Académique Documents
Professionnel Documents
Culture Documents
1
2
3
Advantages of Static Relay
The static relay consumes very less power because of which the
burden on the measuring instruments decreases and their accuracy
increases.
The static relay gives the quick response, long life, high reliability and
accuracy and it is shockproof.
The relay amplifies the input signal which increases their sensitivity.
6
The construction of the relay is easily affected by the surrounding
interference.
7
Differential Relay – The relays operate when some specified phase or
magnitude difference between two or more electrical quantities
occurs.
8
Definite Time Lag Relays – In these relays, the time of operation is
sensibly independent of the magnitude of the current or other
quantity causing operation.
Inverse Time Lag Relays – In this relay, the magnitude of the current
or other quantity causing operation is inversely equal to the time
requires for the operation.
9
Comparator
Types of Comparator
Amplitude Comparator
Phase Comparator
Hybrid Comparator
10
comparator
One of the inputs is the operating quantity and the other a restraining
quantity. When the amplitude of the operating quantity exceeds that
of restraining quantity, the relay sends a tripping signal to the circuit
breaker.
12
The Amplitude comparator compares two vector, |A| and |B|
- Gives an output: the algebraic difference between the
magnitudes |A| and |B|
- Output is +ve, if |A| > |B|
- Output is –ve, if |A| < |B|
- Output is zero, if |A| = |B|
Comparison by ratio:
- Output is >1, if |A| > |B|
- Output <1, if |A| < |B|
- Output is Zero, if |A| is zero.
13
Amplitude comparator types
Integrating comparator
Instantaneous comparator
Sampling Comparator
Integrating Comparator
14
Circulating Current Type
The polarized relay operates when S1>S2 where S1=K1i1 and S2 = K2i2. This
arrangement gives a sensitive relay whose voltage may be represented
in the VI characteristic of the figure. 15
Opposed Voltage type
This type works with voltage input signals derived from PTs. The
operation depends on the difference of the average rectified
voltage (V1-V2).Here the rectifiers are not protected against higher
16
currents. The relay operates when V1 >V2.
17
Instantaneous Comparator (Directing Amplitude
Comparator) – Averaging Type
18
Here the restraining signal is rectified and smoothed completely in
order to provide a level restraint.
Restraining signal is then compared with the peak value of
operating signal, which may or may not be rectified but is
smoothened.
The tripping signal is provided if the operating signal exceeds the
level of the restraint.
Since this method involves smoothening, the operation is slow.
19
A faster method is phase splitting the wave shapes of instantaneous
amplitude comparator are shown in fig. Before rectification the
averaging circuit can be eliminated.
20
Phase Comparator
• Period of coincidence of +ve polarity of 2 signals are
compared with a reference angle. (usually 90 degree)
• If the 2 signals have a phase difference of ɸ, then the
angle of coincidence ψ = 180 - ɸ.
• If ɸ < 900, then ψ > 900. The phase comparator may be
designed to trip the C.B, when ψ > 900.
• The period of coincidence is measured by different
techniques.
21
22
Phase Comparator
Phase comparison technique is the most widely used one for all
practical directional, distance, differential and carrier relays.
If the two input signals are S1 and S2 the output occurs when the
inputs have phase relationship lying within the specified limits.
Both the input must exist for an output to occur. The operation is
independent of their magnitudes and is dependent only on
their phase relationship.
23
The figures below show the phase comparator. The function is
defined by the boundary of marginal operation and represented by
the straight lines from the origin of the S-plane.
24
The condition of operation is β1 < θ < β2.
25
Types of Phase Comparator
• 1.2.1 Vector product P.C
a) Hall effect P.C
b) Magneto-resistivity P.C
• 1.2.2 Coincidence type P.C
a) Block spike P.C
b) Phase-splitting type P.C
c) Integrating type P.C
d) Rectifier bridge type P.C 26
Vector Product comparator
28
29
b) Phase Splitting Comparator
• In this method, two phase shifted (+/-45 0) components
30
31
Hybrid Comparator
This kind of comparator compares both magnitude and phase of the input quantities.
Hence this type is of mixed version.
In the hybrid comparator, both amplitude and phase comparators are used. Inputs are
given to a phase comparator. The output of the phase comparator is given to
amplitude comparator.
When input I exceed the level (L) and the output (O) of the level
detector exceeds and the output stage of the relay gets a triggering
signal via an amplifier
33
General Equation for Comparators
Let us first derive the general threshold equation assuming that
there are two input signals S1and S2 such that when the phase
relationship or magnitude relationship fulfills pre-determined
threshold conditions, tripping is initiated.
The input signals are derived from the system through instrument
transformers (CTs and/or PTs). In case the two quantities to be
compared are different (i.e., voltage and current), some form of
mixing device, such as current voltage transactor, is required.
34
Where, A and B are the primary system quantities, K1 and K3 are the
scalar numbers and |K2|and | K4| are the complex numbers with
35
36
Analysis for Amplitude Comparator:
If the operating criterion is given by |S1| > |S2| then at the threshold
of operation
37
38
Analysis for Phase Comparator:
The two quantities to be compared are S1 and S2. Let the phase
Dividing the above equation by |K2||K4| |A|2 cos (θ2 – θ4), we have
–
40
41
In most of the relays, at least one of the constants K1, K2, K3 and K4 is
zero and two of them are often equal.
Also the angle of the two phasor constants is usually the same. This
makes the practical case relatively simple.
42
If θ2 = θ4, the values of r and c in the two cases are tabulated
below:
43
Duality between Amplitude and Phase Comparators:
It can be shown with the help of phasor diagrams that an inherent
amplitude comparator becomes a phase comparator and vice-versa
if the input quantities to the comparator are changed to the sum
and difference of the original two input quantities.
Consider the operation of an amplitude comparator with input
signals S1 and S2 such that it operates when |S1| > |S2|.
If the inputs are changed to |S1 + S2| and |S1 – S2| so that it operates
So the original amplitude comparator with inputs now |S1 + S2|
47
From the phasor diagram it is clear that if the original inputs S 1 and
S2 to the phase comparator are with such a phase relation that they
will operate the relay and if now the inputs are changed to |S1 + S2|
and |S1 – S2| and supplied to the same comparator, the comparator
Unless |S1| > |S2|, the phase relation between |S1 + S2| and |S1 – S2|
will not be less than 90° and hence the phase comparator with inputs
with the other, a small error in the larger quantity may cause an
49
Definite Time Overcurrent Relays
TC = RCloge [V / (V-VT)]
The operating time of overcurrent relays are constant irrespective of the level of the fault
current. In this case, an intentional time delay is introduced through a timing circuit. The
figure below shows that the simplified block diagram of a definite time overcurrent relay.
The input current signal derived from the main CT is converted to a proportional voltage
signal by the input transformer and then rectified, filtered and compared with the preset
threshold value of the level detector (1). If the voltage exceeds the preset threshold value,
the level detector gives an output voltage, thereby the charging of the capacitor C of the RC
timing circuit starts. As soon as the voltage across the capacitor exceeds the
preset threshold value (VT) of level detector (2), a signal through the amplifier is given and
time setting, respectively.
50
Instantaneous Overcurrent Relays
The block schematic diagram of the static instantaneous Overcurrent relay is shown in the
figure. The current derived from the CT is fed to the input transformer which gives a
proportional output voltage. The input transformer has an air gap in the iron core to give
linearity in the current / voltage relationship up to the highest value of current expected and
is provided with tapping on its secondary winding to obtain different current settings. The
output voltage of the transformer is rectified through a rectifier and then filtered at a single
stage to avoid undesirable time delay in filtering, so as to ensure high speed of operation. A
limit made of a zener diode is also incorporated in the circuit to limit the rectified voltage to
safe values even when the input current is very high under fault conditions. A fixed portion of
the rectified and filtered voltage (through a potential divider) is compared against a preset
pick-up value by a level detector and if it exceeds the pick-up value, a signal through an
amplifier is given to the output which issues the trip signal. The output device may either be
a static thyristor circuit or an electromagnetic slave relay.
51
Where V is the voltage applied to the capacitor. If V, R and C are constant, the charging
time for a given value of VT will be constant. The time TC can be varied by varying R-C
combinations and VT. In this case, since the capacitor charging is done from a fixed d.c.
output, voltage of level detector (1), the operating time of the relay for particular values
of R and C of the timing circuit and VT of the level detector (2) will be constant for
different values of the fault current.
52
Overvoltage, Overcurrent, and Overpower Relay – The relay operates when the voltage,
current or power arises above a specified value.
Undervoltage, Undercurrent, and Underpower Relay – The relays operate when the
voltage, current or power falls below a specified value.
Directional or Reverse Current Relay – The relay operates when the applied current
assumes a specified phase shift on the supply voltage and the relay is compensated for
the fall in voltage.
Directional or Reverse Power Relay – The relay operates when the applied voltage and
current assumed specified space displacement and no compensation is allowed for fall in
voltage.
53
Inverse-Time Overcurrent Relay
54
The block diagram of the inverse-time overcurrent relay is shown in the figure. The
current signal is converted to a proportional voltage signal by the input transformer and
then rectified, filtered and compared with a reference voltage of the level detector (1) set
by the potentiometer P1. Under normal conditions i.e., when the input current is low
switch S1 is ON, short circuiting the capacitor C of the RC timing circuit and switch S2 is
OFF. As soon as the input voltage exceeds the preset reference voltage of the level
detector (1), switch S1 is switched OFF and switch S2 is switched ON and the charging of
capacitor C of the timing circuits starts from a voltage proportional to the current.
Switches S1 and S2 are made of static components. When the voltage across the capacitor
C of the timing circuit exceeds the reference voltage of the level detector (2) as set by
potentiometer P3, a signal is given to the output device through an amplifier. Finally, the
output device issues the trip signal. Here the plug setting multiplier is given by the
transformer secondary tap and potentiometer P1 and the time multiplier setting is
determined by potentiometers P2 and P3.
55
56
57
Hardware Architecture of Numerical Relay
58
59
A digital relay consists of
60
Numerical distance relay
features
Distance Protection – several schemes Overcurrent Protection (directional/non-
including user definable directional)