Individual testing of each protective device and stop/control valve

assembly.
Automatic functional PRE-TESTING of substitute circuit which protect the turbine during ATT. Monitoring off all programme steps for execution within a pre-defined time. Interruption of the testing programme if the running time of any programme step is exceeded or if the turbine trip is initiated. Automatic resetting of the test programme after a fault.

Full protection of the turbine during testing is ensured by special test safety
devices.

AUTOMATIC TURBINE TESTING

PROTECTIVE DEVICES Remote trip solenoid-1 Remote trip solenoid-2 Over speed trip device Thrust bearing trip device Low vacuum trip device

MAIN STOP/CONTROL VALVE HP stop/control valve-1 HP stop/control valve-2


HP stop/control valve-3 HP stop/control valve-4

IP stop/control valve-1 IP stop/control valve-2


IP stop/control valve-3 IP stop/control valve-4

ATT SAFETY DEVICES TEST START PRE-TEST


Energise the test solenoids Control oil pr adequate De-energise the test solenoids Control oil pr zero

FAULT

HYDRAULIC TEST CKT ON FAULT


Test solenoid on Change over valve in test position Oil pressure in trip oil header O.K

MAIN TEST ON FAULT


Test ckt on Selected protective Device Operated Turbine trip gear operated Turbine protection operated

RESET
Test ckt OFF Reset solenoid energise Trip gear & protective device reset Change over valve in operating position Test solenoid de-energise

TEST ENDS

AUX TRIP FLUID

CONTROL FLUID

AUX START-UP FLUID

TEST OIL

TEST OIL

DRAIN

CONTROL OIL

HTT

CONDENSER

ATMOSHPHERE

ATT SV & CV TEST START RELEASE


EHG in service One set of SV & CV selected CV opening < 60 %

MAIN TEST ON
Positioner motor ON Control valve closed Test solenoid ON Trip oil to SV drains SV closed

RESET
Reset solenoid ON SV spring reset Test solenoid OFF SV opens Positioner motor reverse Control valve opens

TEST ENDS