Capacity Tables

Gross Cooling Capacity (kW)

Outdoor DB(°C) 40.60 46.10 51.70

Indoor WB(°C) 16.10 19.40 22.80 16.10 19.40 22.80 16.10 19.40 22.80

CFM DB(°C) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI

23.9 17.1 14.0 8.16 18.7 10.5 8.40 19.9 4.6 8.55 15.6 12.8 8.35 17.1 9.7 8.61 18.3 4.2 8.86 14.8 12.1 9.16 16.0 9.1 9.52 17.1 4.0 9.77
26.7 17.4 15.8 8.18 19.0 12.3 8.42 20.3 8.8 8.57 15.9 14.5 8.37 17.4 11.3 8.63 18.6 8.0 8.88 15.1 13.7 9.18 16.4 10.6 9.54 17.5 7.5 9.79
1920
29.4 17.8 17.1 8.20 19.4 15.9 8.44 20.7 12.3 8.59 16.2 15.6 8.39 17.8 14.6 8.65 19.0 11.3 8.90 15.4 14.8 9.20 16.7 13.7 9.56 17.8 10.6 9.81
32.2 18.1 17.8 8.22 19.8 18.0 8.46 21.2 15.6 8.61 16.6 16.2 8.41 18.1 16.5 8.67 19.4 14.3 8.92 15.7 15.4 9.23 17.0 15.5 9.59 18.2 13.4 9.84
23.9 17.7 14.9 8.36 19.3 11.1 8.60 20.5 4.8 8.75 16.2 13.6 8.55 17.7 10.2 8.81 18.9 4.5 9.06 15.4 12.9 9.36 16.6 9.6 9.72 17.7 4.2 9.97
26.7 18.1 16.7 8.38 19.7 13.9 8.62 21.0 9.2 8.77 16.6 15.3 8.57 18.1 12.8 8.83 19.3 8.4 9.08 15.7 14.5 9.38 17.0 12.0 9.74 18.1 7.9 9.99
2100
29.4 18.4 18.1 8.40 20.0 16.8 8.64 21.4 13.0 8.79 16.9 16.6 8.59 18.4 15.5 8.85 19.6 12.0 9.10 16.0 15.7 9.40 17.3 14.6 9.76 18.4 11.2 10.01
32.2 18.8 18.8 8.42 20.4 18.9 8.66 21.8 16.3 8.81 17.2 17.2 8.61 18.8 17.4 8.87 20.0 14.9 9.13 16.3 16.3 9.43 17.7 16.4 9.79 18.8 14.0 10.04
23.9 18.2 16.7 8.06 19.8 12.3 8.45 21.0 5.4 8.45 16.7 15.3 8.79 18.2 11.4 9.05 19.4 5.0 9.30 15.9 14.6 9.60 17.1 10.7 9.96 18.2 4.7 10.20
26.7 18.6 18.6 8.08 20.2 15.5 8.32 21.5 10.3 8.47 17.1 17.1 8.81 18.6 14.3 9.07 19.8 9.4 9.32 16.2 16.2 9.62 17.5 13.4 9.98 18.6 8.9 10.23
2500
29.4 18.9 18.9 8.10 20.6 18.9 8.34 21.9 14.5 8.49 17.4 17.4 8.83 18.9 17.4 9.09 20.1 13.3 9.34 16.5 16.5 9.64 17.8 16.4 10.00 19.0 12.6 10.26
32.2 19.3 19.3 8.12 21.0 19.1 8.36 22.3 18.1 8.51 17.7 17.7 8.85 19.3 17.5 9.12 20.5 16.7 9.37 16.8 16.8 9.67 18.2 16.5 10.03 19.3 15.7 10.28

R410A Tropical Split Type Technical Manual


Notes:
1. DB = Dry Bulb Temperature (°C), WB = Wet Bulb Te mperature (°C)
4. TGC = Total Cooling Capacity (kW)
5. SHC = Sensible Heating Capacity (kW)
6. PI = Power Input (kW)
Floor-standing Type
69