Artificial Intelligence Artificial Neural Network(ANN) Transformer fault and Dissolved Gas Analysis Transformer Fault Diagnosis Artificial Intelligence (TFDAI) System TFD Expert System TFDANN Illustration Conclusion Reference
AI implemented using ANN Emulation of biological neural system Imitates information processing of brain Can teach oneself and adapt non-linear relations between input and output.
NEURAL NETWORK
Biological Artificial
BIOLOGICAL NEURON 1) Dendrites 2)Electrical impulse 3)Strength of synapse 4)Cell body 5)Axon 6)Signal of axon
ARTIFICIAL NEURON Input unit Input (p) Weight (W) Summation unit and transfer function Output unit Output (a)
TRANSFORMER FAULTS
Main faults are Arcing or high current breakdown H2, C2H2 Low energy sparking or partial discharges H2, other lower HC Hot spots or localized overheating CH4, C2H6 General overheating CO, CO2
2. Ratio Method
CH4/H2, C2H2/C2H6, C2H2/C2H4
TFD ANN
Base
KNOWLEDGE BASE
Six Modules:
Coordinator module
Coordinates and controls TFDES. Starts with chromatography, then exterior inspection followed by oil feature and insulation preventive test modules.
2.
3.
4.
5.
Characteristic Gas Method Module BP1 Three Ratios Method Module BP2 Insulation Oil Feature Test Module BP3 Exterior Inspection Module BP4 Comprehensive Analysis Module BP5
BP1 6inputs, 4outputs I/p: H2, CH4, C2H2, C2H4, C2H6, CO O/p: Normal, over heating, corona, arcing BP2 3i/p, 9 o/p I/p: C2H2/C2H4, CH4/H2, C2H4/C2H6 O/p: 1 normal and 8 Faults BP3 6 i/p, 3 o/p I/p: acidity, resistivity, water content, surface tension, dielectric loss, breakdown voltage O/p: good, alert, bad
BP4 3 i/p, 2 o/p I/p: noise, oil level, oil temperature O/p: exterior imperfection, interior imperfection BP5 From the results of BP1, BP2, BP3, BP4, makes final judgment
TFDAI
Input - transformers measured data Preliminary judgment by logical judging model Status - either normal or abnormal If abnormal, TFDES and TFDANN starts parallel Their output to Comprehensive Analysis to give final judgment
EXAMPLE
Test Data of a transformer:
H2 217.5 CH4 40 C2H6 4.9 C2H4 51.8 C2H2 67.5 CO 646.7 CO 1264
Acidity Resistivity Water content Surface tension Voltage rank Breakdown voltage Dielectric loss
From TFDES:
Transformer Interior Abnormal Nature of fault: High Energy Discharge Suggestion: stop operation immediately, make interior inspection
From TFDANN:
BP1 output: Y4=1.000, conclusion electric arc discharge BP2 output: Y4=0.998, conclusion high energy discharge BP3 output: Y1=.9895, conclusion oil can be still used BP4 output: Y1=.9385, conclusion interior abnormal
From TFDAI:
Transformer interior abnormal Nature high energy discharge Conclusion - Transformer interior winding not good Suggestion stop operation, make interior inspection On site conclusion Winding Fault
CONCLUSION
ES to imitate logical thinking of brain ANN to imitate thinking in images of brain DGA powerful tool in fault diagnosis *advantage *disadvantage o TFDAI remedy to the disadvantages o Results highly reliable, less training time, less memory consumption, 80% success levels
REFERENCES
Mu Xue-Yun, Wang Jun and Yang Qi-Ping, Li Meng-Qun. Application of AI in Power Transformer Fault Diagnosis, International Conference on Artificial Intelligence and Computational Intelligence, 2009, 7-8 Nov, p442-445 Martin T Hagan, Howard B Dcmuth and Mark Beale, Neural Network Design, chapter-2,3, page-2.1-2.23 and 3.1-3.16 Deepika Bhalla, RajKumar Bansal and Hari Om Gupta, Appication of Artificial Intelligence Techniques for Dissolced Gas Analysis of Transformers- A Review, World Academy of Science, Engineering and Technology 62 2010. Methods and applications of Artificial Intelligence: vol3, pg 421-424, George A Vouros K V Satyanarayana, C H Charkradhar Reddy, T P Govindan, Manoj Mandlik and T S Ramu, Application of Artificial Intelligence for the assessment of the Status of Power Transformers, Indian Institute of Science, Downloaded on March 9, 2010 from IEEE Xplore. Jessey G Smith, B Venkba Rao, Vivek Diwanji and Shivaram Kamat, Fault Diagnosis- Isolation of Malfunctions in Power Transformers, june 10, 2009, Tata Consultancy Sevices. Copyright 2009 Tata Consultancy Services.