Energy Conservation opportunity In Street Light System

Date :-December 8, 2021


Replacement of conventional Ballast with
Energy Efficient Electronic Ballast
Flow of Presentation
 Background
 Objectives
 Key Strategies

2 confidential
Highlight Of REL Street Light System
-Total Number of Street Lights = 88,045

- Type of Lamp Used = 70W HPSV

= 150W HPSV

= 250W HPSV

- Maximum Demand of Street Lighting = 14.11MW

- Loss of Power as watt loss = 1.87 MW

- Operating P.F (Averages) = < 0.82

3 confidential
Energy Conservation opportunity in Street light system
 Objective

­ To meet need of time


­ Energy Conservation
­ Reduction in O&M cost.
­ Improve System Reliability

 Opportunity available
­Reactive power Management
­Dimming of street light during late night
­Utilization of energy efficient equipment. (E.g. Lamps, Ballast )

4 confidential
Pilot Project –Result –Based on meter Reading
Replacement of existing 21 no of Magnetic Ballast with Electronic ballast
Average
Average
Average Average Average Lux
Parameter P.F. % I THD %V THD Burning
KW KVA KWH ( Below
hrs
Lamp)

With Old Luminaries


Magnetic Ballast
4.09 5.30 1253.50 0.77 40.00 30.63 0.73 327.32

With New
Luminaries Magnetic 3.88 4.80 1212.00 0.93 44.00 30.63 0.73 341.10
Ballast

With New luminaries


With electronic 3.60 3.60 1388.00 1.00 47.90 4.73 0.70 390.18
Ballast

 Step -1
 PF Improve by 20.77 % from 0.77 to 0.93 , KW reduced by 5.13% ,KVA reduced by 9.43%

 Step-2

 PF Improve by 7.5 % from 0.93 to unity , KW reduced by 7.22% ,KVA reduced by 26.23%

5 confidential
Comparison of Kwh /hrs consumption based on meter reading---pilot project

Average Average
Parameter Average KWH
burning hrs KWH / Hrs
With Old Luminaries
1253.50 327.32 3.8296
Magnetic Ballast
With New Luminaries
1212.00 341.10 3.5532
Magnetic Ballast
With New Luminaries
1388.00 390.18 3.5573
Electronic Ballast

 KWH consumption / hrs reduced by 7.2 % when old luminaries are replaced with new luminaries

 There is no change in consumption when new magnetic ballast replaced with electronic ballast

 If all old 150 W luminaries with magnetic ballast are replaced with electronic Ballast
- KWH/Hr will be reduced by 7.2 %
- KVA will be reduced by 32.1%
- KW Will be reduced by 11.98%
- PF will improve by 29.88%

6 confidential
WATT LOSS CALCULATION-BASED ON METER READING
A B C D E=B/C F=E-D

WATT
RECORDED NUMBER WATT / WATT
INSTALLED W CONSUMED
W( Avg) OF LAMP LAMP LOSS/LAMP
  PER LAMP

WITH OLD 150W


LUMINARIES-MAGNETIC 3150.00 4009.00 21.00 150.00 190.90 40.90
BALLAST

WITH NEW 150W


LUMINARIES -MAGNETIC 3150.00 3860.00 21.00 150.00 183.81 33.81
BALLAST

WITH NEW 150W


LUMINARIES-ELECTRONIC 3150.00 3600.00 21.00 150.00 171.43 21.43
BALLAST

 Watt loss consumed per unit decreased by 47.6 % from old magnetic ballast to electronic ballast.

 Watt consumer per lamp decreased by 10.19 % from old magnetic ballast to new magnetic ballast

7 confidential
Cost –benefit analysis –Data as on 31/01/2010
1st year 2nd year 3rd year 4th year 5th year

Initial Investment (Mu RS) - 130


Energy saved (MU) 1.31 1.31 1.31 1.31 1.31
Cost of power perches 10.51 10.51 10.51 10.51 10.51
( Million Rs)
Cost material 2.24 2.24 2.24 2.24 2.24
( Million Rs)
Cost Labor & Transport 2.58 2.58 2.58 2.58 2.58
( Million Rs)

Selling cost of scrap 1.67 0.00 0.00 0.00 0.00


recovered (Million Rs)
Total cost saved 17.04 15.34 15.34 15.34 15.34

 NPV = -67.98 Million


Project is not finically viable
 We should wait for technology development.

8 confidential
Thank you
December 8, 2021