Vous êtes sur la page 1sur 180

Advance

Refrigeration & Air


Conditioning

1
Training Agenda: Refrigeration &
Air Conditioning
Introduction
Type of refrigeration
Applied Psychrometric
Air Duct Design
Pressurization System
Chilled/Condenser Water Piping Design
Compressors
Condensers & Evaporators
Expansion Devices
Cooling Tower
Assessment of refrigeration and AC
Energy efficiency opportunities

2
Introduction

How does High Temperature Reservoir


it work?
Heat Rejected

R Work Input

Heat Absorbed

Low Temperature Reservoir

3
Introduction

How does it work?


Thermal energy moves from left to right through five
loops of heat transfer:
1) 2) 3) 4) 5)
Indoor air Chilled Refrigerant Condenser Cooling
loop water loop loop water loop water loop

(Bureau of Energy Efficiency, 2004) 4


Introduction

AC Systems
AC options / combinations:
• Air Conditioning (for comfort / machine)
• Split air conditioners
• VRV System in Group Housing etc.
• Fan coil units in a larger system
• Air handling units in a larger system
• Evaporating Cooling in a larger system
5
Introduction

Refrigeration systems for industrial


processes
• Small capacity modular units of direct
expansion type (50 Tons of Refrigeration)
• Centralized chilled water plants with
chilled water as a secondary coolant (50
– 250 TR)

• Brine plants with brines as lower


temperature, secondary coolant (>250 TR)
6
Introduction

Refrigeration at large companies


• Bank of units off-site with common
• Chilled water pumps
• Condenser water pumps
• Cooling towers

• More levels of refrigeration/AC, e.g.


• Comfort air conditioning (20-25 oC)
• Chilled water system (8 – 10 oC)
7
• Brine system (< 0 oC)
Types of Refrigeration
Introduction
Types of refrigeration
Applied Psychrometric
Air Duct Design
Pressurization System
Chilled/Condenser Water Piping Design
Compressors
Condensers & Evaporators
Expansion Devices
Cooling Tower
Assessment of refrigeration and AC
Energy efficiency opportunities

8
Types of Refrigeration

Refrigeration systems

• Vapour Compression
Refrigeration (VCR): uses
mechanical energy
• Vapour Absorption Refrigeration
(VAR): uses thermal energy

9
Types of Refrigeration

Vapour Compression Refrigeration


• Highly compressed fluids tend to get
colder when allowed to expand
• If pressure high enough
• Compressed air hotter than source
of cooling
• Expanded gas cooler than desired
cold temperature
10
Types of Refrigeration

Vapour Compression Refrigeration


Two advantages
• Lot of heat can be removed (lot of
thermal energy to change liquid to
vapour)
• Heat transfer rate remains high
(temperature of working fluid much
lower than what is being cooled)
11
Types of Refrigeration

Vapour Compression Refrigeration


Refrigeration cycle
3
Condenser
High
4 Pressure
Side
Expansion
Device Compressor

1 2 Low
Pressure
Evaporator Side
12
Types of Refrigeration
Low pressure liquid
refrigerant Vapour
in evaporator
Compression Refrigeration
absorbs heat and changes
to a gas Refrigeration cycle

3
Condenser
High
4 Pressure
Side
Expansion
Device Compressor

1 2 Low
Pressure
Evaporator Side
13
Types of Refrigeration
The superheated vapour
enters the compressor
Vapour Compression Refrigeration
where its pressure is
raised Refrigeration cycle
3
Condenser
High
4 Pressure
Side
Expansion
Device Compressor

1 2 Low
Pressure
Evaporator Side
14
Types of Refrigeration
The high pressure
superheated gas is cooled
Vapour
in several stages Compression
in the Refrigeration
condenser
Refrigeration cycle
3
Condenser
High
4 Pressure
Side
Expansion
Device Compressor

1 2 Low
Pressure
Evaporator Side
15
Types of Refrigeration
Liquid passes through expansion
device, which reduces its pressure
Vapour and
Compression Refrigeration
controls the flow into the
evaporator
Refrigeration cycle
3
Condenser
High
4 Pressure
Side
Expansion
Device Compressor

1 2 Low
Pressure
Evaporator Side
16
Types of Refrigeration

Vapour Compression Refrigeration


Type of refrigerant
• Refrigerant determined by the
required cooling temperature
• Chlorinated fluorocarbons (CFCs) or
freons: R-11, R-12, R-21, R-22 and R-
502

17
Types of Refrigeration

Vapour Compression Refrigeration


Choice of compressor, design of
condenser, evaporator determined by
• Refrigerant
• Required cooling
• Load
• Ease of maintenance
• Physical space requirements
• Availability of utilities (water, power) 18
Types of Refrigeration

Vapour Absorption Refrigeration

Condenser Generator

Hot
Side

Evaporator

Cold Absorber
Side

19
Types of Refrigeration

Vapour Absorption Refrigeration

20
Types of Refrigeration

Vapour Absorption Refrigeration

21
Types of Refrigeration

22
Types of Refrigeration

Vapour Absorption Refrigeration

23
Types of Refrigeration

Refrigerant-absorbent combinations for VARS

The desirable properties of refrigerant-absorbent mixtures for


VARS are:
i The refrigerant should exhibit high solubility with
solution in the absorber. This is to say that it should
exhibit negative deviation from Raoult’s law at absorber.

ii. There should be large difference in the boiling points of


refrigerant and absorbent (greater than 200oC), so that
only refrigerant is boiled-off in the generator. This
ensures that only pure refrigerant circulates through
refrigerant circuit (condenser-expansion valve-
evaporator) leading to isothermal heat transfer in
evaporator and condenser.
24
Types of Refrigeration

iii. It should exhibit small heat of mixing so that a high


COP can be achieved. However, this requirement
contradicts the first requirement. Hence, in practice a
trade-off is required between solubility and heat of
mixing.

iv. The refrigerant-absorbent mixture should have high


thermal conductivity and low viscosity for high
performance.

v. It should not undergo crystallization or solidification


inside the system.

vi. The mixture should be safe, chemically stable, non-


corrosive, inexpensive and should be available easily.
25
Types of Refrigeration

The most commonly used refrigerant-absorbent pairs in commercial


systems are:
1. Water-Lithium Bromide (H2O-LiBr) system for above 0oC
applications such as air conditioning. Here water is the refrigerant
and lithium bromide is the absorbent.
2. Ammonia-Water (NH3-H2O) system for refrigeration applications
with ammonia as refrigerant and water as absorbent.
Of late efforts are being made to develop other refrigerant-absorbent
systems using both natural and synthetic refrigerants to overcome
some of the limitations of (H2O-LiBr) and (NH3-H2 O) systems.
Currently, large water-lithium bromide (H2O-LiBr) systems are
extensively used in air conditioning applications, where as large
ammonia-water (NH3-H2O) systems are used in refrigeration
applications, while small ammonia-water systems with a third inert
gas are used in a pumpless form in small domestic refrigerators
(triple fluid vapour absorption systems). 26
Types of Refrigeration

Evaporative Cooling
• Air in contact with water to cool it close to ‘wet
bulb temperature’
• Advantage: efficient cooling at low cost
• Disadvantage: air is rich in moisture

Sprinkling
Water

Hot Air Cold


(Adapted from
Air
Munters, 2001)

27
Applied Psychrometric

28
Applied Psychrometric

29
Applied Psychrometric

30
Applied Psychrometric

31
Applied Psychrometric

32
Applied Psychrometric

33
Applied Psychrometric

34
Applied Psychrometric

35
Applied Psychrometric

36
Applied Psychrometric

37
Applied Psychrometric

38
Applied Psychrometric

39
Applied Psychrometric

40
Applied Psychrometric

41
Applied Psychrometric

42
Applied Psychrometric

43
Applied Psychrometric

44
Applied Psychrometric

45
Applied Psychrometric

46
Applied Psychrometric

47
Applied Psychrometric

48
Applied Psychrometric

49
Applied Psychrometric

50
Applied Psychrometric

51
Applied Psychrometric

52
Applied Psychrometric

53
Applied Psychrometric

54
Applied Psychrometric

55
Applied Psychrometric

56
Applied Psychrometric

57
Applied Psychrometric

58
Applied Psychrometric

59
Applied Psychrometric

60
Air Duct Design

61
Air Duct Design

62
Air Duct Design

63
Air Duct Design

64
Air Duct Design

65
Air Duct Design

TABLE 7 – RECOMMENDED MAXIMUM DUCT


VELOCITIES FOR LOW VELOCITY SYSTEMS (FPM)

66
Air Duct Design

67
Air Duct Design

68
Air Duct Design

69
Air Duct Design

70
Air Duct Design

71
Air Duct Design

72
Air Duct Design

Methods of Duct Design


1- Equal friction Method
2- Static Regain Method

1-Equal Friction Method

This method of sizing is used for supply, exhaust and


return air duct systems and employs the same friction loll
per foot of length for the entire system. The equal friction
method is superior to velocity reduction since it requires
less balancing for symmetrical layouts. If a design has a

73
Air Duct Design

mixture of short and long runs, the shortest run


requires considerable dampering. Such a system is
difficult to balance since the equal friction method
makes no provision for equalizing pressure drops in
branches of for providing the same static pressure
behind each air terminal.

74
Air Duct Design

Example 4 – Equal Friction Method of Designing


Ducts
Given:
Duct systems for general office (Fig.47).
Total air quantity – 5400 cfm
18 air terminals – 300 cfm each
Operating pressure forall terminals – 0.15 in. wg
Radius elbows, R/D = 1.25
Find:
1. Initial duct velocity, area, size and friction rate in the
duct section from the fan to the first branch.
2. Size of remaining duct runs.
3. Total equivalent length of duct run with highest
resistance.
4. Total static pressure required at fan discharge
75
Air Duct Design

2-Static Regain Method

The basic principle of the static regain method is to


size a duct run so that the increase in static pressure
(regain due to reduction in velocity) at each branch or air
terminal just offsets the friction loss in the succeeding
section of duct. The static pressure is then the same
before each terminal and at each branch.
The following procedure is used to design a duct
system by this method: select a starting velocity at the fan
discharge from Table 7 and size the initial duct section
from Table 6.

76
Air Duct Design

The remaining sections of duct are sized from Chart


10 (L!Q Ratio) and Chart 11 (Low Velocity Static Regain).
Chart 10 is used to determine the L/Q ratio knowing the
air quantity (Q) and length (L) between outlets or
branches in the duct section to be sized by static regain.
This length (L) is the equivalent length between the
outlets or branches, including elbows, except
transformations. The effect of the transformation section is
accounted for in “Chart 11 3 Static Regain.” This
assumes that the transformation section is laid out
according to the recommendation presented in this
chapter.

77
Air Duct Design

78
Pressurization System

STAIRCASE PRESSURIZATION CALCULATION FOR BASEMENT PART - A


BASEMENT TO GROUND FLOOR)

Q1 = Kf A √ Δ P

Q1 = Air Leakage in Cu. M./ Sec.

A = Area of Leakage in Sq.M.

ΔP = Pressure Difference in Pascal ( 50 Pa)

Kf = Coefficient 0.839

No. of Floors = Basement to Ground Floor = 2

No. of Doors = 2

Door Size = 1.2 M x 2.1 M

Gap Between door and Frame/Floor = 6 mm at Top and on side

= 15 mm at Bottom

Area of Leakage Between Door & Frame


= 2 x H x gap (side) + 1 x W x gap (Top) + 1 x W x gap (Bottom )

= 2 x 2.1 x 6/1000 + 1 x 1.2 x 6/1000 + 1 x 1.2 x 15/1000

= 0.0252 + 0.0072 + 0.018

= 0.0504 Sq. M.
79
Pressurization System

Area of Leakage in Closed Condition/Door = 0.0504 Sq. M.

Total Leakage Area for 2 No. Doors = 0.0504 x 2

= 0.10 Sq.M.

Q1 = 0.839 x 0.10 x √ 50

= 0.60 Cu. M/Sec.

= 1270 CFM

Leakage of Air Thru 2 No. Open Door ( 1 No. at affected floor + 1 No. at Exit to Building )

Q2 = Area of Doors x Velocity

= 2.1 x 1.2 x2 No. x 1.0 M/sec.

= 5.04 Cu. M./Sec

= 10671 CFM

Total Required Air Quantity = Q1 + Q2

= 1270 + 10671

= 11941 CFM
80
Pressurization System

LIFT WELL PRESSURIZATION CALCULATION

TOWER T1 (G+13)- 5 Nos.

Q = Kf A √ Δ P

Q = Air Leakage in Cu. M./ Sec.

A = Area of Leakage in Sq.M.

ΔP = Pressure Difference in Pascal ( 50 Pa)

Kf = Coefficient 0.839

No. of Floors = Lower Basement (Part-A) to 13th Floor = 16

No. of Doors = 16

Door Size = 2.1 M x 1.2 M

Area of Leakage Between Lift Door & Wall/ Door = 0.065 Sq. M.

Total Leakage Area for 16 No. Doors = 0.065 x 16

= 1.04 Sq.M.

Q = 0.839 x 1.04 x √ 50

= 6.17 Cu. M/Sec.

= 13063 CFM

Fan Capacity for Two Lift Well = 13063x2

= 26126 CFM

Say = 26500 CFM

1 No. 26500 CFM DIDW Centrifugal Fan Section For Fresh Air Supply
81
Chilled/Condenser Water Piping
Design

82
Chilled/Condenser Water Piping
Design

83
Chilled/Condenser Water Piping
Design

84
Chilled/Condenser Water Piping
Design

85
Chilled/Condenser Water Piping
Design

86
Chilled/Condenser Water Piping
Design

87
Chilled/Condenser Water Piping
Design

88
Chilled/Condenser Water Piping
Design

89
Chilled/Condenser Water Piping
Design

90
Chilled/Condenser Water Piping
Design

91
Chilled/Condenser Water Piping
Design

92
Chilled/Condenser Water Piping
Design

93
Chilled/Condenser Water Piping
Design

94
Compressors

95
Compressors

96
Compressors

97
Compressors

98
Compressors

99
Compressors

100
Compressors

101
Compressors

102
Compressors

103
Compressors

104
Compressors

105
Compressors

106
Condensers & Evaporators

Introduction
Reference Handbooks/Standards
Type of refrigeration
Applied Psychrometric
Heat Load Calculation
Air Duct Design
Pressurization System
Chilled/Condenser Water Piping Design
Compressors
Condensers & Evaporators
Expansion Devices
Cooling Tower
Assessment of refrigeration and AC
Energy efficiency opportunities
107
Condensers & Evaporators

108
Condensers & Evaporators

109
Condensers & Evaporators

110
Condensers & Evaporators

111
Condensers & Evaporators

112
Condensers & Evaporators

113
Condensers & Evaporators

114
Condensers & Evaporators

115
Condensers & Evaporators

116
Condensers & Evaporators

117
Condensers & Evaporators

118
Condensers & Evaporators

119
Condensers & Evaporators

120
Condensers & Evaporators

121
Condensers & Evaporators

122
Condensers & Evaporators

123
Condensers & Evaporators

124
Condensers & Evaporators

125
Condensers & Evaporators

126
Condensers & Evaporators

127
Condensers & Evaporators

128
Condensers & Evaporators

129
Condensers & Evaporators

130
Condensers & Evaporators

131
Condensers & Evaporators

132
Expansion Devices

133
Expansion Devices

134
Expansion Devices

135
Expansion Devices

136
Expansion Devices

137
Cooling Tower
Introduction
Type of refrigeration
Applied Psychrometric
Heat Load Calculation
Air Duct Design
Pressurization System
Chilled/Condenser Water Piping Design
Compressors
Condensers & Evaporators
Expansion Devices
Cooling Tower
Assessment of Refrigeration and AC
Energy efficiency opportunities

138
Cooling Tower

139
Cooling Tower

140
Cooling Tower

141
Cooling Tower

142
Cooling Tower

143
Cooling Tower

144
Cooling Tower

145
Cooling Tower

146
Cooling Tower

147
Cooling Tower

148
Cooling Tower

149
Cooling Tower

150
Cooling Tower

151
Cooling Tower

152
Cooling Tower

153
Cooling Tower

154
Cooling Tower

155
Cooling Tower

156
Cooling Tower

157
Cooling Tower

158
Cooling Tower

159
Cooling Tower

160
Cooling Tower

161
Cooling Tower

162
Cooling Tower

163
Cooling Tower

164
Cooling Tower

165
Cooling Tower

166
Cooling Tower

167
Cooling Tower

168
Cooling Tower

169
Cooling Tower

170
Cooling Tower

171
Assessment of Refrigeration and AC
Introduction
Reference Handbooks/Standards
Type of refrigeration
Applied Psychrometric
Heat Load Calculation
Air Duct Design
Pressurization System
Chilled/Condenser Water Piping Design
Compressors
Condensers & Evaporators
Expansion Devices
Cooling Tower
Assessment of Refrigeration and AC
Energy efficiency opportunities
172
Assessment of Refrigeration and AC

Assessment of Refrigeration
• Cooling effect: Tons of Refrigeration
1 TR = 3024 kCal/hr heat rejected

• TR is assessed as:

TR = Q xCp x (Ti – To) / 3024


Q= mass flow rate of coolant in kg/hr
Cp = is coolant specific heat in kCal /kg deg C
Ti = inlet, temperature of coolant to evaporator (chiller) in 0C
To = outlet temperature of coolant from evaporator (chiller) in 0C
173
Assessment of Refrigeration and AC

Assessment of Refrigeration
Specific Power Consumption (kW/TR)
• Indicator of refrigeration system’s
performance
• kW/TR of centralized chilled water
system is sum of
• Compressor kW/TR
• Chilled water pump kW/TR
• Condenser water pump kW/TR
174
• Cooling tower fan kW/TR
Assessment of Refrigeration and AC

Assessment of Refrigeration
Coefficient of Performance (COPCarnot)
• Standard measure of refrigeration efficiency
• Depends on evaporator temperature Te and
condensing temperature Tc:

COPCarnot = Te / (Tc - Te)

• COP in industry calculated for type of


compressor:

Cooling effect (kW)


COP =
Power input to compressor (kW) 175
Assessment of Refrigeration and AC

Assessment of Refrigeration

COP increases with rising COP increases with


evaporator temperature decreasing condensing
(Te) temperature (Tc) 176
Assessment of Refrigeration and AC

Assessment of Air Conditioning


Measure
• Airflow Q (m3/s) at Fan Coil Units (FCU) or Air
Handling Units (AHU): anemometer
• Air density  (kg/m3)
• Dry bulb and wet bulb temperature: psychrometer
• Enthalpy (kCal/kg) of inlet air (hin) and outlet air
(Hout): psychrometric charts

Calculate TR Q  ρ  h in  h out 
TR 
3024
177
Assessment of Refrigeration and AC

Assessment of Air Conditioning


Indicative TR load profile
• Small office cabins: 0.1 TR/m2
• Medium size office (10 – 30 people
occupancy) with central A/C: 0.06
TR/m2
• Large multistoried office complexes
with central A/C: 0.04 TR/m2
178
Assessment of Refrigeration and AC

Considerations for Assessment


• Accuracy of measurements
• Inlet/outlet temp of chilled and condenser
water
• Flow of chilled and condenser water

• Integrated Part Load Value (IPLV)


• kW/TR for 100% load but most equipment
operate between 50-75% of full load
• IPLV calculates kW/TR with partial loads
• Four points in cycle: 100%, 75%, 50%, 25% 179
180

Vous aimerez peut-être aussi