Académique Documents
Professionnel Documents
Culture Documents
TRAINING
REPORT 2009
AT
(DCCPP)
DHOLPUR (RAJ.)
South West of Agra. Dholpur was considered an ideal location for setting
connected by roads (G.T. road passes through this city) and being an
The total estimated cost of the plant is Rs. 1155 crore.The main
equipments were supplied by M/s BHEL and it was also the main
BOP(Balance of plant) was given to M/s GEA Energy System. The main
fuel used for this plant is R-LNG(liquified natural gas) which will be
supplied by M/s GAIL. The gas required per day for both unit is 1.3MM
SCM at 9000Kcal.
The unique feature of this plant is that waste heat from the gas turbine is
control system has been introduced for the first time in the northern
region in INDIA.
PREFACE
Practical training in must for each and every student and especially for
be practical along with their practical knowledge. Today time need more
knowledge.
for each and every technical student along with theoretical knowledge.
GENERAL INTRODUCTION
Method for transforming other power into electrical power :-
Power plants are classified in the following categories according to the
fuel used:
(a) Coal based thermal power plant
(b) Nuclear power plant
(c) Hydro electric power plant
(d) Solar power plant
(e) Wind power
(f) Gas power plant Rotating turbines attached to electrical generators
produce most commercially available electricity. Turbines may be driven
by using steam. Water wind or other fluids as an intermediate energy
carrier. The most common usage is by steam in fossil fuel power plants or
nuclear power plants and by water in hydroelectric dams. Alternately
turbines can be driven directly by the combustion of natural gas.
(c.) Air Emissions :- The average emissions rates in the united states
from natural gas fired generation are 1135 ibd/meh of carbon dioxide 0.1
ibs/mwh of sulfur di oxide and 1.7 ibs/mwh of nitrogen oxide compared
to the average air emissions from coal fired generation natural gas
produces as much carbon dioxide less than a third as much nitrogen
dioxide at the power plant in addition the process of extraction treatment
and transport of the natural gas to the power plant generators additional
emissions.
(d) Design Principle :- In a gas turbine, set composed primarily of a
compressor burner and the gas turbine proper. The input temperature to
the gas turbine is relatively high but the output temp of the fuel gas
temperature is sufficient for production of steam in the second steam
cycle with live steam temperature in the range of steam cycle depends on
the ambient temperature .The methods of waste heat disposal either by
direct cooling by lake river or sea water or using cooling towers.
(e) Efficiency of CCGT plants :- The thermal efficiency of a combined
cycle power plant is normally in terms of the net power output of the
plant as a percentage of the lower heating value or net calorific value of
the fuel. In the case of generating only etc. criticity power plant
efficiencies of up to 59% can be achieved in the case of combined heat
and power generation the efficiency can increase to about 85%.
DCCPP located at Dholpur has an unique feature that the same energy
source (i.e. natural gas) is used to rotate both gas and steam turbine
without wasting much of energy. As the name implies it is a combined
cycle i.e. waste heat from the gas turbine is recovered by a heat recovery
steam generator to power a conventional steam turbine in a combined
cycle configuration. Hence, the working of both gas and steam turbine is
discussed here.
GAS TURBINE
WORKING OF GAS TURBINE:
turbine element.
Energy is released when compressed air is mixed with fuel and ignited in
the combustor . The resulting gases are directed over the turbine's blades,
spinning the turbine and mechanically, powering the compressor. Finally,
the gases are passed through a nozzle, generating additional thrust by
accelerating the hot exhaust gases by expansion back to atmospheric
pressure.
Energy is extracted in the form of shaft power, compressed air and thrust,
in any combination, and used to power electrical generators .
Theory of operation:
Gas Power Cycle :- Although any cycle may in principle be used as a heat engine or as
a refrigerator and heat pump by just reversing the direction of the process in practice
there are big difference and the study is split between power cycle and refrigeration
cycle.
Many gas cycle have been proposed and several are currently used to model real heat
engines. From the academic point of view we will the brayton cycle.
Brayton Cycle :- The brayton cycle named after the American Engineer
George Bray ton, is a good model for the operation of a gas turbines
engine. Now a days used by practically all aircraft except the smallest
once by fast boast and increasingly been used for stationary power
generation. Particularly when both power and heat are of interest the ideal
bray ton cycle in the T-S and P-V diagram and the regenerative cycle.As
with all cyclic heat engines, higher combustion temperature means
greater efficiency. The limiting factor is the ability of the steel, nickel,
ceramic, or other materials that make up the engine to withstand heat and
pressure. Considerable engineering goes into keeping the turbine parts
cool. Most turbines also try to recover exhaust heat, which otherwise is
wasted energy. the heat released from the exhaust gas has been absorbed
by many kms of tubing which line the boiler. Inside these tubes is water,
which takes the heat and is converted into steam at high temperature and
pressure. The type of boiler is called heat recovery steam generation
(HRSG) This steam at high temperature and pressure is sent to the turbine
where it is discharged through the nozzles on to the turbine blades. The
energy of the steam striking on the blades makes the turbine to rotate.
Coupled to the turbine is the rotor of the generator. So when the turbine
rotates the rotor of the generator turns. The rotor is housed inside a stator
having heavy coils of copper bars in which electricity is produced
through the movement of magnetic field produced by the rotor. Electricity
passes from stator winding to the transformer, which increases its voltage
level so that it can be transmitted over the lines to far off places.
The steam, which has given away its energy, is changed back into water
in the condenser. Condenser contains many kms of tubing through which
cold water is continuously pumped. The steam passing over the tubes
continuously loses heat and is rapidly changed back into water. But the
two waters i.e. the boiler feed water and cooling water must never mix.
Boiler water must be absolutely pure otherwise the tubing of the boiler
may get damaged due to the formation of salts inside the tubes due to the
presence of different impurities in water.
To condense large quantities of steam huge and continuous volume of
water is required. In some power stations same water has to be used again
and again because there is not enough water. So the hot water tracts are
passed through the cooling towers. The cooling towers are simply
concrete shells acting as a huge chimney creating a draught of air. The
design of cooling towers is such that a draught of air is created in the
upward direction. The water is sprayed at the top of the tower. As it falls
down the air flowing in the upward direction cools it. The water is
collected in a pond from where the water is recirculated by the pumps to
the condenser. Inevitably, however some of the water is taken taken away
by the draught of water in the form of vapours and it is this water with
familiar white clouds emerging from the cooling towers.
LP Feed Water
Steam Line
HP Feed Water
Cond. In/Out
HP Steam LP Steam
Drum Drum
GT HP HP HP HP HP LP LP LP HP
CPH
SH-II SH-I EVP-IIEVP-I ECO-II SH EVP-IIEVP-II ECO-I
Exhaust
DD GD DESH
Spray line
LP Main Steam
Line
STEAM TURBINE
Steam turbine auxiliary (STA) :-
1. H.P. & L.P. by pass system
2. shapt turning system
3. feed water system
4. air extraction water side.
5. cw make up and raw water system.
6. hub oil system.
7. tacking oil system.
8. hydrolic oil system.
9. glained steam system
(1) two glained steam
(a) fan
(b) cooler
(2) pressure can valve
10. cooling water circuit :-
to create low back pressure
11. cooling water pump :-
two pump are in service one is service & second is stained
12. cooling tower:-
fans is use in cooling.
13. lub water pump:-
3 pumps one is service of two is stained.
14. air extraction system:-
Steam side removes non condensable from steam turbine.
15. air ph system:-
load on turbines is lers.
We head up air.
It’s density is reduce
Mass flow is reduced
• Stator
– Stator Frame (Fabrication & Machining)
• Core Assembly
– Stator Core, Core Suspension Arrangement
• End Shield
• Stator Winding Assembly
– Stator Winding , Winding Assembly, Connecting Bus bar,
Terminal Bushing
• Rotor
– Rotor Shaft, Rotor Wedges, Rotor Coils, Wound Rotor, Rotor
Assembly
• Completing Assembly
– Bearing Assembly, Shaft Seal Assembly, Oil Catchers,
Insert Cover etc
• Exciter
• Auxiliary Systems
•
Parameter GTG
STG
MVA 132.3
148.4MVA
SPEED/FREQUENCY 3000/50
3000/50RPM/Hz
INNER CONNECTION OF
STATOR WINDING Y-Y
Y-Y
ISOLATORS:
Isolators are used to make or break the circuit on no load. They should never be
operated on load. The isolators installed in the sub station have a capacity
of 1250 amperes. They are double end break type, motor operated and
can be operated from local as well as remote.
Isolators
1. Tightening of the jumper clamps
2. Tightening of electrical connections
3. Cleaning of male female connections
4. Checking of fuses and replacement there F.
5. Checking of operation of isolators
Current transformers
1. Checking of oil level.
2. Checking of oil and leakage
3. Tightening of jumper clamps
4. Tightening of electrical terminal secondary connection
Lightning Arrestors
1. Tightening of jumper connections
2. Tightening of earthing connections
3. Checking of counter reading
4. Checking of porcelain part
5. Checking of grading current
Battery 220 V D. C.
1. Cleaning of battery terminals
2. Tightening of battery terminal connections
3. Recording of specific gravity and voltage of each cell.
Isolators
1. Cleaning of male female connections
2. Tightening of all the jumper clamps
3. Lubrication of control rotary post insulator with grease
4. Checking of proper operation of the isolator
5. Tightening of all the nuts and bolts
6. Cleaning the motor cubical
7. Tightening of all the terminal connections
8. Greasing the gear box of motor
9. Checking of all the fuses
10. Checking of operation of isolator from local/remote
Current Transformers
1. Checking / cleaning of porcelain part of CT
2. Checking of oil and level and stopping it if low
3. Checking of oil leakage and its stoppage
4. Checking of N2 pressure and maintaining it at 0.2 kg/cm2
5. Tightening of earthing connection
6. Checking of BDV value of CT oil
7. Tightening of all the secondary terminal connections
8. Cleaning of marshalling box and tightening of terminal connections
9. Recording of IR values of primary and secondary side of CT
10. Tightening of bushing clamps.
Capacitive Voltage Transformers
1. Checking of oil level and topping thereof
2. Checking of N2 pressure and maintaining it at 0.2 kg/cm2
3. tightening of jumper clamps.
4. Tightening of secondary connection
5. Recording of IR values of primary and secondary side
6. BD value of oil
Lightning Arrestors
Cleaning of porcelain part and checking
1. Tightening of earthing connection
2. Tightening of jumper connection
3. Recording of IR values
4. Checking of counter readings
5. Checking of grading current
EARTH SHIELDING
It is a mesh of wire upon the tower. Its main purpose is to protect the substation equipment
from direct lightning strokes. Metallic body of each equipment is properly earthed.
The earthing resistance of any switch yard is about 0.2 ohm. Before the building up of
the sub station earthing material of G. I. wire is buried in the ground whose depth
depends upon the moisture content of ground. Earthing electrodes are provided at
various points. This increases the number of parallel provided at various points. This
increases the number of parallel paths and hence resistance of earth decreases.
WORKING
The voice frequency if converted into electrical signal. These signals are super imposed
on a carrier frequency and transmitted on the line through a coupling capacitor. At
the receiving end wave trap does not allow the modulated signal to enter the
power circuit where as the coupling capacitor provides a low resistance path to
this signal. This signal is then given to the line matching unit. In the LMU this
frequency is matched and after wards filtration of signal is done. The signal is
demodulated and again converted into the voice signal, which is available at
phone receiver.
DIFFERENT TRANSFORMERS INSTALLED IN TRANSFORMER YARD:
Transformer is a static device which is used to change the voltage level keeping
the power and frequency same. In the plant transformer is one of the most
important equipment. In the whole plant, there are about 83 transformer installed
at various places to operate the auxiliaries.
5 Buccholz relay:
It is the most important protective device for internal faults. It is a gas-activated relay.
During any fault inside the winding light gases like hydrogen are generated. The
Buccholz relay is connected on the pipe between the conservator and the main tank.
These gases get struck in the Buccholz relay and cause the level of oil in the relay to
go down. Due to this a mercury switch is operated which makes the contact and given
a signal. In the beginning only an alarm is there. But if the fault persists and becomes
serious there is a second mercury switch, which gets operated and trips the
transformer. The various readings for the alarm and trip signal are:
Alarm signal - 220 mm Hg
Trip signal - 500 mm Hg
6 Tap changer:
Tap changers are provided in the transformer to get the desired output voltage by
changing the number of turns.
The tap changers are of two types:
DETAIL OF 220KV C. B.
• VOLTAGE : 245KV
• NORMAL CURRENT : 2000A
• LIGHTNING IMPULSE WITHSTAND VOLTAGE : 1050KV
• SHORT CIRCUIT BREAKING CURRENT : 40kA
• SHORT TIME WITHSTAND CURRENT & DURATION : 40KA,
3SEC.
• OPERATING SEQUENCE : O - 0.3sec.- CO – 3 min. –
CO
• GAS PRESSURE ( SF6) : 7. 0 bar.
• CLOSING & OPENING SUPPLY VOLTAGE : 220V DC
• AUXILIARY CIRCUIT SUPPLY VOLTAGE :Iph.240V AC, 415V AC.
• AIR PRESSURE : 21.5 BAR
• FREQUENCY : 50HZ
• MASS (Approx.) : 3800Kg.
UNIT AUXILIARY TRANSFORMER
GENERATOR TRANSFORMER
POWER: 90/120/160
MVA
HV VOLTAGE 230 KV
LV VOLTAGE 10.5KV
TRANSFORMER PERCENTAGE IMP 12.5 %
TRANSFORMER VECTOR GROUP YNd11
TAP +/- 5 % OF RATED
VOLTAGE
DC SYSTEM
BATTERIES
Main Building
• Wet cell battery bank
o 125 V Battery Bank – 1
o 125 V Battery Bank – 2
o 125 V Battery Bank – 3
o 125 V Battery Bank – 4
o 220 V Battery Bank – 1
o 220 V Battery Bank – 2
BATTERY ROOM
Battery room should be well ventilated, clean, dry and temperature moderate
(Damping is dangerous due to possibility of earth leakage from the battery)
Smoking is prohibited
Battery get best result at the room temperature between 20 – 35o C
ELECTROLYTE
It is a mixture of Acid and Pure Water (Distilled) with proper portion.
General value of proportion is 85 % water and 15 % acid.
Gravity to be maintained 1.200 + 0.005 in al the cells.
CAUTION
Batteries and Battery Room should be clean, dry and well ventilated.
Never allow a flame, cigarette near the batteries.
Wear old clothes or terylene when working with acid or electrolyte (Terylene
is resistant to dilute acid).
Never add water to acid. It will spurt dangerously
TEMPERATURE CORRECTION
The specific gravity of the electrolyte works with temperatire. Any reading
observed on the hydrometer should therefore be corredted to 270o C as all the
specific gravity values indicated by use are at 27o C
For every 1o C above 27o C add 0.007 to the specific gravity as read
on hydrometer
NORMAL OPERATION OF BATTERIES
Keep the battery on trickle charge continuously (25 hrs. each day) except
where it is on discharge or on Boost charge.
The trickle charge current shown on milli ammeter should be so adjusted that
the battery be kept fully charges without being over charged.
The trickle charging current should be so appropriate that it should neither be
too much trickle charge not too little trickle charge.
The value above 2.3 and below 2.25 volts per cell during routine checking it
found means adjustment of trickle charging current is required.