Académique Documents
Professionnel Documents
Culture Documents
Bus-2 Bus-1
21
Ckt-1
Ckt-2
Distance Protection
Distance Protection schemes shall have
Three independent zones Separate measurements for all Phase to Phase & Phase to ground faults. Single and three pole tripping capability. Directional characteristics for Zone-1, Zone-2 and Zone-3. Capability of operation for close up three phase and switch on to faults. Adjustable characteristic angle to match line angle.
Distance Protection
Distance Protection schemes shall have
Accuracy of better than or equal to 5% of set value for reach measurement in Zone-1 & Better than equal to 10% of set value for Zone-2 & Zone-3. Accuracy of better than or equal to 5% of set value for time measurement of Zone-2 & Zone-3. Power Swing detection feature for selective blocking, as required. Suitable fuse failure protection to monitor all types of fuse failure and block the protection.
Zone-1 : To cover 80-85% of protected line section. Zone-2 : To cover minimum 150% of length of principal line section. Zone-3 : To cover 120% of principal section plus adjacent longest section.
A 85% 150%
ZAB + 120%
Zone-1 : Instantaneous Zone-2 : 0.3 sec, 0.5 sec (For short line followed by long line) Zone-3 : 1.0 sec.
Power Swing
X Z3 Z2 Z1 Load Area Recoverable Swing
Current Phase comparison type Suitable for operation without PLCC High sensitivity for all types of faults Capable of single and three pole tripping
A B A+B No Trip
B A A+B No Trip
A B A+B Trip
B A A+B Trip
2. 3.
< 0.5 VA Yes .Hardware .Power supply .Output relays .Software .CT, PT, Ckts Yes
6.
Vibration proof
Yes
Possible through Yes, digital filtering analog filtering incorporated Not required as settings are stored in memory in digital format
9.
Frequently Required as settings drift required as settings drift due to ageing due to ageing
12. 13.
Multiple Not possible Not possible characteristics Integrated protective functions Not possible Not possible
Possible Possible
18.
No
Yes
The apparent resistance and reactance presented to the relay may be calculated as follows: R x D = (Vr1ir2 - Vr2 ir1) and XxD= where LD = (Vr2 ir - Vr1ir2 )
Single Phase and /or three Phase reclosing facilities Continuously variable single phase and three phase dead time. Continuously variable reclaim time Facility of selecting single phase / three phase / Single & three phase auto reclosure/ Non-auto reclosure modes. Facility for selecting check synchronising or dead line charging features. Sequential reclosing facility of breakers in multiple breaker arrangement.
R Y B
R Y B III
LBB Line reactor Protection Over Voltage Protection Bus Bar Protection Zone-2/3 of distance Protection Circuit breaker problem Carrier fail Receipt of Direct Trip signal.
Two stages High drop off to pick up ratio. Adjustable setting range for voltage and time. Low set stage and shall monitor any one Phase Phase voltage and shall have associated timer. High set stage shall monitor all three voltage and shall have associated timer.
59
1.1 Vn CVT
Vn
Trip connected line breaker(s) Start LBB Block auto reclose Send direct trip command
Low set stage at 110% with typical time delay of 5 seconds. High set stage at 150% with time delay of 100mSec
Transformer Protection
Transformer differential protection Restricted earth fault protection Over fluxing protection Back up directional Over current & Earth fault protection on HV side Back up directional Over current & Earth fault protection on IV side
R Y B
Transformer Protection
Buchholz relay Winding temperature Oil temperature Oil level Pressure relief Fire protection Protection of tertiary winding Over load alarm
Differential Protection
Triple pole feature with individual phase indication Unrestrained instantaneous high set O/C units which should not operate during in rush. Adjustable for multi bias setting Second harmonic or other inrush proof feature. One bias winding per phase and per CT input An adjustable operating current
Bias
3.0 Operate 2.0 Not-Operate
1.0 0.2
64
Phase to Phase connected Operating on the principle of measurement of voltage to frequency ratio. Provided with inverse time characteristics compatible with transformer over fluxing. Provided with independent alarm with a definite time delay at value of V/F between 100% to 130% of rated value. Having high reset ratio of 98% or better.
51
Single Pole feature Definite time over current feature Continuously variable current range of 50-200% of rated current and continuously variable timer setting range of 1 to 10 Secs. Drop off to Pick up ratio of 95% or better.
Reactor Protection
Differential Protection Restricted earth fault Protection Reactor Back-up protection Buchholz relay Winding temperature Oil Temperature Pressure relief Oil Level Fire Protection
Shunt Reactor
R Y B R Y B
Operating current sensitivity of atleast 10% of nominal current Tuned to system frequency Suitable non-linear resistors to limit peak voltage during in-zone faults High or low impedance principle
Operating current sensitivity of atleast 10% of nominal current Tuned to system frequency Suitable non-linear resistors to limit peak voltage during in-zone faults High or low impedance principle
Backup Protection-Reactor
Either Impedance type or definite time O/C & E/F type Impedance type reactor back up Protection shall be Triple Pole type Single step Polarised MHO or impedance distance relay Having characteristic angle between 60 80 degree. Provided with adjustable definite time delay relay Provided with suitable range for covering 60% of reactor impedance.
Ckt-1
Ckt-2
R Y B N
87 Main Zone
Check Zone 87
R Y B N
3 Phase type and operate selectively for each bus bar section Operating on differential principle and shall provide independent zones of protection for each bus. Provided with Zone indication Stable for through fault condition Provided with continuous supervision for CT secondaries.
Short operation and drop-off times Three phase current elements with facility for phase wise initiation Current setting range such that the relay can be set at minimum 200mA (for line) and 50 mA (for generator) for 1Amp CT secondary Associated timer with adjustable setting.
Shall be electronic or microprocessor based On line type Shall be suitable for CB operation of 2 cycles Built-in display(KM) 3% accuracy for all type of faults
Event Logger
To record the state of switchyard equipments and relays. To record the occurrence of alarms. To record changes in digital inputs To record switching of primary plant within sub-station.
Event Logger
Time synchronised with GPS clock Permissible drift +/- 0.5seconds/day Print out of current alarm and plant status available on request. To entry of date and time from key board. Programmability at site. Shall record 40 changes in 10mSec interval.
Disturbance Recorder
To understand behavior of the Power network before or after any disturbance. Useful info in planning of new installations. For further improvement in the equipment
Disturbance Recorder-Functions
Records instantaneous values of V, I, In and open delta voltage. Status of relay contacts and CB during disturbance. Requirement Recoding capacity-8 analog + 16 digital. Memory 5 sec Min. Pre fault 160mSec Post Fault 2sec- min , not less than 5sec.
Disturbance Recorder-Triggers
Any digital signal triggering. Analog triggering by threshold levels. Trigger selection of over/under levels should be possible. Time tagging:
Built-in real time clock. Drift of the clock shall not be more than 0.5sec per day.
Disturbance Recorder
Sync. With GPS 16Analog + 32 digital for D/C lines DR + FL If DR is part of Numerical Protection,external binary input should be possible.