TURBINE SYSTEM
The power unit is installed with a -1000-50/3000-2 high-speed condensing turbine Operating on saturated steam, With non-controlled steam bleeds, With moisture separation and single-stage steam reheating, With a rotational speed of 3000 rpm.
TURBINE SYSTEMS
The Turbine Systems consists of: A single double flow HP Turbine (HPC) A single stage combined Seperator and Reheator Three LP Turbines (LPC) Three Condensers Regenerative Feed Heating System
MOIST. SEPRTR
REHEATER
HP TURBINE
LP TURBINE 1
LP TURBINE 2
LP TURBINE 3
DEMINZR
LPH 1
TURBINE SYSTEMS
Shaft Lubricating oil System Shaft Turning Gear System Turbine Governing System C & I Systems for control and monitoring the Turbo-Generator
GENERATOR SYSTEMS
The Generator Systems consist of a single a TVV-1000-2/24 alternator with Stator Water Cooling System Rotor Hydrogen Cooling System Shaft Sealing System Generator Excitation System Generator control System C & I Systems Power evacuation System
Arul Kumaran Kothandapani
TURBINE SYSTEM
The steam from the Four steam generators is supplied via Main Steam Isolating Valve (MSIV) and a Main Isolating Valve (MOV) to the HPC.The function of the MSIV AND MOV are To Isolate the SG in case of tube leaks To Isolate the SG in case of steam line rupture to prevent fast cooling of the reactor
To atmosphere
To atmosphere
BRU-A
MSIV
BRU-A
TO HP TURBINE
TURBINE SYSTEM
The steam then passes through the four Stop valve and Throttle Governing valve units on each steam line and enters the HPC.
TURBINE SYSTEM
After the HPC the steam goes through four steam lines (two lines per each exhaust from the HPC) to the steam separator-reheater for separation and intermediate reheating, both are single-staged. On passing separation and reheating, the steam goes, through the LP valve units, to the LPCs. From the LPC the steam is discharged into three condensers. The condensers are basement-type, transverse, with titanium tubes.
Arul Kumaran Kothandapani
The basic regeneration scheme is 4LPH+D+2HPH. The low-pressure heater LPH-1 is a surface type, horizontal, built in the condenser. The LPH-2 is of mixing type. LPH-3 and LPH-4 are of surface type. The HPHs are vertical and chamber-type. The tubing is made of stainless steel. Each housing of the HPH has an in-built drain cooler.
REHEATER
HP TURBINE
LP TURBINE 1
LP TURBIN
COND
TEAM GENERATOR
DEAERATOR
LCV
LPH 2
TURBINE SYSTEM
The condensers steam receivers, which are equipped with receive steam from the steam generators dumped into the condenser through the Steam Dump Valves (BRU-K).Also, the excess steam can be relieved to the atmosphere through Steam Discharge Valves (BRU- A) and by Safety Relief Valves. The Safety Relief Valves are Instrumented relief valves called Pulse Safety Devices (PSD)
Arul Kumaran Kothandapani
To atmosphere
To atmosphere
BRU-A
MSIV
BRU-A
TO HP TURBINE
TURBINE SYSTEMS
WE NOW PROCEED TO DESCRIBE THE FUNCTIONAL DETAILS OF THE VARIOUS SYSTEMS.
The turbine bypassing system is intended for: Steam dump from the steam generators to the turbine condensers via fast-acting steam dump valves with discharge to the turbine condensers (BRU-K) during load through-off for prevention of an excessive pressure rise in the steam generators to exclude actuation of the Safety Valves and Atmospheric Dump Valves (BRU-A);
Steam removal from the steam generators in the unit startup and shutdown modes; Pressure regulation in the secondary circuit; Maintenance of the reactor thermal power at the specified level with a change in the turbines electrical load.
Steam dumping to the turbine condensers or to atmosphere in case of load through-off of the power unit load and in case of scheduled or emergency cooling down;
Protection of the steam generators and steam lines against excessive pressure rise; Live steam supply to the auxiliary header (when steam supply from extraction line of turbine is not available);
Live steam supply to the deaerator (when steam supply from extraction line of turbine is not available); Live steam supply to the MSR in the steam reheating system and moisture removal upstream of the turbine low-pressure cylinders (LPC); Isolation of steam generators by fast acting isolation valves in emergency situations
The main cooling water system is intended for condensation of steam and removal of heat from condensers of the turbine. The components to ensure performing of the system functions are the main cooling water pump units.
Turbine condensate demineralizing system (LDF) is a system for maintaining secondary circuit water-chemistry regime (WCR) and to minimise deposits on steam generators (SG) heat exchanging surface, in turbines flow part and in condensate-feeding line. This is to prevent SG, secondary circuit equipments and pipelines structure materials corrosion and corrosion-erosion damage;
Arul Kumaran Kothandapani
To provide condensate flow in recirculation line needed for normal operation of the condensate pumps of both stages when the turbine is running at no load and at low load. The system consists of I-st stage condensate pumps II-nd stage condensate pumps
Prevention of feed water supply to a damaged steam generator in case of the SG steam line rupture in the non disconnectable section, feed line rupture or leakage from the primary circuit to the secondary circuit; Deaeration and regenerative heating of turbine condensate in the deaerator to provide the design rates of oxygen content in feed water (10 g/kg at most), and also accumulation of hot water in the deaerator;
Arul Kumaran Kothandapani
Power unit cooling down in case of failure of auxiliary feed water pump, as well as for quick cooling of the steam generators by standby electric pump; Averaging of feed water parameters downstream of the high-pressure reheater (HPH) groups.
The LAB system consists of two basic turbine feed pumps (2 50 % capacity) and two stand-by electric feed pumps (2 25 % capacity) which pump feedwater from the Deaerator to the Steam Generators through the HP Heaters.
MOIST. SEPRTR
REHEATER
HP TURBINE
LP TURBINE 1
LP TURBINE 2
LP TURBINE 3
DEMINZR
LPH 1
The auxiliary feedwater system is designed: To provide steam generators with feedwater in the modes of startup, shutdown in the state of hot standby as well as cooldown;
To provide steam generators with feedwater in case of failures accompained by the limitations in water supply from the system of the main feedwater pumps;
To supply feedwater through the deaerator of the secondary circuit for deaeration of feed water prior to filling of steam generators; To provide the after-cooling of steam generators in the water-water mode when the reactor is shut down for repair.
To receive normal make-up water; To deaerate condensate and make-up water primarily;
To evacuate noncondensable gases; To collect drains and noncondensable gases from the regenerative system and other sources;
To receive steam from the turbine bypass system (MAN); To control level of condensate in the hotwells in order to ensure steady operation of the condensate pumps under steady and transient conditions.
The system for steam generators blowdown is designed for the SG blowdown and supply of blowdown water for purification (LCQ50-80) with the aim to keep required water chemistry of secondary circuit. It is also used for chemical flushing and decontamination of the steam generators.
Changing rotational speed by commands of an automatic synchronizer and keeping of rotational speed in the process of synchronization. Keeping the given turbine output; Creation of loading rate given by an operator in case of scheduled change of load;
Keeping the given live steam pressure; Turbine change over to station service load keeping rated rotational speed after load drop; Switching of controllers (load, live steam pressure) depending on operating conditions of the power unit and in interaction with reactor controller;
Analysis of temperature stresses in critical parts of turbine structure; Keeping the rated rotational speed of the turbine.
The Turbine sealing system is intended as follows: To prevent steam leakage from the turbine valve stems. To remove steam-air mixture and to supply it to the gland steam condenser (GSC).
Sealing of the turbine flow path to prevent steam leakage into the machine hall through the clearances of the turbine cylinder shaft end glands as well as the ingress of air into the casings when there is vacuum inside them.