Académique Documents
Professionnel Documents
Culture Documents
=
T
R In Pcu =
2
3
Un
S
In
rT
=
3
upstream
k
Z
Un c
I Isc
= =
3
05 , 1
max
max 3
Division - Name - Date - Language 25
Circuit description
Generators
Power (kVA) : see previous
Earthing arrangement : see previous
Distributed neutral : see previous
Un Ph-Ph : see previous
Power factor : see previous.
System frequency : see previous
Xo : Zero phase impedance
X : Transient impedance, used to calculate the short circuit current
Division - Name - Date - Language 26
Circuit description
Source
Un Ph-Ph : see previous
Isc max (kA) : maximum short circuit current (Ik3max) at the point of the LV
connection from which the study will start.
Power factor : see previous.
System frequency : see previous
Energy supplier : Private substation is the only value.
Distributed neutral : see previous
I service connection (A) : Intensity of the connection, in other words the current
rating of the upstream protection device (not drawn on the diagram).
Division - Name - Date - Language 27
Circuit description
Source (2)
Isc min upstream (kA) : value of the Ik1min short circuit at the point of
connection. This value is used to calculate the warm impedance of the
Phase/Neutral loop.
Earthing arrangement : see previous.
dU initial (%) : The voltage drop from the transformer to the LV connection from
which the study starts. This used to calculate the cumulative voltage drop
downstream of the LV connection.
Division - Name - Date - Language 28
Circuit description
Capacitor
Power factor before compensation : value of the power factor calculated in the
Power Sum (the Power Sum must be run to calculate a Capacitor bank)
Power of the Harmonic sources : In order to take into account the effect of
harmonics on the capacitors, Ecodial needs the power of all the harmonic
generating (non-linear) loads on the network. This value is used in conjunction with
the transformer size to identify the type (Standard, H or SAH) of capacitor used by
Ecodial.
Power (kvar) : Total power of the capacitor bank needed to attain the target power
factor.
Type of compensation
Step : resolution of the automatic capacitor bank : ex 5x50kvar means the
capacitor bank can go from 0 to 250kvar in steps of 50 kvar (controlled by the
regulator)
Ib : current drawn by the capacitor bank (inclusive of possible harmonic currents
and manufacturing tolerances)
Division - Name - Date - Language 29
Circuit description
Capacitor
Ih
L,e
C,e
Transformer
(P
T
)
Capacitor
(Q)
Harmonic current
injection
Equivalent impedance of L-C circuit (resistances ignored)
Z= j.L.e / (1-L.C.e)
Resonance when e=(2.t.f)=1/LC (Zmax induces to Voltage max)
order of resonance :
if order of resonance is close to harmonic current injection, filtering devices
could be required.
Harmonic voltage created across the equivalent impedance of the transformer and
capacitor, which causes circulating currents in the L-C loop, which can be a cause
of nuisance tripping in transformer or capacitor protection devices.
c
T
Q ucc
P
n
=
(%)
Circuit description
Capacitor
Circuit description
Capacitor
Vh
Division - Name - Date - Language 30
Circuit description
Circuit breaker (distribution)
Range : Product range from which the circuit breaker is to be chosen. If Ecodial
cannot find a breaker in that range it will look for a breaker in a predefined range
(function of the demand current)
Designation : name of circuit breaker
Trip unit / curve : name of the trip unit or curve of the circuit breaker
Nb of poles protected : polarity of the circuit breaker that is required.
Earth leakage protection : if earth leakage protection (RCD) is required (by user,
or for a particular application, switch this characteristic to YES).
Fire protection : this is a characteristic that will force an earth leakage device, and
set it to ensure that a leakage current will not be able to cause a fire (threshold <
300mA)
Integrated with the protection device : certain RCDs are integrated (NS Vigi,
) and certain are separated (RH***). The user can choose the type of RCD
required. By default, Ecodial looks for integrated RCDs, and then separated
RCDs if unsuccessful.
Class : (A / AC ) defines the sensitivity of the RCD to continuous and pulsed
DC signals.
Earth leakage protection device : name of the device ensuring the function of
RCD.
Division - Name - Date - Language 31
Sensitivity (mA) : pickup current of the RCD device
Delay (ms) : time delay before disconnection under earth fault conditions
I thermal setting (A) : Thermal setting of the circuit breaker. This value is set to be
greater or equal to the demand current, and is used to size the cable.
I magnetic setting (A) : magnetic setting of the circuit breaker. This setting s made
to ensure protection against indirect contact in TN, and to ensure correct motor
starting based on start-up currents.
Frame rating (A) : maximum rating of the circuit breaker frame
Trip unit rating (A) : maximum setting of the trip unit.
Ir : position of the thermal adjustment on the trip unit
Io : position of the thermal adjustment on the trip unit
Im/Isd : position of the magnetic adjustment on the trip unit
Motor mechanism : breakers must be able to be fixed with a motor mechanism
Circuit description
Circuit breaker (distribution) (2)
Division - Name - Date - Language 32
Cascading requested :
YES : circuit breaker is chosen using cascading with the upstream device (only
the device directly upstream)
NO : circuit breaker is chosen based on its stand-alone breaking capacity.
Discrimination requested :
YES : circuit breakers that have better discrimination potential are selected
instead of normal circuit breakers
Installation : Fixed breakers or withdrawable breakers
Circuit description
Circuit breaker (distribution) (3)
Division - Name - Date - Language 33
Circuit description
Circuit breaker (motor)
Range : see previous
Designation : see previous
Trip unit / curve : see previous
Contactor : name of contactor to be used according to the co-ordination tables
Thermal protection : name of thermal overload (if needed) according to co-
ordination tables.
Soft starter : name of soft starter (if needed) according to co-ordination tables.
Earth leakage protection : see previous.
Fire protection :see previous with the added safety that the tripping time is
delayed by at least 60ms to ensure there is no nuisance tripping on start-up.
Number of poles protected : always 3P3T, as Ecodial does not cover single
phase motors
I thermal setting (A) : Thermal setting of the circuit breaker. This value is set to be
greater or equal to the demand current, and is used to size the cable.
I magnetic setting (A) : magnetic setting of the circuit breaker. This setting s made
to ensure protection against indirect contact in TN, and to ensure correct motor
starting based on start-up currents.
Division - Name - Date - Language 34
Frame rating (A) : maximum rating of the circuit breaker frame
Trip unit rating (A) : maximum setting of the trip unit.
Ir : position of the thermal adjustment on the trip unit
Io : position of the thermal adjustment on the trip unit
Im/Isd : position of the magnetic adjustment on the trip unit
Motor mechanism : breakers must be able to be fixed with a motor mechanism
Cascading requested :
YES : circuit breaker is chosen using cascading with the upstream device (only
the device directly upstream)
NO : circuit breaker is chosen based on its stand-alone breaking capacity.
Discrimination requested :
YES : circuit breakers that have better discrimination potential are selected
instead of normal circuit breakers
Installation : Fixed breakers or withdrawable breakers
Circuit description
Circuit breaker (motor) (2)
Division - Name - Date - Language 35
Circuit description
Load
Number of identical circuits : instead of drawing multiple feeders having
EXACTLY the same characteristic, just draw one !
Ib : demand current of the load (calculated from the power and polarity)
Circuit polarity : polarity of the load
Earthing arrangement : see previous
Power (kVA) : demand power (calculated from the current and the polarity)
Power factor : power factor of the load (.8 is default value)
Fixed / Mobile :
Fixed : permanent connection from installation to load.
Mobile : terminal load is fed through a power socket (special earth leakage
conditions are then applicable : 30mA and Instanataneous protection is
required)
Division - Name - Date - Language 36
Circuit description
Motor
Number of identical circuits : see previous
Mechanical power (kW) : rated mechanical power of motor
Type of starting : for Direct on Line or Soft Starting applications
Motor efficiency : ratio between mechanical and electrical power (in kW)
Ib (A) : full load current of motor
Power factor : full load power factor of the motor
Circuit polarity (always 3P)
Earthing arrangement : see previous
Power (kW) : demand power (calculated from the efficiency)
Type of co-ordination : Type 1 or Type 2
Starting class : Standard / Long
Start-up current : sets the magnetic setting of the breaker
Division - Name - Date - Language 37
Circuit description
Lighting
Number of identical circuits
Lighting Source : type of lamp
Individual lamp power :
Number of lamps per light : for each lighting point there can be several lamps
Nb of lights (A) : total number of lamps on the Canalis lighting line
Ib : full load current at the origin of the Canalis lighting distribution
Ballast power : for lamps using ballasts (fluo tubes, )
Circuit polarity
Earthing arrangement
Power (kW) : total demand power (calculated)
Power factor
Division - Name - Date - Language 38
Circuit description
Variable Speed Drive
Reference : name of VSD
Nominal power of the VSD (kW) : characteristic of VSD
Ib : current drawn by VSD (including harmonics)
Absorbed power : total power drawn by VSD (motor power and heat loss)
Torque (A) : starting torque : High or standard
Form factor : ratio between total RMS and 50Hz signal (characteristic of VSD)
Is permanent : output current
Is max permanent : maximum permanent output current (characteristic of VSD)
Is max 60s : maximum 60s output current (characteristic of VSD)
Earthing arrangement
Circuit polarity
Division - Name - Date - Language 39
Circuit description
Cable
Length : length of the cable (Short circuit and voltage drop calculations)
Installation method : code for the type of installation. Defines the standard
derating factors and the type of conductors used.
Insulation : sets the insulation material of the cable (impedance calculation)
Type of conductor : output from the Installation method, not an input !
Neutral loaded : source of derating on 3P+N networks
Conductor arrangement : calculation of the linear reactance of the cable
Type of PE : influences the type of cables selected by Ecodial
Number of additional circuits : cable derating
Number of layers : cable derating
K user : additional cable derating (over and above the standards)
Ambient temperature : cable derating
Delta U max on circuit (%) : maximum voltage drop allowed on the cable
Reference : name of cable
Division - Name - Date - Language 40
Circuit description
Cable (2)
Nb Ph conductor : calculation result
CSA Ph conductor : calculation result
Nb N conductor : calculation result
CSA N conductor : calculation result
Nb PE conductor : calculation result
CSA PE conductor : calculation result
Phase metal : cable characteristic (input)
Neutral metal : cable characteristic (input)
PE metal : cable characteristic (input)
Safety voltage : 50V or 25V
Division - Name - Date - Language 41
Ecodial and the earthing schemes
Implementing protection against indirect contact
TT
Earth fault current (leakage) calculated using the impedance of the source and
earth electrodes, and the Phase-Earth conductor impedance
Standards require an RCD device on the main incomer
the earth and source electrodes must not be interconnected !
TN
Earth fault current calculated using the Phase-Earth conductor impedance
Protection against indirect contact insured by setting the magnetic under the
Earth fault current
Trip units can be changed to ensure accurate magnetic threshold is used
RCDs can be implemented
IT (2nd fault)
identical calculations as for the TN system
Earth fault current is calculated assuming both fault occur at the same point.
This ensures worse case scenario as if the second fault appears further away,
the real fault current on the 2nd fault would be greater than the calculated fault
current corresponding to the 2nd fault location, and ensuring tripping by the
2nd fault location protection device.
Division - Name - Date - Language 42
Calculation rules
Phase CSA
a
m
Irth
K
Sth
1
1
|
.
|
\
|
=
Theoretical Phase CSA : calculated by a formula, where (IEC 60364-5-523-B):
K is the total derating (temperature laying method, cables in parallel, )
Irth : is the thermal setting of the upstream breaker
m and a : parameters defined by the laying method and the type of cable
(metal, insulator) andthe number of loaded conductors in the circuit)
Choice of Phase conductor
based on cable database supplied
based on theoretical phase CSA and tolerance
based on installation rules (ex TNC Smini = 10mm)
based on limits implied in the standards (ex Smini for multicore conductors on
perforated tray = 25mm)
based on maximum phase CSA allowed
Voltage drop is calculated on this cable using demand current
CSA could be increased
Division - Name - Date - Language 43
Calculation rules
Neutral CSA
Theoretical calculation made by Ecodial
minimum theoretical CSA equal Ph or Ph/2
Warning : the Neutral as any cable should be sized according to the upstream
protection setting (this is to ensure safety, not continuity !).
With 4p4t CB, the neutral can be of the same CSA of the Phase
With 4p3t 1/2N, the neutral can be half
With 3p devices (Neutral not protected), there is an unknown, as there is no
direct protection on the neutral
Phase unbalance can lead (worse case scenario) to a phase current equal to
neutral current, so Neutral should be at least equal to Phase
Triplen Harmonics (3rd, 9th, ) add up on the neutral. Therefore, if the phase is
ONLY 3rd harmonics, neutral current = 3x phase current. In reality, the neutral
current will usually be less than 1.7-1.8 times the phase current, example ;
Irms (phase) = (I1, I3 (80%), I5(45%), I7(12%)) = 1.36x I1
Irms (neutral) = 3x I3 = 2.4x I1 = 1.76 Irms (phase)
Division - Name - Date - Language 44
Calculation rules
Neutral CSA
Recommended actions :
use half neutrals
when there is a 4p3t N/2 circuit breaker protecting the circuit,
and if there is no possibility of excessive phase unbalance and/or triplen
harmonic loading on the circuit.
Note : 3p3t are acceptable solutions, but 4p3t N/2 offer more safety
under unexpected conditions
use full neutrals
when there is a 4p4t circuit breaker protecting the circuit
and if there is a possibility of excessive phase unbalance, or limited
triplen harmonic (max allowed = 33% triplen in the RMS)
Note : 3p3t are acceptable solutions, but 4p4t offer more safety under
unexpected conditions
use double neutrals
with 3p3t circuit breakers
when there is a high risk of excessive triplen harmonic
Division - Name - Date - Language 45
Calculation rules
PE CSA
Automatic minimum PE :
if Ph s 16mm, PE = Ph x kph/kpe
if Ph s 35 mm, PE = 16mm x kph/kpe
if Ph > 35 mm, PE = Ph/2 x kph/kpe
where kph and kpe function of the type of phase and earth conductor (metal,
insulation, single/multi core, )
in TT, max PE = 35mm
Theoretical minimum PE : the theoretical minimum PE cross section should only
verify the It < kS condition, as no current is ever expected to flow on the PE (as
it is an equipotential link). This condition usually implies small PE cross sections
(+/- 4mm in TN and 1mm in TT). Using such small cables has two bad
consequences :
reducing Earth fault current (due to higher impedance), which could require the
use of earth fault protection devices or lowering the magnetic thresholds to
non efficient levels (motor starting and discrimination problems)
creating a higher voltage differential on the PE due to natural leakage currents
Ecodial chooses automatically the CSA given above, but allows smaller
cables to be selected by the user.
Division - Name - Date - Language 46
Network
General characteristics
TNC
400V
Transformer
800kVA transformer
Incomer cable length = 0
Load
3P+N
100A
Installation method EJ(1)
Calculate the network with :
Load cable length =30m, 100m, 140m, 170m
Info needed : Irm, If, Sph, Spe, DeltaU, CB, Sizing criteria
Tableau
B2
T1
C1
Circuit
Q1
Q3
Circuit
C3
L3
Calculation examples
the effect of long cables
Division - Name - Date - Language 47
Calculation examples
the effect of long cables
Cable sized on load current
Cable sized on voltage drop
Setting of trip unit to cater for low earth fault current
(protection against indirect contact)
To ensure disconnection in sufficient time, Ecodial verifies that the earth fault
current is higher than the magnetic setting of the breaker (including tolerance).
Trip units can be changed to ensure this :
C curve to B curve
TM to STR
cable size can be increased
If no solution is found Ecodial interrupts the calculation requesting the user to
manually place an RCD on the circuit breaker to ensure disconnection, and
therefore protection against indirect contact.
Division - Name - Date - Language 48
Non-uniformly distributed load
the Icc and DeltaU can be calculated at each tap-off point, or for worst case
scenario (Icc at source)
Calculation method to be used for distribution systems having loads that vary
substantially in power and location.
Uniformly distributed load
the Icc is calculated at the beginning of BTS.
The voltage drop is estimated as a function of the number of tap-offs
Calculation adapted for distribution systems having evenly distributed loads (in
power and location)
Calculation examples
Prefabricated busbar trunking
Division - Name - Date - Language 49
Uniformly and Non-uniformly distributed load.
800kVA
100A tapoffs
D=5,10,15,20,25
Total length 30m
Info needed :
Icc, deltaU per tap/off.
B2
Tableau
D4
CEP
Q8
Circuit
C8
L8 L9
C9
Circuit
Q9
Q7
Circuit
C7
L7 L6
C6
Circuit
Q6
Q5
Circuit
C5
L5
Q3
Circuit
C3
Q1
Circuit
C1
T1
Calculation examples
Prefabricated busbar trunking (2)
Division - Name - Date - Language 50
Ku : usage coefficient
applicable to a CIRCUIT
% full load current when load is running
example :
motor +/- 80%
Light 100%
Ks : diversity coefficient
applicable to a DISTRIBUTION BOARD
chance of all feeders drawing maximum load at any given time
relative to the number of feeders on DB.
See Electrical Installation Guide
Calculation parameters
Diversity and usage coefficients
Division - Name - Date - Language 51
Lathe 1 5.5 kW
Lathe 2 5.5 kW
Distribution box Lathe 3 5.5 kW
Lathe 4 5.5 kW
Workshop A Drill 1 2.2 kW
Drill 2 2.2 kW
3x socket outlet circuit (1P+N) 20 A each
6x lighting lines (1P+N) 10x 100W each
Compressor 15 kW
Incomer Workshop B 5x socket outlet circuit (1P+N) 20 A each
4x lighting lines (1P+N) 4x 100W each
Ventilation Fan 1 2.2 kW
Distribution box Ventilation Fan 2 2.2 kW
Oven 1 15 kW
Workshop C Oven 2 15 kW
10x socket outlet circuit (1P+N) 20 A each
2x lighting lines (1P+N) 2x 100W each
Calculation parameters
Diversity and usage coefficients - example
Division - Name - Date - Language 52
Apartment blocks :
Consumers 4 9 14 19 24 29 34 39 49
Ks 1 .78 .63 .53 .49 .46 .44 .42 .41
Distribution Boards (IEC439) :
Circuits 3 5 9 10+
Ks .9 .8 .7 .6
Circuits (Ks or Ku ?):
Lighting 1
Heating, air conditioning 1
Socket outlet circuit .1 to .2 (higher in industry)
Lifts/hoists 1 / .75 / .6
Calculation parameters
Diversity and usage coefficients - example
Division - Name - Date - Language 53
Problem with Ku and Ks
Responsibility of the user
Personal experience
Knowledge of installation
Database of existing installations
Advantage of Ku and Ks
more cost effective installation
not oversized
Example
total installed power : 144kVA
maximum expected demand : 80 kVA
Calculation parameters
Diversity and usage coefficients - example
Division - Name - Date - Language 54
The algorithms used by Ecodial
Formulas, constants
impedance
Icc, voltage drop, ..
Reference to standards
Calculation guides
Special help file
Division - Name - Date - Language 55
Different types of information :
The front page
Header and footer
The device lists
Equipment display
Calculation notes
The single-line diagram
Printing :
Customise the setup
Choice of language
Output
Division - Name - Date - Language 56
Open and save a project
How to make a link between projects ?
Choice of interface language
The summary
Different kinds of exports :
DXF
RTF
ECD
Special
Division - Name - Date - Language 57
Circuit breaker and busbar selection
Discrimation and cascading tables
Tripping curves
Guides and tools
Division - Name - Date - Language 58
Maximum number of circuits in a project : 70
Maximum number of copied circuits : 20
Maximum number of transformers : 4
Limitations
Division - Name - Date - Language 59
Normal and emergency sources
Ecodial uses the worst case scenario to select equipment :
max short circuit level from Transformers
min earth fault current from Generators
Complex networks
It is not always possible to draw the exact network. It can be necessary to
draw a simplified network, and define the final network based on these
calculations.
Special applications