1) 2) 3) 4)
Major blackout around the globe Voltage Instability/collapse Facts devices Modal analysis a) Matrix Equations 5) Case study a) IEEE 14 Bus Power System b) Flowchart 6) Proposed method of prevention 7) Comparison with earlier installation
Voltage Stability
The voltage stability of a power system refers to its ability to properly maintain steady, acceptable voltage levels at all buses in the network at all times, even after being subjected to a disturbance. Instability is caused due to insufficient supply of increased demand in reactive power Voltage collapse can be initiated due to small changes of system conditions as well as large disturbances
FACTS Devices 1) The term FACTS refers to alternating current transmission systems incorporating power electronic-based and other static controllers to enhance controllability and increase power transfer capability 2) Used in parallel with electro-mechanical devices 3) Effective response in operation, frequent variation in output and smoothly adjustable output 4) Various functions are : a) Voltage control c) Transient Stability e) Active and Reactive Power Flow Control 5) Commonly used FACTS devices are: SVC BESS STATCOM TCSC SMES SSSC b) Short Circuit Current Limiting
d) Dynamic Stability
UPFC
5
IPC
Modal analysis Most effective static method which involves computation of critical eigenvalue of the reduced power system steady state Jacobian matrix and the associated participation factors Shows how close the current operating point of power system is to the voltage collapse point At each operating point P was kept constant and evaluate voltage stability by considering the incremental relationship between Q and V The linearized steady state system power voltage equations are given by.
v = hV = the vector of modal voltage variations q= hQ = vector of modal reactive power variations
7 Gaurav Agarwal, VIII Sem. EE
where ki and hik are kth element of the right and left eigenvectors corresponding to ith eigenvalue of JR In the proposed method, for each contingency a probabilistic index is defined which evaluates the relative participation of each bus in voltage instability caused by all of the critical eigenvalues corresponding to that contingency
PCMi = contribution of bus i to voltage instability caused by critical modes under kth contingency state Poutage = likelihood of kth contingency occurring corresponding to outage of line k m = number of critical eigenvalues in kth contingency Pij = participation factor of bus i to critical eigenvalue j j = critical eigenvalue j the total participation in all critical modes (TPCM) for each bus
the larger the magnitude of bus participation factor in critical modes, that bus is more effective in voltage instability. the smaller the magnitude of positive j, that mode is more critical
10
11
12
Assumption taken: 1. critical=1 2. The smallest eigen value of the reduced Jacobian matrix is determined as min= 2.7 3. The failure probability of all lines is assumed to be 0.02 4. The load and generation of the system is scaled by the factor of 0.95
13
Table 2- The smallest eigen value associated with contingency after installation of STATCOM at Bus 12 Table 1- smallest eigen values for the three different contingencies
14
Table 5- The smallest eigen value associated with contingency after installation of STATCOM at Bus 7
Comparison of proposed method from earlier installation In earlier proposed methods, the optimal allocations are 0.19pu at bus 10 0.25pu at bus 13 0.25pu at bus 14 for the outage of line 1.
On the other hand are The optimal FACTS devices allocations obtained by the proposed method 0.2pu at bus 7 0.11pu at bus 12. The number of STATCOMs to be installed is decreased as well as their reactive power capacity. The reason- the allocated FACTS devices proposed earlier are applied only in one area of the network which causes a non-uniform reactive power supply in the network.
16
The method proposed here allocates FACTS devices in two separated areas of the network. Gaurav Agarwal, VIII Sem. EE Consequently, it will be effective in more contingency conditions correspond