Technical Data

Table 19.1-16. Typical Data for 480 V Class K-Factor Rated DOE 2016 Efficient Dry-Type Transformers, Aluminum Wound 1
i kVA Frame Weight Losses in Watts Efficiency (T Rise +20º) % Regulation % Imp. X R Sound Efficiency Inrush
No Total at 25% 50% 75% Full 100% 80% T Rise T Rise T Rise Level dB at 3% Absolute Practical
Load Rise +20 Load PF PF +20 +20 +20 (per Load Max. Max.
ii NEMA 75 ºC
ST-20)
Type KT-4 K-Factor 4, 150 °C Rise DOE 2016 Efficient
1 15 939 228 64 517 97.5 97.5 96.9 96.3 3.4 3.9 3.9 2.1 3.3 45 97.89 211 70
30 940 437 121 641 97.9 98.2 97.9 97.5 2.1 2.5 2.7 1.4 2.1 45 98.23 589 196
45 940 438 125 1262 98.2 98.1 97.6 97.0 2.7 4.3 4.4 3.4 2.8 45 98.40 439 146
2 75 942 599 193 1803 98.4 98.3 97.9 97.4 2.3 4.2 4.1 3.9 2.3 50 98.60 731 244
112.5 943 978 256 2427 98.6 98.5 98.1 97.7 2.0 4.6 5.2 4.8 2.1 50 98.74 795 265
150 943 1237 350 2601 98.7 98.7 98.4 98.1 1.6 3.5 3.9 3.6 1.6 50 98.83 1341 447
225 944 1607 489 3344 98.8 98.8 98.6 4.7 1.4 55 98.94 1830 610
3 300 945 2193 592 4189 98.9 98.9 98.7
98.3
98.4
1.4
1.3
3.9
3.9
5.4
4.8 4.7 1.4 55 99.02 2024 675
Type KT-4 K-Factor 4, 115 °C Rise DOE 2016 Efficient
4 15
30

940

413

121

586

97.9

98.3

98.0

97.7

1.9

2.4

2.3

1.4

1.9
45
45
97.89
98.23

589

196
45 942 612 193 596 98.0 98.5 98.5 98.3 1.3 2.4 2.7 2.3 1.3 50 98.40 731 244
75 943 978 256 994 98.3 98.7 98.6 98.4 1.2 3.0 3.5 3.2 1.3 50 98.60 795 265
5 112.5 943 1237 350 1350 98.5 98.8 98.7 98.1 1.1 2.5 2.9 2.7 1.1 50 98.74 1341 447
150 944 1607 489 1374 98.5 98.9 98.9 98.8 0.8 2.6 3.3 3.2 0.9 55 98.83 1830 610
225 945 2193 592 2179 98.7 99.0 98.9 98.8 0.9 2.8 3.6 3.5 0.9 55 98.94 2024 675
6 Type KT-4 K-Factor 4, 80 °C Rise DOE 2016 Efficient
15 — — — — — — — — — — — — — 45 97.89 — —
30 940 438 125 467 98.0 98.4 98.3 98.1 1.5 2.7 2.8 2.3 1.7 45 98.23 439 146
7 45 942 619 193 543 98.0 98.6 98.5 98.4 1.1 2.4 2.4 2.3 1.3 50 98.40 731 244
75 943 978 256 910 98.4 98.7 98.7 98.5 1.1 3.0 3.5 3.2 1.3 50 98.60 795 265
112.5 944 1607 489 711 98.1 98.8 99.0 98.9 0.6 1.9 2.5 2.4 0.6 55 98.74 1830 610
8 150 944 1607 489 1264 98.5 98.9 98.9 98.8 0.8 2.6 3.3 3.2 0.9 55 98.83 1830 610
Type KT-13 K-Factor 13, 150 °C Rise DOE 2016 Efficient
15 939 228 64 517 97.5 97.5 96.9 96.3 3.41 3.9 3.9 2.1 3.2 45 97.89 211 70
9 30 940 395 121 641 97.9 98.2 97.9 97.2 2.10 2.5 2.5 1.4 2.1 45 98.23 589 196
45 942 594 193 649 98.0 98.5 98.4 98.2 1.39 2.4 2.8 2.3 1.3 53 98.40 731 244
75 943 1012 256 1078 98.3 98.6 98.5 98.3 1.36 3.0 3.5 3.2 1.3 53 98.60 795 265
10 112.5 943 1297 350 1463 98.5 98.7 98.6 98.1 1.22 2.5 3.2 2.7 1.1 53 98.74 1341 447
150 944 1607 489 1486 98.5 98.9 98.8 98.0 0.92 2.6 3.3 3.2 0.9 58 98.83 1830 610
225 945 2193 592 2356 98.7 99.0 98.9 98.1 0.97 2.8 3.8 3.5 0.9 58 98.94 2024 675
11 Type KT-13 K-Factor 13, 115 °C Rise DOE 2016 Efficient
15 940 412 91 294 97.2 98.0 97.9 97.5 1.1 1.4 1.6 0.3 0.4 45 97.89 410 137
30 940 413 121 586 97.9 98.3 98.0 97.7 1.9 2.4 2.3 1.4 1.9 45 98.23 589 196
12 45 942 612 193 596 98.0 98.5 98.5 98.3 1.3 2.4 2.7 2.3 1.3 53 98.40 731 244
75 943 978 256 994 98.3 98.7 98.6 98.4 1.2 3.0 3.5 3.2 1.3 53 98.60 795 265
112.5 944 1607 489 773 98.1 98.8 98.9 98.9 0.6 1.9 2.5 2.4 0.6 58 98.74 1830 610
13 150 944 1607 489 1374 98.5 98.9 99.0 98.8 0.8 2.6 3.3 3.2 0.9 58 98.83 1830 610
Type KT-13 K-Factor 13, 80 °C Rise DOE 2016 Efficient
15 — — — — — — — — — — — — — 45 97.89 — —
14 30 942 612 193 241 97.3 98.3 98.6 98.6 0.8 1.6 1.8 1.6 0.9 53 98.23 731 244
45 942 612 193 543 98.0 98.6 98.5 98.4 1.1 2.4 2.7 2.3 1.3 53 98.40 731 244
75 943 1237 350 551 98.0 98.7 98.8 98.8 0.7 1.7 2.0 1.8 0.8 53 98.60 1341 447
15 112.5 944 1607 489 711 98.1 98.8 99.0 98.9 0.6 1.9 2.5 2.4 0.6 58 98.74 1830 610
150 945 2193 592 891 98.3 98.9 99.0 99.0 0.5 1.9 2.4 2.3 0.6 58 98.83 2024 675
1 Typical values for aluminum windings. Refer to Pages 19.1-27–19.1-29 for typical data for copper windings. Up-to-date design data is available at
16 www.eaton.com.
Note: Performance data is based upon 480 V delta primary and a 208Y/120 V secondary for three-phase transformers; 240 x 480 V primary
and a 120/240 V secondary for single-phase transformers. Refer to Eaton for 5 kV class information. All data is subject to future revision.
17

18

19

20

21

For more information, visit: www.eaton.com/consultants CA08104001E


19.1-24 Distribution Dry-Type Transformers
April 2016
Sheet 19 030
Technical Data

Table 19.1-18. Typical Data for 480 V Class K-Factor Rated DOE 2016 Efficient Dry-Type Transformers, Copper Wound 1
i kVA Frame Weight Losses in Watts Efficiency (Trise +20°) % Regulation % X R Sound TP1 Inrush
No Total at 25% 50% 75% Full 100% 80% Imp. Level dB Efficiency Absolute Practical
Load Rise +20 Load PF PF Max. Max.
ii Type KT-4 K-Factor 4, 150 °C Rise DOE 2016 Efficient
15 940 — — — — — — — — — — — — 45 97.89 — —
1 30
45
940
942
458
677
118
206
575
590
98.0
97.9
98.3
98.5
98.1
98.4
97.7
98.3
1.9
1.3
2.5
1.7
2.4
1.9
1.9
1.3
1.7
1.2
45
50
98.23
98.4
511
1135
170
378
75 943 1099 251 1041 98.3 98.7 98.5 98.3 1.3 2.4 2.7 2.4 1.2 50 98.6 922 307
112.5 943 1337 350 1359 98.5 98.8 98.7 98.5 1.1 2.2 2.5 2.3 1.0 50 98.74 1638 546
2 150 944 1857 418 1828 98.6 98.9 98.7 98.5 1.1 2.8 3.4 3.2 1.1 55 98.83 1364 455
225 945 2478 561 2548 98.7 99.0 98.8 98.6 1.1 2.6 3.1 3.0 1.0 55 98.94 2120 707
Type KT-4 K-Factor 4, 115 °C Rise DOE 2016 Efficient
3 15 — — — — — — — — — — — — — 45 97.89 — —
30 940 417 118 528 98.0 98.4 98.2 97.9 1.7 2.53 2.5 1.9 1.7 45 98.23 511 170
45 942 684 206 543 97.9 98.5 98.5 98.4 1.2 1.69 1.7 1.3 1.2 50 98.4 1135 378
4 75 943 1083 251 961 98.4 98.7 98.6 98.4 1.2 2.42 2.2 2.4 1.2 50 98.6 922 307
112.5 943 1337 350 1257 98.5 98.8 98.8 98.6 1.0 2.20 2.5 2.3 1.0 50 98.74 1638 546
150 944 1857 418 1694 98.6 98.9 98.8 98.6 1.0 2.77 3.4 3.2 1.1 55 98.83 1364 455
5 225 945 2478 561 2361 98.8 99.0 98.9 98.7 1.0 2.56 3.1 3.0 1.0 55 98.94 2120 707
Type KT-4 K-Factor 4, 80 °C Rise DOE 2016 Efficient
15 — — — — — — — — — — — — — 45 97.89 — —
6 30 940 475 118 482 98.1 98.4 98.3 98.0 1.5 2.5 2.6 1.9 1.7 45 98.23 511 170
45 942 678 206 496 97.9 98.6 98.6 98.5 1.0 1.7 1.7 1.3 1.2 50 98.4 1135 378
75 943 1099 251 883 98.4 98.8 98.7 98.5 1.1 2.4 2.7 2.4 1.2 50 98.6 922 307
7 112.5 943 1337 350 1156 98.5 98.9 98.8 98.7 0.9 2.2 2.5 2.3 1.0 50 98.74 1638 546
150 944 1857 418 1563 98.6 98.9 98.9 98.7 0.9 2.8 3.4 3.2 1.1 55 98.83 1364 455
225 945 2478 561 2178 98.8 99.0 99.0 98.8 0.9 2.6 3.1 3.0 1.0 55 98.94 2120 707
8 Type KT-13 K-Factor 13, 150 °C Rise DOE 2016 Efficient
15 — — — — — — — — — — — — — 45 97.89 — —
30 940 475 118 575 98.0 98.3 98.1 97.7 1.8 2.5 2.6 1.9 1.7 48 98.23 511 170
9 45
75
942
943
678
1099
206
251
590
1041
97.9
98.3
98.5
98.7
98.4 98.3 1.3 1.7 1.7 1.3 1.2 53 98.4 1135 378
98.5 98.3 1.3 2.4 2.7 2.4 1.2 53 98.6 922 307
112.5 943 1337 350 1359 98.5 98.8 98.7 98.5 1.1 2.2 2.5 2.3 1.0 53 98.74 1638 546
10 150
225
944

1857

418

1828

98.6

98.9

98.7

98.5

1.1

2.8

3.4

3.2

1.1

58
58
98.83
98.94 —
164 455

Type KT-13 K-Factor 13, 115 °C Rise DOE 2016 Efficient
11 15 — — — — — — — — — — — — — 45 97.89 — —
30 940 475 118 528 98.0 98.4 98.2 97.9 1.7 2.5 2.6 1.9 1.7 48 98.23 511 170
45 942 658 206 543 97.9 98.5 98.5 98.4 1.2 1.7 1.9 1.3 1.2 53 98.4 1135 378
75 943 1115 251 961 98.4 98.7 98.6 98.4 1.2 2.4 2.8 2.4 1.2 53 98.6 922 307
12 112.5 — — — — — — — — — — — — — 53 98.74 — —
150 944 1857 418 1694 98.6 98.9 98.8 98.6 1.0 2.8 3.4 3.2 1.1 58 98.83 1364 455
225 — — — — — — — — — — — — — 58 98.94 — —
13 Type KT-13 K-Factor 13, 80 °C Rise DOE 2016 Efficient
15 — — — — — — — — — — — — — 45 97.89 — —
14 30
45
940
942
475
678
118
206
482
496
98.1
97.9
98.4
98.6
98.3
98.4
98.0
98.5
1.5
1.0
2.5
1.7
2.6
1.7
1.9
1.3
1.7
1.2
48
53
98.23
98.4
511
1135
170
378
75 943 1099 251 883 98.4 98.8 98.7 98.5 1.1 2.4 2.7 2.4 1.2 53 98.6 922 307
112.5 — — — — — — — — — — — — — 53 98.74 — —
15 150 — — — — — — — — — — — — — 53 98.83 — —
225 — — — — — — — — — — — — — 58 98.94 — —
1 Typical values for copper windings. Refer to Pages 19.1-20–19.1-26 for typical data for aluminum windings. Up-to-date design data is available at
16 www.eaton.com.
Note: Performance data is based upon 480 V delta primary and a 208Y/120 V secondary for three-phase transformers; 240 x 480 V primary
and a 120/240 V secondary for single-phase transformers. Refer to Eaton for 5 kV class information. All data is subject to future revision.
17

18

19

20

21

For more information, visit: www.eaton.com/consultants CA08104001E


Distribution Dry-Type Transformers 19.1-31
April 2016
Sheet 19 037
Dimensions

i
Outside
Width ii

Top 1

2
Outside
Height 3

4
Left Front

Outside 7
Length

8
Drawing 4

Figure 19.1-6. Enclosure Dimensional Drawings—Ventilated Transformers 9


Table 19.1-25. Ventilated Transformers—Approximate Dimensions in Inches (mm)
Frame Drawing Dimensions 10
Number Height Width Length

939 4 28.00 (711.2) 21.86 (555.2) 17.75 (450.8) 11


940 4 36.77 (934.0) 24.86 (631.4) 21.13 (536.7)
942 4 43.00 (1092.2) 30.50 (774.7) 24.00 (609.6)
943 4 50.92 (1293.4) 34.49 (876.0) 31.48 (800.0) 12
944 4 60.00 (1524.0) 38.00 (965.2) 33.45 (849.6)
945 4 60.00 (1524.0) 45.00 (1143.0) 36.00 (914.4)