Vous êtes sur la page 1sur 48

Refrigeration System

Equipment Room Design

The Trane Company


La Crosse, Wisconsin
© American Standard Inc. 1997
ANSI/ASHRAE Standards

 Standard 34-1992 …
“Number Designation And Safety Classification
Of Refrigerants”

 Standard 15-1994 …
“Safety Code For Mechanical Refrigeration”

© American Standard Inc. 1997


ANSI/ASHRAE Standards …
Standard 34-1992

 Purpose? To establish a …
 “… simple means of referring to common refrigerants
instead of using the chemical name, formula, or trade
name.”
 “… uniform system for assigning reference numbers
and safety classifications to refrigerants.”

“Number Designation And


Safety Classification Of Refrigerants”
© American Standard Inc. 1997
ASHRAE Standard 34-1992 …
Refrigerant Safety Classifications

higher
flammability Group A3 Group B3

lower
flammability Group A2 Group B2

no flame
propagation Group A1 Group B1

lower toxicity higher toxicity

© American Standard Inc. 1997


ASHRAE Standard 34-1992 …
Refrigerant/Blend Data
Refrig Qty Per
Occupied Space
Refrigerant Chemical Name Or Normal Lbs/ PPM
Composition (% By Weight) Boiling Safety 1000 By
Methane Series Point Group cu ft Vol
CFC (or R) –11 Trichlorofluoromethane 75°F A1 1.6 4,000
CFC (or R) –12 Dichlorodifluoromethane –22°F A1 12.0 40,000
HCFC (or R) –22 Chlorodifluoromethane –41°F A1 9.4 42,000
Ethane Series
CFC (or R) –113 1,1,2–Trichlorotrifluoroethane 118°F A1 1.9 4,000
HCFC (or R) –123 2,2–Dichloro–1,1,1–Trifluoroethane 81°F B1 0.4 1,000
HFC (or R) –134a 1,1,1,2–Tetrafluoroethane –15°F A1 16.0 60,000
HFC (or R) –152a 1,1–Difluoroethane –13°F A2 1.2 7,000
Azeotropes
R–500 R–12 (73.8) / R–152a (26.2) –27°F A1 12.0 47,000
R–502 R–22 (48.8) / R–115 (51.2) –49°F A1 19.0 65,000

© American Standard Inc. 1997


ANSI/ASHRAE Standards …
Standard 15-1994

 Purpose?
 “… to specify safe design, construction, installation,
and operation of refrigerating systems.”
 Scope?
 “This code established safeguards for life, limb, health,
and property and prescribes safety standards.”

“Safety Code For


Mechanical Refrigeration”
© American Standard Inc. 1997
ANSI/ASHRAE Standards …
Standard 15-1994

It applies to …
 “ … mechanical refrigerating systems and
heat pumps used in the occupancies defined
in Section 4 and installed subsequently to
adoption of this code”

“Safety Code For


Mechanical Refrigeration”
© American Standard Inc. 1997
ANSI/ASHRAE Standards …
Standard 15-1994

It also applies to …
 “… parts or components added after adoption
of this code, or a change to a refrigerant of a
different number designation after adoption of
this code”

“Safety Code For


Mechanical Refrigeration”
© American Standard Inc. 1997
ANSI/ASHRAE Standards …
Standard 15-1994

Finally, it applies to …
 “… parts or components replaced after
adoption of this code only if they are not
identical in function”

“Safety Code For


Mechanical Refrigeration”
© American Standard Inc. 1997
ANSI/ASHRAE Standards …
Standard 15-1994

Provides classification criteria for …


 Safety group
 Occupancy type
 Refrigerating system “probability”

“Safety Code For


Mechanical Refrigeration”
© American Standard Inc. 1997
ANSI/ASHRAE Standards …
Standard 15-1994

Provides classification criteria for …


 Safety group
 Occupancy type
 Refrigerating system “probability”

“Safety Code For


Mechanical Refrigeration”
© American Standard Inc. 1997
ASHRAE Standard 15-1994 …
Safety Group Classification

 Standard 34’s refrigerant safety classifications

higher
flammability Group A3 Group B3

lower
flammability Group A2 Group B2

no flame
propagation Group A1 Group B1

lower toxicity higher toxicity


© American Standard Inc. 1997
ANSI/ASHRAE Standards …
Standard 15-1994

Provides classification criteria for …


 Safety group
 Occupancy type
 Refrigerating system “probability”

“Safety Code For


Mechanical Refrigeration”
© American Standard Inc. 1997
ASHRAE Standard 15-1994 …
Occupancy Classification

 Institutional
 Occupants can’t readily leave without help
 Public assembly
 Where large numbers of occupants can’t vacate quickly
 Residential
 Occupants have complete, independent living facilities
 Industrial
 Occupancy is restricted only to authorized personnel
© American Standard Inc. 1997
ASHRAE Standard 15-1994 …
Occupancy Classification

 Commercial
 Occupants transact business, receive personal
services, or purchase food or other goods
 Large mercantile
 Premises where more than 100 people congregate to
purchase personal merchandise
 Mixed
 Two or more occupancies share the same building

© American Standard Inc. 1997


ANSI/ASHRAE Standards …
Standard 15-1994

Provides classification criteria for …


 Safety group
 Occupancy type
 Refrigerating system “probability”

“Safety Code For


Mechanical Refrigeration”
© American Standard Inc. 1997
ASHRAE Standard 15-1994 …
Refrigerating System Probability
System Cooling Air Or Substance
Designation Or Heating Source To Be Cooled, Heated

High Probability Direct

Indirect
Open Spray

Double Indirect
Open Spray

Low Probability
Indirect
Closed

Indirect
Vented Closed
© American Standard Inc. 1997
ASHRAE Standard 15-1994…
Refrigerant Quantity Rules
Applicable Rules By Occupancy Classification
Public Assembly,
Refrigerant System Residential, Commercial,
Group Probability Institutional Large Mercantile Industrial
A1 High 2 1 3
Low 4 4 4
A2 High 5 5 3
Low 7 7 7
A3 High 9 9 3
Low 9 9 7
B1 High 2, 6 1, 6 3
Low 4 4 4
B2 High 5, 6 5, 6 3
Low 7 7 7
B3 High 9 9 3
Low 9 9 7
© American Standard Inc. 1997
ASHRAE Standard 15-1994 …
Refrigerant Quantity Rules
Applicable Rules By Occupancy Classification
Public Assembly,
Refrigerant System Residential, Commercial,
Group Probability Institutional Large Mercantile Industrial
A1 High 2 1 3
Low 4 4 4
A2 High 5 5 3
Low 7 7 7
A3 High 9 9 3
Low 9 9 7
B1 High 2, 6 1, 6 3
Low 4 4 4
B2 High 5, 6 5, 6 3
Low 7 7 7
B3 High 9 9 3
Low 9 9 7
© American Standard Inc. 1997
ASHRAE Standard 15-1994 …
Refrigerant Quantity Rules

Rule 4 …
 “When the quantity of refrigerant in any
system exceeds Table 1 amounts, all
refrigerant-containing parts, except piping and
those parts outside the building, shall be
installed in a machinery room constructed in
accordance with the provisions of 8.13.”

© American Standard Inc. 1997


ASHRAE Standard 34-1992 …
Refrigerant Safety Classifications
Refrig Qty Per
Occupied Space
Refrigerant Chemical Name Or Normal lbs/ PPM
Composition (% By Weight) Boiling Safety 1000 By
Methane Series Point Group cu ft Vol
CFC (or R) –11 Trichlorofluoromethane 75°F A1 1.6 4,000
CFC (or R) –12 Dichlorodifluoromethane –22°F A1 12.0 40,000
HCFC (or R) –22 Chlorodifluoromethane –41°F A1 9.4 42,000
Ethane Series
CFC (or R) –113 1,1,2–Trichlorotrifluoroethane 118°F A1 1.9 4,000
HCFC (or R) –123 2,2–Dichloro–1,1,1–Trifluoroethane 81°F B1 0.4 1,000
HFC (or R) –134a 1,1,1,2–Tetrafluoroethane –15°F A1 16.0 60,000
HFC (or R) –152a 1,1–Difluoroethane –13°F A2 1.2 7,000
Azeotropes
R–500 R–12 (73.8) / R–152a (26.2) –27°F A1 12.0 47,000
R–502 R–22 (48.8) / R–115 (51.2) –49°F A1 19.0 65,000

© American Standard Inc. 1997


Equipment Room Design

 Ventilation
 Refrigeration system placement
 Doors, passageways and access
 Refrigerant monitoring
 Open-flame devices
 Pressure-relief piping
 General requirements
© American Standard Inc. 1997
Equipment Room Design

 Ventilation
 Refrigeration system placement
 Doors, passageways and access
 Refrigerant monitoring
 Open-flame devices
 Pressure-relief piping
 General requirements
© American Standard Inc. 1997
equipment room design …
Ventilation

Volume requirements for …


 Natural ventilation
 Mechanical ventilation
 Normal rate
 Alarm rate

© American Standard Inc. 1997


equipment room design …
Ventilation

 Remote machinery room …

Occupied
Building
More Than
20 Feet
Occupied
Building

Lean-to Or Other
Refrigeration Structure With
System Natural Ventilation

© American Standard Inc. 1997


equipment room design …
Ventilation

 Natural ventilation
 For refrigerating systems installed “outdoors, more
than 20 ft from [any] building openings …”

F = G0.5
where:
F = free opening area (sq ft)
G = mass of refrigerant (lbs)

© American Standard Inc. 1997


equipment room design …
Ventilation
 Normal-rate mechanical ventilation
 Needed whenever the equipment room’s occupied
 Requirements:
 0.5 cfm per sq ft OR 20 cfm per person
 Must operate, if necessary for operator comfort, at a volume that limits the temperature rise ( T) to no more than 18°F

© American Standard Inc. 1997


equipment room design …
Ventilation

 Alarm-rate mechanical ventilation


 Required to exhaust accumulated refrigerant

Q = 100 × G0.5
where:
Q = airflow (cu ft per minute)
G = mass of refrigerant (lbs)

© American Standard Inc. 1997


equipment room design …
Ventilation

 Suggested exhaust fan location …


Exhaust Fan

6 Feet

© American Standard Inc. 1997


equipment room design …
Ventilation Exhaust
End View

Airflow

 Dual-purpose
ventilation system …
Plan View

Ventilation
Airflow

© American Standard Inc. 1997


Equipment Room Design

 Ventilation
 Refrigeration system placement
 Doors, passageways and access
 Refrigerant monitoring
 Open-flame devices
 Pressure-relief piping
 General requirements
© American Standard Inc. 1997
equipment room design …
Refrigeration System Placement
 Unobstructed space for inspecting and servicing equipment
 Must comply with applicable safety standards and requirements of the presiding regulatory agency
 Clear head room not less than 7.25 ft below equipment over passageways

© American Standard Inc. 1997


equipment room design …
Refrigeration System Placement

 Multiple-chiller equipment room layouts …

Refrigeration
Exhaust
Systems
Fan
Air
Inlet
Exhaust
Fan
Air
Inlet Exhaust
Fan

Air Refrigeration
Inlet Systems
Refrigeration
Systems
Exhaust
Fan
Arrangement A Arrangement B
© American Standard Inc. 1997
Equipment Room Design

 Ventilation
 Refrigeration system placement
 Doors, passageways and access
 Refrigerant monitoring
 Open-flame devices
 Pressure-relief piping
 General requirements
© American Standard Inc. 1997
equipment room design …
Doors, Passageways And Access

 Equipment room access limited to authorized


personnel
 Adequate number and type of doors
 No openings to other parts of the building
 No “shared” air-handling systems

© American Standard Inc. 1997


Equipment Room Design

 Ventilation
 Refrigeration system placement
 Doors, passageways and access
 Refrigerant monitoring
 Open-flame devices
 Pressure-relief piping
 General requirements
© American Standard Inc. 1997
equipment room design …
Refrigerant Monitoring

“Detector” must …
 Be appropriately sensitive to the refrigerant(s)
in use
 Activate alarm and ventilation at TLV®–TWA
 “Threshold Limit Value–Time Weighted Average”

© American Standard Inc. 1997


equipment room design …
Refrigerant Monitoring

Sensor location and placement …


 Height: 18 inches above the floor
 Plan
 Continuous ventilation: Between the refrigeration
system and room exhaust
 Intermittent ventilation: Close to the refrigeration
system, between it and the room entrance

© American Standard Inc. 1997


equipment room design …
Refrigerant Monitoring

 Typical refrigerant monitor installation …

Roof Or Concrete Floor

Occupied Space Mechanical Equipment Room

Refrigerant
Monitor

Sample-In Tubing

5 Feet
Particle Filter Chiller

12–18 Inches © American Standard Inc. 1997


equipment room design …
Refrigerant Monitoring

 Suggested sensor placement for intermittent


ventilation …

Refrigeration Systems

Identifies refrigerant sampling points


© American Standard Inc. 1997
equipment room design …
Refrigerant Monitoring
 Typical multichannel
scanner application …

Refrigerant Monitor
With Multichannel Option
Pit

Identifies refrigerant sampling points


© American Standard Inc. 1997
Equipment Room Design

 Ventilation
 Refrigeration system placement
 Doors, passageways and access
 Refrigerant monitoring
 Open-flame devices
 Pressure-relief piping
 General requirements
© American Standard Inc. 1997
equipment room design …
Open-Flame Devices

 “No open flames that use combustion air from


the machinery room shall be installed where any
refrigerant is used.”
 Exceptions …
 Combustion air is ducted from outside and sealed to
prevent refrigerant leakage into the combustion chamber
 A refrigerant detector is used to shut down combustion
automatically if a refrigerant leak occurs

© American Standard Inc. 1997


Equipment Room Design

 Ventilation
 Refrigeration system placement
 Doors, passageways and access
 Refrigerant monitoring
 Open-flame devices
 Pressure-relief piping
 General requirements
© American Standard Inc. 1997
equipment room design …
Pressure-Relief Piping
(Alternate Arrangement)
Roof

 Suggested refrigerant Exterior Wall


vent piping … Support this pipe!

Flexible Steel
Connection

Purge Discharge
Vent Line

Rupture Disc
Assembly 15 Feet Above
Ground Level
Drip Leg
(Length As
Needed)

1/4” FL × 1/4” NPT


Drain Valve
© American Standard Inc. 1997
Equipment Room Design

 Ventilation
 Refrigeration system placement
 Doors, passageways and access
 Refrigerant monitoring
 Open-flame devices
 Pressure-relief piping
 General requirements
© American Standard Inc. 1997
equipment room design …
General Requirements

 Signs
 Changing, charging and storing refrigerants
 Self-contained breathing apparatus
 Two required per equipment room

 Emergency shutdown procedure


 General maintenance

© American Standard Inc. 1997


®

An American-Standard Company

Vous aimerez peut-être aussi