EHTC
BHEL
Lb + Ipb
LOCAL BUS
LOCAL BUS
EHTC
BHEL
Lb config.
CONFIGURATION OF LOCAL STATION
KA
Channel -A Channel - B
KA
24 V DC 1 2
Power supply Distribution & monitoring Local bus / Intra - Plant bus coupler Local bus Local bus / Intra - Plant bus coupler Bus traffic director Bus traffic director Processor Module Processor Module
Binary Input
Analog Input
Binary Output
Analog Output
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
ASAAA
ASAAA can be inserted into any procontrol p 13 local bus. Receives only supply (24v) from bus, inputs and outputs are hard wired. FUNCTIONS : M-OUT-OF-3 Votting logic: V/I converter isolated (4 20 ma ). Alarm annunciation. Power supply and power supply monitoring. M- OUT OF 3 votting logic : during normal operation middle value input signal is transmitted directly to the output of module (voltage signal at pin 35). - Operation is normal as long as two extreme value input signals do not exceeds adjustable tolerance w.r.t output signal . Tolerance range is set by means of pot p1 and can be measured at jack A1 and A2. IN THE EVENT OF FAULT there are three possible modes of behavior, depending on how pin 17 is connected.
EHTC
BHEL
ASAAA 1. PIN 17 UNCONNECTED Middle value input signal is transmitted directly to the output even if second fault occurs. 2. PIN 17 CONNECTED TO PIN 41 (-15V) MIN of two unperturbed input signals is transmitted to output. In the event of second fault MIN configuration formed as a result of 1st fault is maintained. 3. PIN 17 CONNECTED TO PIN 37 (+15V) MAX of two unperturbed input signals is transmitted to output. In the event of second fault, MAX configuration formed as a result of 1st fault is maintained. On elimination of faults the circuit automatically returns to its normal configuration. However the fault alarms must be cancelled by pressing push button S1 (pin 21).
EHTC
BHEL
ASAAA Channels can be switched externally by connecting +24v at pin 81,83,85 (ch3,ch2,ch1) resp. individual channel faults are indicated by LED L2, L3,L4 . Group alarm is given by short circuiting jack A3-B3 on front plate of module. V I CONVERTER :- selected output voltage signal is converted to an electrically isolated 4- 20ma current output signal & made available at pin 25 w.r.t pin 39. Insertion monitoring (75,77 pin ) is available for supervision of missing module. INPUT :- +- 10 V At PIN 15, 13, 69 OUTPUT:- +- 10 V voltage 4 - 20 ma current.
EHTC
BHEL
EHTC
BHEL
ASABA
Channels can be switched externally by connecting +24 at PIN 81, 83, 85 ( CH3, CH2, & CH1 resp) & outputs are available at PIN 93, 91 and 87 respectively.
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
ARSAA
SME2 is high when One or more power supply are missing or out of tolerance. Other faults are presents within the module. Information word is not received in cyclic sequence. Information word is incorrect. D0 dist bit is present (logic1). Address word is incorrect V/I converter : Converts output of PI elements (0. +10v) available at pin 17 into 4 20 ma. with isolation measured at pin 25 w.r t pin 39. insertion monitoring is provided. Amplifier : - ( optionally usable ) Two inverting inputs pin 41,29 One non inverting input pin 27 Output at pin 35
EHTC
BHEL
ARSAA
Interface to p13:- module receives data from p13 local bus under the address set at the module. Inputs:Hardwired reference input at pin 87 ( 0 - + 10v ) Actual input at pin 33 Compensating input at pin 31 Actual value at pin 15 (0. +- 10v ) PI controller output :- voltage out put pin 17 ( 0- +10v) current output pin 25 wrt 39 (4 20ma) PD controller output : pin 37
EHTC
BHEL
EHTC
BHEL
AKCAA
APPLICATION: Provide power supply to M/S Collins transmitter .It matches transmitter signal to the position controller. Module is compatible with P13 local bus. FUNCTION: Power supply for Collins transmitter Matching V/I conv. With isolator ( 4-20 ma ) Interface P13 LB. P.S & P.S monitoring. POWER SUPPLY FOR COLLINS TRANSMITTER: Power supply is formed from SMPS using flydback converter(P28). Regulated 24v dc is available at pin 81 (+) & pin 83 ( Gnd).
EHTC
BHEL
AKCAA
MATCHING: Floating signal from the Collins transmitter is matched. V/I CONVERTER: Converts matched signal at pin 73 (0+10v) into 4-20 ma with isolation . This is measured at pin 25 w.r.t 39. INTERFACE TO P13 LB: Module transmits the matched signal available to local bus in the form of telegram. Regulated P.S to Collins transmitter =24 volts dc Position I/P from Collins transmitter =0.10v Matched O/P is provided into LB & hardwired o/p 4-20 ma.
EHTC
BHEL
EHTC
BHEL
APPLICATION: Used for turbine speed measurement. FEATURES: * Decoupled p.s to pulse generator * conditioning of pulse generator signal * Non interactive decoupling of o/p signal. SPEED SENSOR:-
BHEL
EHTC
BHEL
EHTC
BHEL
TRANSMITTER P.S:-
For hall probe:-const current source. For jakie probe:-const voltage source.
EHTC
BHEL
EHTC
BHEL
AFUAA
Converts rectangular frequency pulses into DC voltage. Amplitude is proportional to frequency. Module takes operative voltage from LB. Other i/ps & outputs are hard wires. FUNCTIONS: Frequency to voltage converter V/I converter (4-20ma, 0-20ma isolated) P.S & P.S monitoring.
EHTC
BHEL
EHTC
BHEL
AVLAA
APPLICATION: used to actuate electrohydralic converters. module receives only operating voltage from bus. other I/O s are hardwired. FUNCTIONS:*SUMMATION & POWER AMPLIFIER. *LIMIT VALUE MONITOR. *LOAD ISOLATION. *POWER SUPPLY.
EHTC
BHEL
AVLAA
SUMMATION: upto 3 voltage signals can be summed at the input. input range is (0.+/-10v). summation unit output is given to two output amplifier of opposite polarity. LIMIT VALUE MONITER:Detects o/p short circuit (short circuit to M) and SME 2 becomes High. LOAD ISOLATION:Amplifier o/ps are connected via NC contacts for load isolation.
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
Lmu10b sup+o/p
EHTC
BHEL
LMU 10B:
LMU10B:Power Transduser Module [Iskamatie A] USE: To achive practically instantaneous measurement of three phase active power. it is insensitive to environmental conditions such as electromagnet field. This power transducer consists of two modules. 1. Transducer module LMU BGW11 2. Electronic module LMuV- BGE11. 1.TRANSDUSER MODULE [BGW11]: Consists of two current transformer, two voltage transformer and zener diode for suppressions of surge voltage. Its design ensure that possible surge voltages in the measurement circuits cannot reach the subsequent electronic system. 2.ELECTRONIC MODULE : [BGE11] Consists of two adjacently positioned PCBs. Component needed for adjustment and measurement purpose are accessible from front panel.
EHTC
BHEL
LMU 10 B:
BHEL
LMU 10 B:
DATA: POWER SUPPLY :- +24 VOLTS (18 30V) Power dersipation : max 12w Storage, transport temp :- -40degree c to +70 degree c Analog inputs current : 0 1A OR 0 5A. voltage : 100125v. frequency: 50 60 Hz
EHTC
BHEL
LMU 10 B:
Analog output : current : 020ma OR 420ma voltage signal : 0 10 v (DC). Adjustment : relative gain Vrel by R11 (BGE11) to get desired current. CALIBRATION OF LMU10B LOAD MODULE PT ratio = 11KV/110V To be known. CT ratio= 6KA/5A to be known from customer. Calculation for 80mw: p=VIsqrt3 PRIMARY CURRENT Ipa= P / v sqt 3= 80x10000000 / 11000 x sqt3 =4.195 KA. ACTUAL SECONDARY CURRENT =4.195 X5 /6 = 3.499 A
EHTC
BHEL
LMU 10 B:
INPUT CURRENT (TEST) ADJUST BY R11 1. 0.00 AMP 2. 3.499 AMP 3. 1.75 A 4. 2.62 A OUTPUT CURRENT 4.0 MA 20 MA 12 MA 16 MA
X X
EHTC
BHEL
General arrangement
EHTC
BHEL
EHTC
BHEL
EHTC
BHEL
Bk + ipb connection
EHTC
BHEL
EHTC
BHEL
Standard wirings
EHTC
BHEL
70EB01
EHTC
BHEL
70EB02
EHTC
BHEL
70EB03
EHTC
BHEL
70AB01
EHTC
BHEL
70AB02
EHTC
BHEL
70EA01
EHTC
BHEL
70EA02
EHTC
BHEL
70EA03
EHTC
BHEL
70EA04
EHTC
BHEL
70AA01
EHTC
BHEL
70AA02
EHTC
BHEL
70AMD
EHTC
BHEL
70AS45
EHTC
BHEL
70AS47
EHTC
BHEL