Vous êtes sur la page 1sur 31

Operation and Maintenance

AGENDA

 Off-line Maintenance

 Online Maintenance

 Asset Management

Presentation title | Client’s name or Subtitle | DD Month Year 2


Off-line Maintenance
Off-line Maintenance

 All of the installed underground HV cable for PLN use Crosslink


Polyethilene (XLPE). Hence, it can be categorized as Maintenance
Free.

Presentation title | Client’s name or Subtitle | DD Month Year 4


Offline Maintenance
During off-line, maintenance practices can implemented as follows:
 All the link boxes are designed to be water-proof. Therefore, it is
critical to ensure all the parts are installed properly and there is no
possibilty of fluid leaking in
 Cleaning up the grounding parts, especially ceramic components for
outdoor termination

Presentation title | Client’s name or Subtitle | DD Month Year 5


On-line Maintenance
On-line Maintenance

 Normally, on-line maintenance can only be undertaken at outdoor


sealing end using thermal hot spot detector
 To be able to monitor and manage the whole system while being on-
line, one needs to install an asset management system beforehand.
Such as Pry-Cam

Presentation title | Client’s name or Subtitle | DD Month Year 7


Asset Management
Efficient Maintenance Practice

Cost efficiency
Pre
dicti Based on prediction of
ve critical conditions
Mai
nte
nan
ce
Based on condition
Condition-Based assessment
Maintenance

Planned based on time


Preventive Maintenance or usage data

Run to failure
Reactive Maintenace

Presentation title | Client’s name or Subtitle | DD Month Year 9


Trends in HV AC Internal Failures

XLPE PILC (Paper-Insulated Lead Cable)

SCOF (Self Contained Oil-Filled Power Cable) Other cables

• For cable systems, failures are not


significantly time-correlated
Presentation title | Client’s name or Subtitle | DD Month Year 10
Pry-cam

Presentation title | Client’s name or Subtitle | DD Month Year 11


Why partial discharges?

Presentation title | Client’s name or Subtitle | DD Month Year 12


Why Partial Discharges

Presentation title | Client’s name or Subtitle | DD Month Year 13


Facts

More that 80% of failures in HV/MV assets are related to Partial Discharge (PD) activity

95% % of Insulation Failure

91% 90% 89%


87%
84%

This is WHY we are strongly committed to


on-line, accurate & reliable PD testing

Source: 493-1997 - IEEE Recommended Practice for the Design of Reliable Industrial and Commercial Power Systems (Gold Book)

Presentation title | Client’s name or Subtitle | DD Month Year 14


Type of Partial Discharge

Typical position compared


a) with supply voltage

Corona

b)
Surface
discharge

c)

Internal
discharge
High Risk

Presentation title | Client’s name or Subtitle | DD Month Year 15


PRY-CAM PORTABLE

ACCURATE ACQUISITION SYSTEM


250 mega samples per second
100 MHz bandwidth

PATENTED WIRELESS
SENSOR FOR PD AND
AC SYNCH

Presentation title | Client’s name or Subtitle | DD Month Year 16


PRY-CAM PORTABLE

Key advantages for Customers

• Maximum safety for operators thank to the galvanic


isolation
• Accurate and reliable diagnosis thank to the
complete PD pattern acquisition
• No supply interruption
• Maximum flexibility to test several components with
one device

Presentation title | Client’s name or Subtitle | DD Month Year 17


New business model

 Annual fee

 Unlimited usage

Presentation title | Client’s name or Subtitle | DD Month Year 18


PRY-CAM CLOUD
_____________________________

YOUR ASSET UNDER CONTROL

Presentation title | Client’s name or Subtitle | DD Month Year 19


Products Portofolio

PRY-CAM WINGS
Sensor for Partial Discharge and local temperature

PRY-CAM GRIDS
For continuous Partial Discharge monitoring

PRY-CAM DLOG
For continuous monitoring of the asset key
parameters

DTS
For distributed temperature sensing of
power cables

DAS
For distributed acoustic
sensing of power cables

Presentation title | Client’s name or Subtitle | DD Month Year 20


Energyzing the Pry-cam Grids

How to energize Pry-


Cam Grids
• Energy
Harvester
(ONLY for AC)
• External
battery + PV
panel
• LV Power
network
• Pry-Cam Cable

Presentation title | Client’s name or Subtitle | DD Month Year 21


Pry-Cam Wings Installation

Example of installation of the sensors in a three phase HV circuit joints.

Presentation title | Client’s name or Subtitle | DD Month Year 22


Pry-Cam Monitoring Systems

Land cable monitoring system


FO connection
Pry-Cam Grids

Presentation title | Client’s name or Subtitle | DD Month Year 23


Pry-cam Wings Sensors

Pry-Cam Grids, 3-channel


Pry-Cam Wings
AC
HV & MV

• 1 PD monitor every approx. 1-


1.5km (every second or third
Joint Bay)
• Sensors within 1m from NWC

HVDC Pry-Cam Grids, 4-


channel
• 1 PD monitor every Joint Bay
• 2 sensors on every Joint (at 2m)
• 1 sensor for every termination
(<1m)

Presentation title | Client’s name or Subtitle | DD Month Year 24


Other techniques available for cable monitoring

Presentation title | Client’s name or Subtitle | DD Month Year 25


Distributed Temperature Sensing - Goals

• Detect hot spots in order to protect


the cable and accessories

• Maximize the load in the cable in real-


time based on:
 historical loads
 actual ambient conditions

• Simulate possible scenarios

Presentation title | Client’s name or Subtitle | DD Month Year 26


Distributed Temperature Sensing – The Process

• Sensor cable attached or


integrated into High Voltage
Cable

• Temperature is measured along


the entire cable length

• Rating Software calculates


conductor temperature and
predicts temperatures under
certain load scenarios

Presentation title | Client’s name or Subtitle | DD Month Year 27


Distributed Temperature Sensing

• A laser injects a light pulse in the Fiber Optics sensor cable


• The backscattered light is acquired and processed
• Depending on how the backscattered light is processed, two DTS
technologies are available:
• Raman
• Brillouin

Presentation title | Client’s name or Subtitle | DD Month Year 28


Distributed Accoustic Sensing – DAS

Distributed Acoustic Sensing (DAS)

 Mechanical hazards detection: anchoring, digging, theft

 Fault localization

Presentation title | Client’s name or Subtitle | DD Month Year 29


Combined Monitoring System

HVAC/HVDC CABLE SYSTEMS

MONITORING SYSTEMS After installation test Failure prediction Optimized operation Failure location

Insulation defects
Partial discharge
✓ ✓
Hot spots
Distributed Temperature Sensing
+ Real time thermal rating ✓ ✓
Mechanical hazards
Distributed Acoustic Sensing
✓ ✓
Combined monitoring system
(PD+DTS+RTTR+DAS) ✓ ✓ ✓ ✓

Presentation title | Client’s name or Subtitle | DD Month Year 30


Thank you