AC Voltage drop calculation

Load(VA) -> 2222 80% RealLoad I(A) for Cal. VD


Breaker (A) -> 32 25.6 10.10 25.6
Cable Length(m) -> 40
Load(V) -> 230
Phase -> 1 *Note sqr(3)=1.732

XLPE XLPE
Cable 1P (mV/A/m) 3P (mV/A/m) Vdrop(V) Vd(%)
1 46 40 47.104 20.48
1.5 31 27 31.744 13.80
2.5 19 16 19.456 8.46
4 12 10 12.288 5.34
6 7.9 6.8 8.090 3.52
10 4.7 4 4.813 2.09
16 2.9 2.5 2.970 1.29
25 1.85 1.6 1.894 0.82
35 1.37 1.17 1.403 0.61
50 1.04 0.91 1.065 0.46
70 0.75 0.65 0.768 0.33
95 0.58 0.5 0.594 0.26
120 0.49 0.42 0.502 0.22

dia CSA #No.Wire


4 7.7 46.54 0.00
6 8.3 54.08 0.00
10 9.2 66.44 0.00
16 10.2 81.67 2 163.34
25 11.9 111.16 1 111.16
35 13.3 138.86 0.00
50 14.7 169.63 0.00
Sum CSA 274.51
No. Vd(hop1) Vd(hop2) Vd(hop3) Vd total %
1 0.842 4.170 5.013 2.18
2 0.842 5.267 6.109 2.66
3 0.842 4.8384 5.681 2.47
For auto cad 4 0.842 5.632 6.474 2.81
47.104 V (20.48%) 0.842 5.632 6.474 2.81
31.744 V (13.8%)
19.456 V (8.46%)
12.288 V (5.34%)
8.09 V (3.52%)
4.813 V (2.09%)
2.97 V (1.29%)
1.894 V (0.82%)
1.403 V (0.61%)
1.065 V (0.46%)
0.768 V (0.33%)
0.594 V (0.26%)
0.502 V (0.22%)

Size Pipe CSA PIPe inch


15 176.63 1/2
20 314.00 3/4
25 490.63 1
32 803.84 1 1/4
40 1256.00 1 1/2
50 1962.50 2

686.27
For auto cad Remark
5.013 V (2.18%) 5.013
6.109 V (2.66%)
5.681 V (2.47%)
6.474 V (2.81%)
6.474 V (2.81%)
2C VCT dia CSA #No.Wire Size Pipe CSA PIPe inch
4 14.5 165.05 0.00 15 176.63 1/2
6 16 200.96 0.00 20 314.00 3/4
10 20 314.00 0.00 25 490.63 1
16 23 415.27 1 415.27 32 803.84 1 1/4
25 27.5 593.66 0.00 40 1256.00 1 1/2
35 31 754.39 0.00 50 1962.50 2

Sum CSA 415.27 1038.16


AC Voltage drop calculation
Load(VA) -> 7000 80% RealLoad I(A) for Cal. VD
Breaker (A) -> 50 40 31.82 40
Cable Length(m) -> 75
Load(V) -> 230
Phase -> 1 *Note sqr(3)=1.732

THW THW
Cable 1P (mV/A/m) 3P (mV/A/m) Vdrop(V) Vd(%)
1 44 38 132.000 57.39
1.5 29 25 87.000 37.83
2.5 18 15 54.000 23.48
4 11 9.5 33.000 14.35
6 7.3 6.4 21.900 9.52
10 4.4 3.8 13.200 5.74
16 2.8 2.4 8.400 3.65
25 1.81 1.52 5.430 2.36
35 1.33 1.13 3.990 1.73
50 1 0.85 3.000 1.30
70 0.71 0.61 2.130 0.93
95 0.56 0.48 1.680 0.73
120 0.48 0.4 1.440 0.63

dia CSA #No.Wire


4 4.4 15.1976 0
6 5 19.625 0
10 6.4 32.1536 0
16 7.8 47.7594 2 95.5188
25 9.7 73.86065 1 73.86065
35 10.9 93.26585 0
50 12.8 128.6144 0
Sum CSA 169.37945
No. Vd(hop1) Vd(hop2) Vd(hop3) Vd total %
1 0.842 4.170 5.013 2.18
2 0.842 5.267 6.109 2.66
3 0.842 4.8384 5.681 2.47
For auto cad 4 0.842 5.632 6.474 2.81
132 V (57.39%) 0.842 5.632 6.474 2.81
87 V (37.83%)
54 V (23.48%)
33 V (14.35%)
21.9 V (9.52%)
13.2 V (5.74%)
8.4 V (3.65%)
5.43 V (2.36%)
3.99 V (1.73%)
3 V (1.3%)
2.13 V (0.93%)
1.68 V (0.73%)
1.44 V (0.63%)

Size Pipe CSA PIPe inch


15 176.625 1/2
20 314 3/4
25 490.625 1
32 803.84 1 1/4
40 1256 1 1/2
50 1962.5 2

423.448625
For auto cad Remark
5.013 V (2.18%) 5.013
6.109 V (2.66%)
5.681 V (2.47%)
6.474 V (2.81%)
6.474 V (2.81%)
DC Voltage drop calculation
Load(W) -> 4320 80% RealLoad I(A) for Cal. VD
Breaker (A) -> 100 80 80.00 80
Cable Length(m) -> 5
Load(V) -> 54

*Note: AIS ให้ drop ไดไ้ มเ่ กิน 3V


THW
Cable 1P (mV/A/m) Vdrop(V) Vd(%)
1 44 17.600 7.65
1.5 29 11.600 5.04
2.5 18 7.200 3.13
4 11 4.400 1.91
6 7.3 2.920 1.27
10 4.4 1.760 0.77
16 2.8 1.120 0.49
25 1.81 0.724 0.31
35 1.33 0.532 0.23
50 1 0.400 0.17
70 0.71 0.284 0.12
95 0.56 0.224 0.10
120 0.48 0.192 0.08
For auto cad
17.6 V
11.6 V
7.2 V
4.4 V
2.92 V
1.76 V
1.12 V
0.724 V
0.532 V
0.4 V
0.284 V
0.224 V
0.192 V