R2 – R6 R7 – R8 R7 – R8 75 – 2800 kW
1.1 – 110 kW 55 – 500 kW 55 – 560 kW
Frame for
-control board
-I/O
-options
ABB Tmax Moulded case circuit breaker, ABB miniature circuit breaker and
manual motor starters can be use instead of fuses up to 440kVA drives.
Reduced Run Function for inverters with APBU-44 branching unit Redundant ACS800-07
If one inverter module is broken:
• remove broken inverter module
• drive diagnostics indicates that one inverter module is missing (INT CONFIG)
• user’s must change the value of parameter 95.03 (16.10 in multidrive SW) one
number smaller
• Reset fault
• Start the drive!
DSU modules can run automatically with reduced power after broken
module is removed
CDP 312R
CDP 312