Vous êtes sur la page 1sur 22

Training Woodward Corrosion Control Building

HVAC EQUIPMENT
Rev 0
Woodward CCB

Training Schedule

Classroom Review – 15 Minutes


1. Review MAU, Fans,
Site Review – 15 Minutes
2. Review MUA, Fans. Identify each product.
Woodward CCB
Packaged Heating Units Venmar CES
MAU-0100
Configurations MAU-0100

Indirect Fired
Gas Burner

Direct Drive
Fans Filter
Section
Configurations MAU-0100

Outside Air
Damper

Damper, Tamco Model 9000, Insulated

Actuator – Belimo Open/Closed 2 Position


Configurations MAU-0100

Filter
Section
Pre-filters
Merv 8 – 2” thick AAF Perfect Pleat

Average Pressure Drop = 0.5” WG


Change Filters at 1.0” WG

Filters Removeable from inside unit.


Access Door on side
Configurations MAU-0100

Fan
Section

Back
Draft
Air Entering Side Damper
Configurations MAU-0100

Fan
Section
Motor

Silencer
Configurations MAU-0100

Indirect
Gas Burner

Stainless Drum
and Tube.
Provides Heat
for Winter only
During Summer
shut of main
valve
Configurations MAU-0100

Skematic Layout
Configurations MAU-0100

Skematic Layout

Unit has 2 Fans


each with its own
VFD
Woodward CCB

Fans
MAU-0100
• 2 only 16” Diameter Direct Drive Fans
c/w 3 Hp Motors

• No Belts – Motors are pre-lubricated.


Ease of Maintenance

WHEEL
18 lbs

MOTOR
120 lbs
Ease of Maintenance

Change Filters on a Regular


Basis. Develop a schedule to do
appropriate filter changes.
Inspect after 30 days initially.

There is a Dwyer Gauge


Mounted on unit. Do not allow to
go above 1 inch wg.
Operation 1100 –MAU-01

If Supply Air is below 4.4 C (40 F) for 240


seconds, unit will shut down.

If Supply Air Temperature is above 51.67 C


( 125 F ) for 240 seconds the unit will shut
down.
Operation MAU-0100
Maintenance &
Service Contact

Local Service
Ambient Mechanical Ltd - 905-738-1768 ext 108
www.ambientmechanical.ca

JDM Air Power Services Inc 519-624-2131


www.jdmairpower.com
Woodward Corrosion Control Building
Fans
Fans

Centrifugal Fan
Direct Drive
FRP Construction
Model: MK Plastics CNW

EF-01 & EF-02


Fans

Inline Axial Fan


Direct Drive
Bearing Pre-Lubricated
Model: TCF Model TSL

FN-01
Fans

Tube Axial Inline


All Aluminum Construction
Direct Drive
Bearing Pre-Lubricated
Model: TCF Model TD

EF-03
Woodward CCB
EQUIPMENT

Local Service
Ambient Mechanical Ltd - 905-738-1768 ext 108
www.ambientmechanical.ca

JDM Air Power Services Inc 519-624-2131


www.jdmairpower.com