Editeur

SCHEMA Raccordement BORNIER Centrale incendie GZ1-GZ2 Rev:


Bornier STANDARD pour tous les Site: SCx Date : Bornier
ADRESS C.I. AVANT
Description Incendie Carte/boucle X1 L&R adress
33A Bl 45FCB1 (rcup.) 1BB
33B M 1P1,5A L&R GZ2-CI 1A1
34A Bl 45FCB1 8 0BB
34B N 1P1,5NA 9 1P1,5A 0A1
39A Bl 45FM TC1A
39B N 1P1,5A EA-GZ1
40A Bl 45FM TC1R liaison en filerie
40B N 1P1,5A
41A Bl 45FM TC5A
41B N 1P1,5A MCC TC5/6/7
42A Bl 45FM TC5R
42B N 1P1,5A
37A Bl 45FB BT1A
37B N 1P1,5A LOCAL B.T.
38A Bl 45FB BT1R
38B N 1P1,5A
49A Bl 45FB CP4A
49B N 1P1,5A LOCAL B.T.
50A Bl 45FB CP4R
50B N 1P1,5A
43A Bl 45FB SC1
43B N 1P1,5NA S.T.
44A Bl 45FB SC1R
44B N 1P1,5NA
47A Bl 45FB CP1A
47B N 1P1,5NA S.T.
48A Bl 45FB CP1R
48B N 1P1,5NA
45A Bl 45FB SC1A
45B N 1P1,5A filerie SDC
46A Bl 45FB SC1R
46B N 1P1,5A
35A Bl 45FTA B1 (rcup.) TA1 et TA2 0BB
35B N 1P1,5A 0A1
36A Bl 45FL VB3 TA3 7BB
36B N 1P1,5A 7A1
53A N 5.6 (rcup.) FIRE 1 (existant) 2BB
53B Bl 2x5,2 2A1
52A N 5.7 (rcup.) FIRE 2 (existant) 5BB
52B Bl 2x5,2 5A1
51A 6BB
51B shunt L&R GZ2-CI 6A1
54A 3 0.372 6 0.372 (rcup.) 8 x FIRE (existant) 0BB
54B 4 1P1,5NA 7 7x1,5 0A1
RLA
6
10/11/2008
45FCB4 45FTB4 45FTB3 45FTB1 45FTB2

1P1,5NA


13 dtecteurs + mod. Exi
XLM3-H2
1P1,5NA
FIM2-H2

Boucle BAT. GZ1
Boucle BAT. GZ2

Boucle TC's GZ1 XLM2-H2
FIM-H1
LIM800/1
FIM-H2
LIM800/2
45FCB2 45FCB3 45FTB3
45FCB2 45FCB1 45FCB2


Boucle BAT. Sous-station
lectrique "Boutons
Poussoirs brise vitre"

45FB CP5
1P1,5NA
XLM2-H1
XLM3-H1
FIM2-H2
45FM TC6

Boucle BAT. Salle
Technique "Boutons
Poussoirs brise vitre"

45FB CP2

Boucle TC's GZ2
Boucle BAT. sous-station
lectrique "dtecteurs"


8 dtecteurs + mod. Exi
45FM TC7
1P1,5NA 1P1,5NA
45FB CP3


Boucle BAT. Salle
techniques "dtecteurs"
Boucle BAT. TA GZ2

XLM1-H1
LIM800/3
XLM1-H2
LIM800/4
Boucle BAT. TA GZ1
45FTAB2
Boucle BAT. SDC
( Mag 2/4)

FIM2-H1
L&R GZ1
XDI 11
L&R GZ2
XDI 18
L&R GZ1
XDI 11
L&R GZ1
XDI 11
B.P. FIRE 2 BAT. POMPES

L&R GZ1
XDI 07
FIM2-H2
CIM800/1

XLM4-H2
CIM800/3
L&R GZ1
XDI 08
XLM4-H1
CIM800/2
B.P. FIRE 1 BAT. TC's GZ1
45FTB2 45FTB1
L&R GZ1
XDI 07
8 B.P's. FIRE BAT. TC's GZ2

L&R GZ2
XDI 14
CIM
800
CIM
800
CIM
800
CIM
800
CIM
800
CIM
800
CIM
800
MAG2/4
CIM
800
45FCB1 (rcup.)
230V Bl TEN C1 Armoire TEN
0V N 3G2,5 R2V
Q115.1 Bl 70-38 Armoire EA-GZ1
Q115.1 N 3G25 RVFV
Q156.1 Bl 0-211 Armoire EA-GZ2
Q156.1 N 3G25 RVFV
.+V24 Bl ST5 C1 Repeater
.-V24 N 3G1,5 A Box SdC
62A Bl ST1 C1A transmit
62B N 1P1,5 TP A ST1
63A Bl ST1 C1B receive
63B N 1P1,5 TP A ST1
1A Bl 45FB SC17 SIRENE niv 2 SDC
1B N 1P1,5A
2A Bl 45FB SC16 SIRENE niv 1 L.T.
2B N 1P1,5A au dessus de la C.I.
10A Bl CI L&R GZ1/1
10B N 1P1,5NA
11A Bl CI L&R GZ1/2
11B N 1P1,5NA
13A Bl CI L&R GZ2/1
13B N 1P1,5NA
14A Bl CI L&R GZ2/2
14B N 1P1,5NA
18A Bl CI L&R GZ1/3
18B N 1P1,5NA
19A Bl CI L&R GZ2/3 relais rajouter
19B N 1P1,5NA
4A Bl CI L&R GZ2/5
4B N 1P1,5NA
3A Bl CI L&R GZ2/6
3B N 1P1,5NA
28A Bl CI L&R GZ2/7
28B N 1P1,5NA
29A Bl CI L&R GZ2/8
29B N 1P1,5NA
30A Bl CI L&R GZ2/9
30B N 1P1,5NA
31A Bl CI L&R GZ2/10
31B N 1P1,5NA
Trip L&R CCTA1,2,3 L&R GZ1-CI
31 1 1 1 1 21
32 2 2 2 Trip L&R CCTA1 (rcup) 2 22
131 3 3 3 10G1,5A 3 23
132 4 4 4 4 24
41 5 5 1 1 25
42 6 6 2 Trip L&R CCTA2 (rcup) 2 26
CI - REPEATER
vers H9
Bus
Liaison Ethernet CI - REPEATER , SDC
K103,2
GZ1
FIM SIR 1
Bornier
K108,3
GZ2
L&R GZ1 , XAU
L&R GZ1 , XAU
L&R GZ1 , XIN
L&R GZ2 , XAU
K103,1
GZ2
K108,5
GZ1
K103,2
GZ2
162INC
IOB3,6
4BB
L&R GZ2 , XDI 23,4
4A1
2BB
L&R GZ2 , XDI 23,2
2A1
Info cde gaz turbine
162INC
IOB3,5
3BB
L&R GZ2 , XDI 23,3
3A1
L&R GZ2 , XDI 23,0
0A1
SOLAR TA1 / ZF2090
15
6BB
L&R GZ2 , XDI 23,6
6A1
L&R GZ2 , XDI 23,1
1A1
0BB
L&R GZ1 , XAU
11
L&R GZ2 , XAU
12
25
26
4
161 INC
IOB2.2
Contact Feu BAT. GZ2
3
A.U. Incendie TA1
10
11
V50
1BB
Info cde Dluge GZ1
162INC
IOB3,4
1
2
21
22
160 INC
IOB1.5
Contact Feu TC's GZ1
23
24
160 INC
IOB1.3
Alim 230V de la C.I.
, dpart QS24 ALIM 230V , C.I.
Sirne niv.2 SDC

Alim REPEATER
Alim REPEATER SDC
CI - REPEATER
Liaison Ethernet CI - REPEATER , SDC
FIM SIR 2
vers H9
Bus
Coffret 125 /110Vdc
162INC
IFMR2
10
SOLAR TA2 / TS 295
11
SOLAR TA1 / TS 295
K103,1
GZ1
161 INC
IOB2.3
L&R GZ1
XAU
vers FB800
XT1
L&R GZ1
XAU
Bornes:
Sirne niv.1 L.T.
A.U. Incendie TA2
Contact Feu BAT. GZ1
Contact Feu TC's GZ2
Contact Feu TA1-2 GZ1
Dfaut centrale incendie
Alarme centrale incendie
Mode "TEST" C.I.
Contact Feu TA3 GZ2
Info cde Dluge GZ2
160 INC
IOB1.2
160 INC
IOB1.6
162INC
IOB3,7
relais
K160.7
relais
K160.8
162INC
IFMR1
Alim 110Vcc de la C.I.
, dpart QEA41 , 16A ALIM 110Vcc , C.I.
4G10
4G10
Alim 125Vcc de la C.I.
, dpart QEA33.4 , 16A ALIM 125Vcc , C.I.
141 7 12G1,5 7 3 10G1,5A 3 27
142 8 8 4 4 28
51 9 9 1 1 29
52 10 10 2 Trip L&R CCTA3 (rcup) 2 30
151 11 11 3 10G1,5A 3 31
152 12 12 4 4 32
11 1 .5-90 (rcup) 1
111 2 2x2,5 L&R GZ2-CI 3
21 M 0,373 1 0,373(rcup) 1
121 Bl 3X10 2 2x10 2
71 M 40-91 (rcup) 2
171 Bl 3G6 4
61 0.346 (rcup) 7
161 5G2,5 9
71 N rcup 7
171 Bl 2x5,2 9
11 L&R GZ2-CI 3
111 0.372 3 0.372(rcup) 4 commun
21 4X1,5 4 7x1,5
121 5 5
31 Bl 5.9 (rcup.) 6
131 N 2x4,3 8
N.A.
N.A.
51 N 5.8 (rcup) 5
151 Bl 2x4,3 8
N.A.
N.A.
CI DCS1
Liaison C.I. - switch MODBUS Switch pupitre SDC
Ethernet NA COM 183 SW1PORT 11 DCS
A 21A
B 21B
borne double tage
UKK5
V50
SOLAR TA3 / ZF2090
V50
SOLAR TA2 / ZF2090
15
Sirne BAT. Pompes
Sirne BAT. TC's GZ2
Gyrophare BAT. TC's GZ2
vanne Dluge GZ1
Gyrophare BAT. TC's GZ1
Dluge GZ2 ENCL
Sirne sous station ELEC
Gyrophare sous station ELEC
XAU
Bornes:
L&R GZ1
XAU
Bornes:
L&R GZ1
Xinc
L&R GZ1
Xinc
L&R GZ1
Xinc
L&R GZ2
Xinc
L&R GZ2
Xinc
L&R GZ1
Xinc
L&R GZ1
Xinc
SOLAR TA3 / TS 295
11
L&R GZ1
Xinc



vanne Dluge GZ2
vanne GAZ combust.
TA1-2-3 SOLAR
relais
K161.7B
10
Gyrophare BAT. Pompes
gyrophare n'existe pas
15
relais
K161.4B
relais
K161.6A
A.U. Incendie TA2
A.U. Incendie TA3
relais
K161.7A
relais
K160.1
relais
K160.4
relais
K161.8
relais
K161.4A
Sirne BAT. TC's GZ1
Fermeture Vanne GAZ
combust. TA1-2-3
relais
K161.5A
Dluge GZ1 ENCL
gyrophare n'existe pas
relais
K161.6B
relais
K161.5B
K160.8
relais
K161.1