Vous êtes sur la page 1sur 1

CLIENT

PLAN CLÉ

SECTION 2

INGÉNIEUR
P2-1 P2-1.2 P2-1.3 1.5 P2-2 P2-3 P2-4 P2-5

ARCHITECTE
P.A.
D-1
P.A.
LESS

P2-H P.A.
CECD-24
LESS CEFD-24

D-1

STRUCTURE
E-1 CA-1
L-1

3.10

L-1 3.02
D-1 E-1
CA-1

P.A. LESS
CEFD-14
CECD-14
P2-J
• L'ENTREPRENEUR DEVRA VÉRIFIER TOUTES LES DIMENSIONS ET
CONDITIONS EXISTANTES SUR LE CHANTIER AVANT LE DÉBUT DES
TRAVAUX.
D-1 D-1
CA-1 CA-1 • AUCUNE DIMENSION NE SERA PRISE SUR CE PLAN POUR FIN DE
L-1 L-1 RELEVÉ À MOINS QUE CE PLAN SOIT UN ORIGINAL.

NOTES
• TOUTES OMISSIONS OU ERREURS DÉCOUVERTES PAR
L'ENTREPRENEUR OU AUTRES DEVRONT ÊTRE TRANSMISES À
3.09 L'INGÉNIEUR AFIN D'APPORTER LES MODIFICATIONS REQUISES
3.03 AVANT LE DÉBUT DES TRAVAUX.

E-1 • TOUTE REPRODUCTION OU UTILISATION TOTALE OU PARTIELLE DE


CECD-23 E-1
CE DOCUMENT EST STRICTEMENT INTERDITE À MOINS D'OBTENIR
CEFD-23 CECD-15 L'APPROBATION DE LA FIRME DESJARDINS EXPERT CONSEIL.
LESS
CEFD-15

P.A.
P2-K P.A.
P.A. CECR-02
CGZN-02
E-1
L-1
LESS
CECD-22 D-1
E-1 CEFD-22 P.A. CEFD-16 CA-1
CECD-16
3.04
3.08

P2-L

ÉMISSION
L-1
CA-1
D-1 ESC#3
305

CEFD-17
CECD-17

CEFD-19
CECD-19 P.A. 1 2022-04-08 DIRECTIVE ME-04 C.P.
0 2022-01-21 CONSTRUCTION C.P.
CECD-18
CEFD-18 CA-1
2020-07-10 PERMIS J.D.
L-1 No DATE ÉMIS POUR: PAR:
P.A. B-1
P.A.
P2-M CA-1 L-1
L-1 CA-1
D.O.
B-1 D-1

SCEAU
D-1 E-1
CA-1
DIMENSIONNEMENT DE LA
E-1 L-1
TUYAUTERIE D'ALIMENTATION
E-1 L-1 D-1 DIMENSION
D.O. NOMINALE (f.a.) FACTEUR
L-1 CA-1 D'ALIMENTATION
Ø TUYAU (po-mm)
APPAREILS EFD ECD EFD ECD TOTAL
3.07 3.05
CA-X ½Ø-15Ø - 3 - 3

L-X ½Ø-15Ø ½Ø-15Ø 0.75 0.75 1


3.06
B-X ½Ø-15Ø ½Ø-15Ø 1 1 1.4
P2-N

PROJET
D-X ½Ø-15Ø ½Ø-15Ø 1 1 1.4
E-X ½Ø-15Ø ½Ø-15Ø 1 1 1.4
LES ½Ø-15Ø ½Ø-15Ø 1.4 1.4
P2-N.4 LV - ½Ø-15Ø 1 1 1.4
NOTES:
1. LES DIMENSIONS DE LA TUYAUTERIE
3000 BLVD THIMENS,
D'ALIMENTATION D'EAU FROIDE ET D'EAU VILLE ST-LAURENT
CHAUDE DES APPAREILS SANITAIRES DOIT
ÊTRE CONFORME AU TABLEAU CI-DESSUS.
2. TOUS LES RACCORDEMENTS DES
APPAREILS DE PLOMBERIE SONT DE ½"∅-15
∅ POUR EFD ET ECD, SAUF INDICATION
CONTRAIRE. RACCORDER UN APPAREIL MÉCANIQUE

TITRE
SEULEMENT SUR LA TUYAUTERIE DE
1/2"Ø-15Ø
3. POUR LE DIMENSIONNEMENT DES TUYAUX
MAÎTRES, VOIR SCHÉMA AU PLAN M-501 & M-502 PLOMBERIE - DISTRIBUTION - 3e
TOTAL
DIMENSION
ØTUYAU DE FAÇON GÉNÉRALE
ÉTAGE SECTION 2
(f.a.) (po-mm) (SAUF INDICATION
EFD & ECD CONTRAIRE), LE
DIAMÈTRE DE LA
0À2 ½Ø-15Ø TUYAUTERIE
3À7 ¾Ø-20Ø D'ALIMENTATION
SERA
8 À 19 1Ø-25Ø DÉTERMINÉ SELON LA ÉCHELLE: 1 : 100
DESSINÉ PAR: G.SCRAIRE
20 À 37 1¼Ø-32Ø SOMME DES

20055
FACTEURS
38 À 72 1½Ø-40Ø
D'ALIMENTATION S'Y
73 À 271 2Ø-50Ø RAPPORTANT, TEL PRÉPARÉ PAR: G.SCRAIRE
QUE
272 À 580 2½Ø-65Ø SPÉCIFIÉ CI-CONTRE:
581 À 1100 3Ø-80Ø SELON UNE PERTE DE
PRESSION DE:
5.0 psi / 100'-0"
VÉRIFIÉ PAR: C.PETRAS
M-313