Xiria / Xiria E
Entrenamiento Nivel 2 avanzado

© 2010 Eaton Corporation. All rights reserved.


Introducción

2
2
Historia
• Introducida en 2002
• Started with a three panel block
• Next the four, two and five panel were developed
• Integrated metering added to the three panel block
• In 2012 launched the single panel, called Xiria E (Extendable)
• In 2013 added an “open” metering panel to the range

• Customer in more than 30 countries


• 50.000 panels sold worldwide
• Most compact metal enclosed SF6-free RMU in the market

3
3
Complete Xiria family

4
4
Rangos

5
5
Product Range (1)

Rated voltage 24 kV
Power frequency withstand voltage 50 kV
Impulse withstand voltage 125 kV
Rated current busbars 630 A
Short-time current * optional 3 s 20 kA-1s*
Rated normal current (max.) 630
Internal arc (IAC) 20 kA-1s AFL
Internal arc with chimney 16 kA-1s AFL

6
6
Product Range (2)

Rated voltage 24 kV
Power frequency withstand voltage 50 kV
Impulse withstand voltage 125 kV
Rated current busbars 630 A
Short-time current * optional 3 s 20 kA-1s*
Rated normal current (max.) 200 A
Internal arc (IAC) 20 kA-1s AFL
Internal arc with chimney 16 kA-1s AFL

7
7
Product Range (3)

Rated voltage 24 kV
Power frequency withstand voltage 50 kV
Impulse withstand voltage 125 kV
Rated current busbars 630 A
Short-time current * optional 3 s 20 kA-1s*
Rated normal current (max.) 630 A
Internal arc (IAC) 20 kA-1s AFL
Internal arc with chimney 16 kA-1s AFL

8
8
Product Range (4)

Rated voltage 24 kV
Power frequency withstand voltage 50 kV
Impulse withstand voltage 125 kV
Rated current busbars 630 A
Short-time current * optional 3 s 20 kA-1s*
Rated normal current (max.) 630 A
Internal arc (IAC) 20 kA-1s AFL
Internal arc with chimney 16 kA-1s AFL

9
9
Product Range (5)

Rated voltage 24 kV
Power frequency withstand voltage 50 kV
Impulse withstand voltage 125 kV
Rated current busbars 630 A
Short-time current * optional 3 s 20 kA-1s*
Rated normal current (max.) 200 / 630 A
Internal arc (IAC) 20 kA-1s AFL
Internal arc with chimney 16 kA-1s AFL

10
10
Product Range (6)

Rated voltage 24 kV
Power frequency withstand voltage 50 kV
Impulse withstand voltage 125 kV
Rated current busbars 630 A
Short-time current * optional 3 s 20 kA-1s*
Rated normal current (max.) 630 A
Internal arc (IAC) 20 kA-1s AFL
Internal arc with chimney 16 kA-1s AFL

11
11
Product Range (7)

Rated voltage 24 kV
Power frequency withstand voltage 50 kV
Impulse withstand voltage 125 kV
Rated current busbars 630 A
Short-time current * optional 3 s 20 kA-1s*
Rated normal current (max.) 630 A
Internal arc (IAC) 20 kA-1s AFL
Internal arc with chimney 16 kA-1s AFL

12
12
Product Range (8)

Rated voltage 24 kV
Power frequency withstand voltage 50 kV
Impulse withstand voltage 125 kV
Rated current busbars 630 A
Short-time current * optional 3 s 20 kA-1s*
Rated normal current (max.) N.A.
Internal arc (IAC) 16 kA-1s AFL
Internal arc with chimney Not available yet

13
13
Detalles de Construcción

14
14
Xiria E version - Basic Design
1. Low voltage compartment
2. Protection relay
3. Control panel
4. Mimic diagram
5. Voltage detection system
6. Inspection window
7. Mechanism
8. Cable cones
9. Cable clamps
10. Earth bar
11. Busbar
12. Change-over switch
13. Vacuum interrupter
14. Current transformers
15. Voltage transformers
16. Coil and resistor

15
15
Xiria Metering panel – Basic Design

2
1
1. Mimic diagram
3
2. Locking
3. Low voltage compartment
4 4. Coupling
5 5. Isolation caps
6. Busbars
6
7
7. Current transformer
8. High voltage compartment
8 9. Flexible VT connection
9 10. Voltage transformer
10 11. HV fuse
11

16
16
Architecture of compartments
• Extreme customer safety due to highest class
• LSC 2B PM 1
• Most critical parts in sealed compartment
• 3 in 1 embedded architecture
2
• simpel and safe construction
• Maintenance free
3

1. Low voltage compartment 5


2. Auxiliary compartment
3. Busbar / Breaker / Change-
over switch / mechanism 4
compartment
4. Cable compartment
5. Internal arc compartment

17
17
Extra safety due to
Double point of Isolation

• Highest safety for the operator.


• 2 points of isolation:
 2-position change-over
switch
 Vacuum interrupter
• changing-over in air
• interrupting in vacuum
• Simple operating mechanism
• Same set-up for CB and LBS

18
18
Construction simplicity due to same
housing construction and main parts
• All panels have same depth
• Block panels have same width (350mm)
• Modular panels have same width (500mm)
• Any sequence is possible

19
19
Mechanism – location & type
• both function (interruption & change-over) integrated
• same for LBS and CB
• same for block and E-versions
• housed in sealed for life tank
• maintenance free
• spring type

20
20
Mechanism - operation
• hand or motor-operated
• motor only for the breaker (LBS / CB), not for change-over switch

Closing
The closing spring is charged first (manually with the operation handle or by motor), automatically
followed by the closing movement. During the closing movement the opening springs are charged
automatically.
Opening
Opening is achieved by pressing the red mechanical trip pushbutton on the front or by energizing
the trip coil via the integrated overcurrent protection relay or via a remote trip signal.

Trip lever Trip coil

Trip mechanism

21
21
Mechanism – positions (demonstrated by movies)
Open position Closed position

22
22
Mechanism – remote control
• For LBS and / or CB
• Control options:
 Signalling
 Tripping
 Operation

Y2: Trip coil


Q1: Auxiliary contact vacuum interrupter
Q2: Auxiliary contact change-over switch
H1: Trip indictor
K7: Electronic controller
K8: Selector / timer unit
M1: Motor
Y1: blocking coil
U10: voltage converter (needed if not 24 VDC)

23
23
Cable compartment – earth bar
• Copper design
• M10 nuts for connecting cable earth screens
• Extra connection in most left / right panel
• M12 bolt connection on side for station earthing

24
24
Cable cones (according EN50181)

25
25
Cable clamps
• Plastic design, type KOZ
• Mounted on adjustable frame
• clamps for single and three phase cables

Three phase cables


Panel provided with one clamp with a diameter of
66-90 or 50-75 mm, suitable for the following
cables:

Single phase cables


Panel provided with three clamps with a
diameter of 36-52 or 26-38 mm, suitable
for the following max. cable diameters:

26
26
Cable connectors
• Not supplied with the Xiria delivery!
• various types can be installed
• type depending on cone type, A or C
• above 12 kV only connectors with earthed layer

27
27
Current transformers –
Design & location
• Different types possible:
 Ring core type for metering & protection
 Block type in “open” metering panel
Ring core Block
• Brand ring core type: Eaton, ELEQ
• Brand block type: Any, if dimensions according DIN 42600 narrow design
• Position of ring core type:
 Behind cone (selected number)
 Around cable

TC Protección

TC Medida

Behind cone
Around cable In metering panel

28
28
Current transformers –
Ratings

20 kA

29
29
Voltage transformers –
Design & location
• Different types possible:
 Single phase insulated
 With open connections in “open” metering panel
insulated open
• Brands:
 Sadtem for insulated type
 With open connections; any brand if dimensions is according
DIN 42600 narrow design
 Open type with option for HV fuse
 Both types have option for
anti-ferroresonance kit

Insulated type
integrated in panel In metering panel
30
30
Voltage transformers –
Ratings

31
31
Intelligent devices embedded
Short-circuit Trip indicator Advanced relay
indicator

Ampere meter

Voltage detection
system (VDS)
Self-powered
relay

32
32
Low voltage compartments
• Easy accessible
• Hinged solution for top-unit (Xiria E) and “open” metering panel
• Screwed or hinged solution for block version
• Secondary cable entrance:
 from the side for the block version
 from the top or the side for the Xiria E and “open” metering panel

33
33
Operación & Enclavamientos

34
34
Operación Manual

35
35
Operación Manual

36
36
Secuencia de Operación (1)

Posición de Servicio

37
37
Secuencia de Operación(2)

Posición Abierto

38
38
Secuencia de Operación (3)

Posición Aislado

39
39
Secuencia de Operación (4)

Posición Aterrizado

40
40
Secuencia de Operación (5)

Posición Test

41
41
Indicador de Posición

42
42
Indicador de Posición

43
43
Interlocks – Built-in types
• Interlock to prevent cable access from being opened if cable is not earthed
• Interlock to prevent operation of the change-over switch when the circuit-
breaker or load-break switch is in the ON position
• Interlock to prevent operation of the vacuum interrupter when the change-
over switch is not in an end position (busbar or earth position)
• The operating handle can only be removed in an end position. (vacuum
interrupter fully open or closed, change-over switch fully in busbar or earth
position)

44
44
Interlocks – padlockable types
• The active earthed position of the circuit-breaker or load break switch
can be locked with a padlock (only possible with cable access
compartment door closed)
• Interlock of the OFF button of the circuit-breaker or load break switch.
(switching off by the protective relay, if fitted, remains possible)
• Interlock of the OFF position of the circuit-breaker or load break
switch. Use is made of a separate accessory (padlockable locking
scissor) which is placed in the access hole for the operating handle of
the vacuum interrupter.

45
45
Interlocks – castell lock
• Provides that the key needs to be installed before the panel can be
switched to service position
• In case the key is removed the door can not be installed
• Without the door installed the panel can not be switched to service
position

46
46
Switchroom set-up

47
47
Internal Arc Test (IAC) – Tested ratings

• The panels within the Xiria familiy are tested for IAC
with classification AFL
A = Authorized personnel
F = Front (position of indicators)
L = Lateral (position of indicators)
• Standard all panels are tested for 20 kA-1s
• Exception for:
 Metering panel -> 16 kA-1s
 In case a chimney is installed behind a panel -> 16 kA-1s

48
48
Internal Arc Test (IAC) – Test set-up

49
49
Switchroom set-up (cellar venting)

50
50
Switchroom set-up (adjacient room
venting)

51
51
Switchroom set-up (adjacient room +
cellar venting)

52
52
Switchroom set-up (adjacient room +
cellar venting)

53
53
Switchroom set-up (in room venting)

Note:
•minimum ceiling height 2400mm
•Pressure check needed

54
54
Installing the system

55
55
Before installation
• Customer should make sure switchroom meets ambient conditions

56
56
Installation steps (1)
• Lifting
• Travelling
• Preparation prior to installation
• Setting up the panel

57
57
Installation steps (2)
• Coupling the panels
• Securing to the floor
• Connecting panel to panel wiring

58
58
59
59