensity component is
less than its minimum preset limit or greater than its
maximum preset limit. If a fault signal is established, a
fault LED is lit and flame signal cannot be established for
that corner. Hence oil flame or coal flame lights will not
come ON.
DESCRIPTION OF MODULES:-
Flame scanner card rack assembly consists of the following modules:
1. Flame processor module- 4 Nos.
2. 2/4 output module - 1 No.
3. Power supply unit - 1 No.
There are two semiconductor fuses rated for 63mA are available in the
flame processor motherboard to protect the DC supply to scanner head
electronics.
The front facia of this module consists of a 7-segment display, 9 status LEDs and
one Push Button
Figure - 6B
BHELSCAN – GENERAL ARRANGEMENT
Figure - 7B
BHELSCAN –FLAME PROCESSOR MODULE
AC gain
pot.(Coal)
2/4 Relay
Fault Relay
Figure - 9B
BHELSCAN –POWER SUPPLY MODULE (FRONT VIEW)
Figure - 9C
BHELSCAN –POWER SUPPLY MODULE (REAR VIEW)
Power Supply Module
1. +15 V DC
2. –15V DC
3. +5.0V DC
The digital outputs of flame1 (coal) and flame2 (oil) status are fed to
the 2/4 output module. A 4-20 mA current output is available to
represents the intensity of the flame.
Dip Switch Setting Procedure