Vous êtes sur la page 1sur 22

GOLONGAN

PELANGGAN DIMENSI BERAT OLI PEMBATAS

PLN TRAFO LISTRIK (L X W X H) (KG) (LITER) AMPERE

250
200
160
125
100
3 Phase 3150 kVA 20kV / 400V 80
3 Phase 2500 kVA 20kV / 400V 63
3 Phase 2000 kVA 20kV / 400V
3 Phase 1750 kVA 20kV / 400V 50
3 Phase 1500 kVA 20kV / 400V 40
3 Phase 1250 kVA 20kV / 400V 1860 X 1215 X 1730 3705 815 32
3 Phase 1000 kVA 20kV / 400V 1830 X 1215 X 1660 3285 712 25
20

3 Phase 630 kVA 20kV / 400V 1600 X 960 X 1740 2665 615 16

3 Phase 500 kVA 20kV / 400V 10

3 Phase 400 kVA 20kV / 400V 1495 X 900 X 1615 1990 510 6.3
3 Phase 315 kVA 20kV / 400V 1360 X 810 X 1450 1415 285
3 Phase 250 kVA 20kV / 400V 1520 X 790 X 1290 1260 320
3 Phase 200 kVA 20kV / 400V 1240 X 790 X 1295 1115 282
3 Phase 160 kVA 20kV / 400V 1170 X 700 X 1185 955 276
3 Phase 100 kVA 20kV / 400V 1045 X 700 X 1150 690 188
3 Phase 50 kVA 20kV / 400V 1170 X 600 X 1080 615 160
3 Phase 25 kVA 20kV / 400V 1030 X 555 X 1020 415 120
1 Phase 50 kVA 20kV / 220V 560 x 670 x 1380 445 112
1 Phase 25 kVA 20kV / 220V 560 x 670 x 1250 335 88

trafo CSP 50kVA 860 x 765 x 1230 355 130


FAKTOR
DAYA PEMAKAIAN PEMAKAIAN METER Daya PLN

Kva CT AMPERE PT VOLT KALI SISTEM DISTRIBUSI PLN terpasang (VA)

8660 kVA 300/5 20.000/100 12000


6930 kVA 250/5 20.000/100 10000
5540 kVA 200/5 20.000/100 8000
4330 kVA 150/5 20.000/100 6000
3465 kVA 125/5 20.000/100 5000
2770 kVA 100/5 20.000/100 4000
2180 kVA 80/5 20.000/100 3200

1730 kVA 60/5 20.000/100 2400


1385 kVA 50/5 20.000/100 2000
1110 kVA 40/5 20.000/100 1600
865 kVA 30/5 20.000/100 1200 SISTEM SEKUNDER TM 20 kV
690 kVA 25/5 20.000/100 1000

630,000
555 kVA 20/5 20.000/100 800 -526,000
414,000
345 kVA 15/5 20.000/100 600 -329,000
279,000
240 kVA 10/5 20.000/100 400 -233,000

197,000
164,000
147,000
131,000
SISTEM SEKUNDER TR 220/380V 105,000
kWh 3P 4 kawat 220/380V 82,500
66,000
53,000
41,500
33,000

23,000
16,500
13,200
10,600
6,600
3,900

22,000
17,000
13,900
11,000

SISTEM SEKUNDER TR 220/380V 7,700


kWh 1P 2 kawat 220V 5500
4400
3500
2200
1300
900
450
250
PEMBATAS BEBAN

BREAKER AMPERE MOTOR

3 x 3200
3 x 2500
ACB 3 Phase 3 x 2000
3 x 1600
3 x 1250
3 x 1000
3 x 800
3 x 630
(3 x 500)
3 x 400
(3 x 335)
3 x 320
3 x 300
3 x 250
(3 x 225)
MCCB 3 Phase 3 x 200
3 x 160
3 x 125
3 x 100
3 x 80
3 x 63
3 x 50
3 x 40
3 x 35
3 x 25
MCB 3 Phase 3 x 20
3 x 16
3 x 10
3x6
3x4
3x2

1 x 100
1 x 80
1 x 63
1 x 50
1 x 40
1 x 35
1 x 25
MCB 1 Phase 1 x 20
1 x 16
1 x 10
1x6
1x4
1x2
1 x 1,2
1Phase 3 Phase Besar Ampere
3,200
2,500
ACB 2,000
1,600
1,250
1,000
800
630
400
320
300
250
MCCB 200
160
125
100
80
63
50
40
32
25
MCB MCB 20
16
10
6
4
2
KW HP A MCB (A) NFB (A) KONTAKTOR OVERLOAD KABEL
0.4 0.5 0.8 2
0.75 1 1.4 2
1.1 1.5 2.1 4
1.5 2 2.8 4
2.2 3 4.2 6
3 4 5.7 10
3.7 5 7 10
4.5 6 8.5 10
5.5 7.5 10.4 16
7.5 10 14.2 16
9 12 17.1 20
11 15 20.9 25
15 20 28.5 32
18.5 25 35.1 40 40
22 30 41.8 50
30 40 57 60
37 50 70.3
45 60 85.5
55 75 104.5
75 100 142.4
125
TEMBAGA STRIP
Standard PLN, Ukuran Kabel Minimal vs Ampere
SPLN - Standar PLN
AKLI (Asosiasi Kontraktor Listrik dan Mekanikal Indonesia)
Note : ukuran cross section kabel size dalam ø mm (jarak)atau mm² (area) ?

No KLASIFIKASI Daya ( VA )

1 Industri menengah 450


2 900
3 1,300
4 2,200
5 3,500
6 4,400
7 5,500
8 7,700
9 11,000

10 6,600
11 10,600
12 13,200
13 16,500
14 23,000
15 33,000
16 41,500
17 53,000
18 66,000
19 82,500
20 105,000
21 131,000
22 171,000
23 197,000
24 329,000
25 414,000
Minimal vs Ampere

ik dan Mekanikal Indonesia)


bel size dalam ø mm (jarak)atau mm² (area) ?

MCB ( Ampere ) NFB (Ampere)

2
4
6
10
16
20
25
35
50

3 x 10
3 x 16
3 x 20
3 x 25
3 x 35
3 x 50
3 x 63
3 x 82
3 x 100
3 x 125
3 x 160
3 x 200
3 x 250
3 x 300
3 x 500
3 x 630
MCCB (Ampere) KABEL

3 X 2,5 mm 2
3 X 2,5 mm 2
3 X 4 mm 2
3 X 4 mm 2
3 X 4 mm 2
3 X 4 mm 2
3 X 4 mm 2
3 X 6 mm 2
3 X 6 mm 2

4 X 4 mm 2
4 X 6 mm 2
4 X 10 mm 2
4 X 10 mm 2
4 X 16 mm 2
4 X 16 mm 2
4 X 25 mm 2
4 X 35 mm 2
4 X 50 mm 2
4 X 50 mm 2
4 X 70 mm 2
4 X 95 mm 2
4 X 120 mm 2
4 X 150 mm 2
4 X 240 mm 2
4 X 300 mm 2
SKUND (mm2) TRAFO

3 Phasa 25 kVA 20kV/ 400V 1


3 Phasa 50 kVA 20kV/ 400V
3 Phasa 100 kVA 20kV/ 400V 2
3 Phasa 160 kVA 20kV/ 400V
3 Phasa 200 kVA 20kV/ 400V 3
3 Phasa 400 kVA 20kV/ 400V
3 Phasa 500 kVA 20kV/ 400V 4
3 Phasa 630 kVA 20kV/ 400V
3 Phasa 1000 kVA 20kV/ 400V 5
3 Phasa 1250 kVA; 20kV/400V
3 Phasa 1500 kVA; 20kV/400V 6
3 Phasa 1750 kVA; 20kV/400V
3 Phasa 2000 kVA; 20kV/400V
3 Phasa 2500 kVA; 20kV/400V
3 Phasa 3150 kVA; 20kV/400V
No Daya ( VA ) TRAFO MCCB ( Ampere )
KABEL
TEBAL (mmLEBAR (mm) CAP (A)
3 15 184
3 20 245
3 25 300
3 30 350
3 35 405
3 40 470
3 50 570
4 15 235
4 20 305
4 25 365
4 30 430
4 40 540
5 20 345
5 25 415
5 30 480
5 40 610
5 50 740
5 60 865
5 80 1110
5 100 1345
6 25 460
6 30 535
6 35 675
6 40 815
6 50 955
6 60 1146
6 80 1528
8 100 1910
8 40 795
8 50 950
8 60 1110
8 80 1480
8 100 1850
10 30 700
10 40 800
10 50 1060
10 60 1200
10 80 1525
10 100 1800
10 120 2100
10 150 2625
10 160 2800
10 200 3500
12 100 2100
12 120 2520
15 100 2625
PENGANTAR TIPE LUAS KHA (A)
NO INTI KABEL PENAMPANG DALAM TANAH JARINGAN UDARA NO
(mm2) (30C) (40C)
1 TEMBAGA NYM 1.5 19 16 2
2.5 25 22
4 34 30
6 44 39
10 61 53
16 82 71
25 108 94
35 134 117

NYFGbY 10 69 60
16 89 80
25 116 105
35 138 130
50 165 160
70 205 200
95 245 245
120 280 285
150 315 325
185 355 370
240 415 435

NYRGbY 1.5 24 18
2.5 32 25
4 41 34
6 52 44
10 69 60

NYY 1.5 24 18
2.5 32 25
4 41 34
6 52 44
10 69 60
16 89 80
25 116 105
35 138 130
50 165 160
70 205 200
95 245 245
120 280 285
150 315 325
185 355 370
240 415 435
300 465 500

NYA 1.5 15 24
2.5 19 32
4 25 43
6 33 54
10 45 73
16 61 98
25 83 129
35 103 158
50 132 197
70 165 245
95 207 290
120 235 345
150 390
185 445
240 525
300 605
400 725
PENGANTAR TIPE LUAS KHA (A)
INTI KABEL PENAMPANG DALAM TANAH JARINGAN UDARA
(mm2) (30C) (40C)
ALUMINIUM AAAC 16 105
(ALL 25 135
ALUMINIUM 35 170
ALLOY 50 210
CONDUCTOR) 70 255
95 320
120 365
150 425
185 490
240 585
300 670
400 810
500 930
630 1085
800 1255
1000 1450

AAC 16 110
(ALL 25 145
ALUMINIUM 35 180
CONDUCTOR) 50 225
70 270
95 340
120 390
150 455
185 520
240 625
300 710
400 855
500 990
630 1140
800 1340
1000 1540
INTI TEMBAGA
LUAS NYM NYFGbY NYRGbY NYY NYA
PENAMPANG KHA (Ampere) KHA (Ampere) KHA (Ampere) KHA (Ampere) KHA (Ampere)

Dalam Jaringan Dalam Jaringan Dalam Jaringan Dalam Jaringan


(mm2) tanah udara tanah udara tanah udara tanah udara Dalam
(30C) (40C) (30C) (40C) (30C) (40C) (30C) (40C) pipa (30C)
1.5 19 16 24 18 24 18 15
2.5 25 22 32 25 32 25 19
4 34 30 41 34 41 34 25
6 44 39 52 44 52 44 33
10 61 53 69 60 69 60 69 60 45
16 82 71 89 80 89 80 61
25 108 94 116 105 116 105 83
35 134 117 138 130 138 130 103
50 165 160 165 160 132
70 205 200 205 200 165
95 245 245 245 245 207
120 280 285 280 285 235
150 315 325 315 325
185 355 370 355 370
240 415 435 415 435
300 465 500 465 500
400
500
630
800
1000
INTI ALUMINIUM
NYA AAAC AAC
KHA (Ampere) KHA (Ampere) KHA (Ampere)

Jaringan Dalam Jaringan Dalam Jaringan


udara tanah udara tanah udara
(40C) (30C) (40C) (30C) (40C)
24
32
43
54
73
98 105 110
129 135 145
158 170 180
197 210 225
245 255 270
290 320 340
345 365 390
390 425 455
445 490 520
525 585 625
605 670 710
725 810 855
930 990
1085 1140
1255 1340
1450 1540

Vous aimerez peut-être aussi