And the practical limit for the separation between guard cables will be:
2dmax= 1,5*Sm
• At the end ours calculated parameters are:
Parámetros Valor
Sm 18,58 m
k 1,0
Ic 3,6584 kA
CFO 659,88 kV
w 1,2m
Z0 373,004
ha 8m
hmax 8m
Rc 0,0904m
r 0,00915m
Vc 702
E0 1500 kV/m
he 0,6851m
2dmax 27,88m
d 5m