Uninterruptible Power Supply

Technical Specification & Features


LP Series U

Technical presentation

ISO 9001
UL
CUL
FCC Class A
CE
Key Features & Benefits

• True On-Line Double Conversion …


provides highest level of power reliability
• Fully isolated output … additional power
fault protection
• Power factor corrected input (>0.99) …
clean input
• Scalable Using GEDE’s Unique
“Redundant Parallel Architecture (RPA)
… maximum reliability
• Superior battery management … enhanced
battery life time
• ECO-mode … energy savings for less critical
loads e.g., during off hours, emergency lights etc
• Small Footprint … easy to place
Key Features & Benefits (continued)

• Excellent inrush current handling… prevents tripping


protection devices
• Superior overload handling … protection against
unplanned overloads
• Minimal Output Voltage Distortion of <3% … stable
power for the load
• Multi-functional LCD screen … easy to operate
• Multi language display … Spanish etc
• Automatic battery testing – every 500 hrs. … no
“surprises”
• Cold start … unit can be started with no AC present
• No load shutdown … prevents unnecessary discharging of
batteries
Key Features & Benefits (continued)

• Backfeed relay … maximum safety


• EPO- Emergency Power Off… maximum
safety
• Multiple I/O voltages … 120,240, 208 VAC
• Alarm interface : RS 232 and OC
contacts … easy to integrate with existing
systems
• Redundant power supply for critical
functions (LCD, Bypass) … increased
reliability
• UL, C-UL and CE markings for world-
wide applications ...fits to many different mains
Product Specifications
LP Series 5-11U 5 kVA- 4 kW LP Series 8-11U 8 kVA - 6.4
LP Series 6-11U 6 kVA - 4.8 kW
kW LP Series 10-11U 10 kVA - 8
kW
Voltages and Frequencies

Input Voltage Output Voltage


• 208 – 230/240 • 120 + 208 + 230/240
• 120 V option (for 5/6 • Fully isolated, even in
kVA only in additional bypass mode
transformer cabinet; Output Frequency
Input Frequency • 50 or 60 Hz
• 45-65 Hz • (Front Panel Selectable)

Flexible input and output voltages and frequency


Operating Mode
True On-Line - double conversion
• Bypass enable / disable
… in frequency conversion mode no alarms
… in case of weak mains protects the equipment against
operations on mains
• Programmable frequency tracking range
(2%, 4%, 6%)
… compatible with gen-sets with wider frequency range
• HF PWM technique
… compact design , low-losses, excellent characteristics

Output Completely Independent of Input


Voltage and Frequency
LP Series U Front Panel

• LCD screen 2 lines with 16 characters


- Information Screen
status and alarm messages
- Service screen
internal settings test screens
- Set Up Screen
setting of parameters
• Push buttons (keypads to scroll up,
down, reset and enter)
• LED operation / alarm status
• On/Off switch turns unit on/off
completely, including bypass on back
of unit
Rear Panel
Manual On/Off switch turns unit
Bypass on/off completely,
including bypass

Battery fuses

Utility & Bypass Protection Magnetic


Circuit breakers for overload or
short circuit in the UPS load
I/O
terminals
RS232/contact interface/EPO
Conduit
box Optional:
SNMP or relay card
EMI

Cable entry Optional: RPA card

DC Connector for
external batteries
Technology without compromise

EMI protection Isolation on BYPASS


MANUAL
No inrush current
bypass
on bypass during start up
Bypass MCB
Elektronic
Bypass

Backfeed
protection Mains MCB
I/O •120/240
H bridge
terminals HF input Output •208
Surge converter Converter RFI
•GND
protection Filter
RFI •208
Filter External •120/240
Battery
LCD
Stepdown Internal

Batteries
Converter
Supply Isolation
up enter down
operation
transformer
alarm
Battery charging capacity
always active
General alarm, Utility failure

L
up120toVolt60 minutes
optional
auto-input xfrmr L
run time 4X Bypass active, Batterey low
UPS Shutdown
MICRO- processor CONTROL
N without additional
L charger RS232

Emergency External
battery
shutdown disconnected
INTERFACE
Option: SNMP card
Technology with Premium Performance

Input voltage:187-285 V at 100% load


Bypass
MCB RFI

Input voltage: 150-285 V at 50 % load


internal supply

F3

P
Line
MCB

THD-I < 10% PF 1 input converter


Technology : Output Converter

Inverter DC
voltage
+380V
Bypass 240 V
Isolation on
208V
bypass
Output
HS

•EMI
H-BRIDGE F3
Output C2
C1 converter
current

Output
transformer 2x 120
V
Heatsink 4X temp.sensor
IGBT 1x 120
temp.sensor
V
208 V
240 V
Fan speed controlled by load & heat
sink temperature
Battery Specifications

• Standard 20 X batteries 12V/7Ah (5/6kVA) or


12V/12Ah (8/10kVA)
• Charge voltage = 271V, 13.55V/battery
• Constant current/constant voltage characteristic
+ boost charge current is ± 0.3 C
• Temperature protected till 45ºC
• Battery extension up to 500 Ah
• Battery capacity programmable over LCD/serial
port
Superior Battery Management

• Ripple-free Boost Charging


• Temperature Compensated
Charging
• Load dependent end of
discharge voltage • Maximum Up-time
• No-load Shutdown • Prevents Damage
• Automatic Battery Test • Prolonged Battery
/every 500 hours Lifetime
• Deep Calibration Test • No Surprises
• Load dependent runtime
prediction
• Load dependent battery
low signal
Output Performance

• Output THD < 3% for linear loads


• Output Power Factor = 0.8
• Output filter performance control
enabling robust operation
• Fully isolated output
• Protected against:
– Low/high DC voltage
– Over-temperature
– Overload
– AC on Output
– Short circuit

No Compromise on Output Performance


Bypass Specifications

Manual
Bypass Bypass Hall Sensor Bypass Switch
MCB thyristors

Output • to output-
current transformer
Line
MCB
L1
UPS
L2

• Bypass input voltage -10 to +10%


• Bypass frequency window selectable 2%, 4%, 6%
• Tracking rate 1 Hz/sec “low”, 5 Hz/sec “high”
• Protected against overload
• Short circuit protection State-of-the-art Bypass
• Galvanic isolation
Communication

• Standard: RS 232 dialogue


UPS shutdown
Emergency Power off ( EPO )
External DC - fuse alarm

• Optional: SNMP - card


RS 232 is not available if SNMP is installed

Dry contacts

Easy to integrate into computer network


Available Options
• Power Distribution unit (PDU)
• External battery cabinets
• External battery cable
• Seismic anchor
• SNMP interface card
• Relay interface card
• RPA kit (Redundant Parallel Architecture)
• Alarm boxes
• Connectivity products, like Splitter box; interface kits;
interface software for all common OS, incl Java
• 120 Volt input voltage transformer/cabinet