Easy UPS 3M - 60kVA – Runtime Table

Runtime Estimation in Munutes

E3MUPS60KH E3MUPS60KH E3MUPS60KH E3MUPS60KH E3MUPS60KH E3MUPS60KH E3MUPS60KH E3MUPS60KH E3MUPS60KH


% of load KVA KW
+ E3MCBC7A + E3MCBC7B + E3MCBC10A + E3MCBC10B + E3MCBC10C + E3MCBC10D + E3MCBC10E + 2 x E3MCBC7A + 2 x E3MCBC7B
5% 3 3 315 400 480 715 805 1000 1500 730 900
10% 6 6 150 190 240 350 395 525 775 345 435
20% 12 12 65 87 110 160 185 245 360 150 195
25% 15 15 49 66.5 88 125 140 190 280 115 150
30% 18 18 39 53.5 71.5 100 115 155 230 94.5 120
40% 24 24 26.5 37.5 51 73.5 83.5 115 165 66 88
50% 30 30 19 28 39 56 63.5 89 125 49.5 67
60% 36 36 14.5 22 31 44.5 50.5 72 100 39 53.5
70% 42 42 11.5 18 25.5 36.5 41.5 60 86 31.5 44
75% 45 45 10 16.5 23.5 33.5 38 55.5 79 29 40.5
80% 48 48 9.1 15 21.5 30.5 35 51 73 26.5 37.5
90% 54 54 7.3 12.5 18.5 26 30 44.5 63 22 32
100% 60 60 5.9 10.5 16 22.5 26 39 55.5 19 28
Easy UPS 3M - 80kVA – Runtime Table
Runtime Estimation in Munutes

E3MUPS80KH E3MUPS80KH E3MUPS80KH E3MUPS80KH E3MUPS80KH E3MUPS80KH E3MUPS80KH E3MUPS80KH E3MUPS80KH


% of load KVA KW
+ E3MCBC7A + E3MCBC7B + E3MCBC10A + E3MCBC10B + E3MCBC10C + E3MCBC10D + E3MCBC10E + 2 x E3MCBC7A + 2 x E3MCBC7B
5% 4 4 220 280 345 510 575 750 1100 510 640
10% 8 8 100 135 170 250 280 375 550 240 305
20% 16 16 44.5 61 81 115 130 175 260 105 140
25% 20 20 33.5 46.5 63 90.5 100 140 200 82.5 105
30% 24 24 26 37.5 51 73 83 110 165 66 87.5
40% 32 32 17.5 26 36 51.5 58.5 82.5 115 45.5 62
50% 40 40 12 19 27.5 39 44.5 63.5 91 34 47
60% 48 48 9.1 15 21.5 30.5 35 51 73 26.5 37.5
70% 56 56 6.8 12 17.5 24.5 28.5 42.5 60.5 21 30.5
75% 60 60 5.9 10.5 16 22.5 26 39 55.5 19 28
80% 64 64 5.1 9.9 14.5 20.5 23.5 36 51 17 25.5
90% 72 72 8.2 12 17 20 31 44 14.5 22
100% 80 80 6.9 10.5 14.5 17 27 38.5 12 19
Easy UPS 3M - 100kVA – Runtime Table
*
Runtime Estimation in Munutes
E3MUPS100KH E3MUPS100KH E3MUPS100KH E3MUPS100KH E3MUPS100KH E3MUPS100KH E3MUPS100KH E3MUPS100KH E3MUPS100KH
% of load KVA KW
+ E3MCBC7A + E3MCBC7B + E3MCBC10A + E3MCBC10B + E3MCBC10C + E3MCBC10D + E3MCBC10E + 2 x E3MCBC7A + 2 x E3MCBC7B
5% 5 5 170 220 275 400 455 595 885 395 500
10% 10 10 79 100 135 195 220 295 430 185 235
20% 20 20 33.5 46.5 63 90.5 100 140 200 82.5 105
25% 25 25 24.5 35.5 48.5 69.5 78.5 105 155 62.5 83
30% 30 30 19 28 39 56 63.5 89 125 49.5 67
40% 40 40 12.5 19 27.5 39 44.5 63.5 91.5 34 47
50% 50 50 8.5 14 20.5 29 33.5 49 70 25 35.5
60% 60 60 6 11 16 22.5 26 39 56 19 28
70% 70 70 4.2 8.7 13 18 21 32.5 46 15 23
75% 75 75 3.5 7.8 11.5 16 19 29.5 42 13.5 21
80% 80 80 2.9 7 10.5 14.5 17 27.5 38.5 12 19
90% 90 90 1.9 5.7 8.9 12 14.5 23.5 33 10 16.5
100% 100 100 1.2 4.7 7.5 10 12 20.5 28.5 8.4 14
Easy UPS 3M - 120kVA – Runtime Table
UPS with Classic Battery Cabinet

Runtime Estimation in Munutes


E3MUPS120KH E3MUPS120KH E3MUPS120KH E3MUPS120KH E3MUPS120KH E3MUPS120KH E3MUPS120KH E3MUPS120KH E3MUPS120KH
% of load KVA KW
+ E3MCBC7A + E3MCBC7B + E3MCBC10A + E3MCBC10B + E3MCBC10C + E3MCBC10D + E3MCBC10E + 2 x E3MCBC7A + 2 x E3MCBC7B
5% 6 6 135 180 225 330 370 490 725 320 405
10% 12 12 62.5 83.5 105 155 175 240 350 145 190
20% 24 24 26 37 50.5 72.5 82 110 160 65 87
25% 30 30 19 28 39 55.5 63 88 125 49 66.5
30% 36 36 14.5 22 31 44 50.5 71.5 100 39 53.5
40% 48 48 9.1 15 21.5 30.5 35 51 73 26.5 37.5
50% 60 60 5.9 10.5 16 22.5 26 39 55.5 19 28
60% 72 72 3.9 8.3 12.5 17.5 20 31 44.5 14.5 22
70% 84 84 2.5 6.4 10 13.5 16 25.5 36.5 11 18
75% 90 90 1.9 5.7 8.9 12 14.5 23.5 33 10 16.5
80% 96 96 1.5 5.1 8 11 13 21.5 30.5 9.1 15
90% 108 108 0.7 4 6.6 9 10.5 18.5 26 7.3 12.5
100% 120 120 0.1 3.2 5.4 7.3 8.9 16 22.5 5.9 10.5
Runtime Estimation in Munutes
E3MUPS120KH E3MUPS120KH
E3MUPS120KH E3MUPS120KH E3MUPS120KH E3MUPS120KH E3MUPS120KH
% of load KVA KW + E3MCBC10D + E3MCBC10E
+ 2 x E3MCBC10A + 2 x E3MCBC10B + 2 x E3MCBC10C + 2 x E3MCBC10D* + 2 x E3MCBC10E*
+ E3MCBC10A* + E3MCBC10B*
5% 6 6 490 725 815 1000 1500 770 1100
10% 12 12 240 350 395 520 770 375 555
20% 24 24 110 160 185 245 360 175 260
25% 30 30 88 125 140 190 280 140 200
30% 36 36 71.5 100 115 155 230 110 165
40% 48 48 51 73 83 110 165 82.5 115
50% 60 60 39 55.5 63.5 88.5 125 63.5 91
60% 72 72 31 44.5 50.5 72 100 51 73
70% 84 84 25.5 36.5 41.5 60 86 42.5 60.5
75% 90 90 23.5 33 38 55 79 39 55.5
80% 96 96 21.5 30.5 35 51 73 36 51.5
90% 108 108 18.5 26 30 44 63 31 44
100% 120 120 16 22.5 26 39 55.5 27 38.5

*Capacity only (two Classic Battery Cabinets must be present to support full load)
Easy UPS 3M - 160kVA – Runtime Table
UPS with Classic Battery Cabinet
Runtime Estimation in Munutes
E3MUPS160KH E3MUPS160KH E3MUPS160KH E3MUPS160KH E3MUPS160KH E3MUPS160KH E3MUPS160KH E3MUPS160KH E3MUPS160KH
% of load KVA KW
+ E3MCBC7A + E3MCBC7B + E3MCBC10A + E3MCBC10B + E3MCBC10C + E3MCBC10D + E3MCBC10E + 2 x E3MCBC7A + 2 x E3MCBC7B
5% 8 8 99 125 165 240 270 360 530 230 290
10% 16 16 43.5 59.5 79.5 110 125 175 255 105 135
20% 32 32 17 25.5 35.5 51 58 81.5 115 45 61.5
25% 40 40 12 19 27 38.5 44 63.5 91 33.5 47
30% 48 48 9.1 15 21.5 30.5 35 51 73 26.5 37.5
40% 64 64 5.2 10 14.5 20.5 24 36 51.5 17.5 26
50% 80 80 2.9 7 10.5 14.5 17.5 27.5 39 12 19
60% 96 96 1.5 5.1 8.1 11 13 21.5 30.5 9.1 15
70% 112 112 0.5 3.7 6.2 8.4 10 17.5 24.5 6.8 12
75% 120 120 0.1 3.2 5.4 7.4 9 16 22.5 5.9 10.5
80% 128 128 0 2.8 4.8 6.4 8 14.5 20.5 5.1 9.9
90% 144 144 0 2 3.7 4.9 6.3 12 17 3.9 8.2
100% 160 160 0 1.4 2.9 3.7 4.9 10.5 14.5 2.8 6.9

Runtime Estimation in Munutes


E3MUPS160KH E3MUPS160KH
E3MUPS160KH E3MUPS160KH E3MUPS160KH E3MUPS160KH E3MUPS160KH
% of load KVA KW + E3MCBC10D + E3MCBC10E
+ 2 x E3MCBC10A + 2 x E3MCBC10B + 2 x E3MCBC10C + 2 x E3MCBC10D* + 2 x E3MCBC10E*
+E3MCBC10A* +E3MCBC10B*
5% 8 8 360 530 595 780 1100 565 840
10% 16 16 175 255 285 380 560 275 405
20% 32 32 81.5 115 130 180 260 130 185
25% 40 40 63.5 91 100 140 200 100 145
30% 48 48 51 73 83 110 165 82.5 115
40% 64 64 36 51.5 58.5 82.5 115 59 84.5
50% 80 80 27.5 39 44.5 63.5 91.5 45 64.5
60% 96 96 21.5 30.5 35 51 73 36 51.5
70% 112 112 17.5 24.5 28.5 42.5 60.5 29.5 42
75% 120 120 16 22.5 26 39 55.5 27 38.5
80% 128 128 14.5 20.5 23.5 36 51 25 35.5
90% 144 144 12 17 20 31 44 21.5 30.5
100% 160 160 10.5 14.5 17 27 38.5 18.5 26

*Capacity only (two Classic Battery Cabinets must be present to support full load)
Easy UPS 3M - 200kVA – Runtime Table
UPS with Classic Battery Cabinet
Runtime Estimation in Munutes
E3MUPS200KH E3MUPS200KH E3MUPS200KH E3MUPS200KH E3MUPS200KH E3MUPS200KH E3MUPS200KH E3MUPS200KH E3MUPS200KH
% of load KVA KW
+ E3MCBC7A + E3MCBC7B + E3MCBC10A + E3MCBC10B + E3MCBC10C + E3MCBC10D + E3MCBC10E + 2 x E3MCBC7A + 2 x E3MCBC7B
5% 10 10 74 98 125 180 205 275 405 170 220
10% 20 20 32 44.5 60.5 87 98.5 135 195 79 100
20% 40 40 12 19 27 38 43.5 62.5 90 33.5 46.5
25% 50 50 8.4 14 20.5 28.5 33 48.5 69 24.5 35
30% 60 60 5.9 10.5 16 22.5 26 39 55.5 19 28
40% 80 80 2.9 7 10.5 14.5 17 27 38.5 12 19
50% 100 100 1.2 4.7 7.5 10 12 20.5 29 8.5 14
60% 120 120 0.1 3.2 5.4 7.4 9 16 22.5 5.9 10.5
70% 140 140 0 2.2 4 5.3 6.7 13 18 4.2 8.6
75% 150 150 0 1.8 3.4 4.5 5.7 11.5 16 3.5 7.7
80% 160 160 0 1.4 2.9 3.8 4.9 10.5 14.5 2.9 6.9
90% 180 180 0 0.9 2.1 2.6 3.6 8.8 12 1.9 5.6
100% 200 200 0 0.4 1.4 1.7 2.6 7.4 10 1.1 4.6

Runtime Estimation in Munutes


E3MUPS200KH E3MUPS200KH
E3MUPS200KH E3MUPS200KH E3MUPS200KH E3MUPS200KH E3MUPS200KH
% of load KVA KW + E3MCBC10D + E3MCBC10E
+ 2 x E3MCBC10A + 2 x E3MCBC10B + 2 x E3MCBC10C + 2 x E3MCBC10D* + 2 x E3MCBC10E*
+E3MCBC10A* +E3MCBC10B*
5% 10 10 275 405 455 600 890 435 645
10% 20 20 135 195 220 295 430 210 310
20% 40 40 62.5 90 100 135 200 100 145
25% 50 50 48.5 69 78.5 105 155 78 110
30% 60 60 39 55.5 63 88.5 125 63 90.5
40% 80 80 27 38.5 44 63.5 91 45 64
50% 100 100 20.5 29 33 48.5 69.5 34.5 49
60% 120 120 16 22.5 26 39 55.5 27 38.5
70% 140 140 13 18 21 32 45.5 22.5 31.5
75% 150 150 11.5 16 19 29.5 42 20.5 28.5
80% 160 160 10.5 14.5 17 27 38.5 18.5 26.5
90% 180 180 8.8 12 14 23.5 33 16 22
100% 200 200 7.4 10 12 20 28.5 13.5 19

*Capacity only (two Classic Battery Cabinets must be present to support full load)